Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

E

ELECTRICAL
T

TESTER SPECIAL

Insulation assessment
of motors through
partial discharge testing
and analysis
By Markus Soeller and Alexander
Gorbunov
ISSUE 003 / 2021 EXTRACT

Extract article from Electrical Tester Issue I003 - Copyright 2021 Megger limited.

ARTICLE TITLE 1
E
T
Read the full Electrical Tester magazines here
Issue 1 Issue 2 Issue 3

Contents Contents Contents


Integration of EVs with the electric grid......7 Grid energy storage ................................. 7 Virtual testing of protection relays is real!.7
Geek Challenge 2....................................15 Instantaneous torque as a predictive Geek Challenge III - The solution.............25
maintenance tool.................................... 17
Motor insulation test voltages..................17 Testing high speed DC circuit breakers
Geek Challenge II The solution............... 26 ..............................................................27
Lesser-known facts about TTR testing that
are affecting your results..........................23 On-line testing of circuit breakers............ 29 Electrical hot spot inspection and
Partial discharge: an interview with the preventative maintenance.......................33
DC testing of vacuum integrity in MV
switchgear...............................................30 experts.................................................... 38 ELECTROPEDIA – The IEC vocabulary
A toolbox approach to fault location in LV ..............................................................39
Monitoring TT low-voltage distribution
systems....................................................37 power cables.......................................... 43 POWERED BY
Geek Challenge III ................................. 49 … Isobel Fraser-Underhill....................45
Professional development........................41
HVDC transmission – in 1904!................ 50 Insulation drying and oil processing of
A kit for earth testing...............................42
in-service transformers............................47
Have you ever heard of the Alexanderson Testing parallel resistances....................... 52
VLF testing on motors and generators
alternator?...............................................45 The high stakes of ignoring the mechanical ..............................................................57
A bird’s-eye view of the rise of transformer health integrity of a transformer............. 58
IEC 60255 1xx: Protection relay functional
electrical, dielectric testing.......................47 POWERED BY… Julie Pettit...................... 67 standards for all......................................63
Testing ROCOF protection........................52 End-to-end testing for line differential What is a knee point?.............................71
Global conferences..................................55 protection............................................... 69
BOOK CLUB Part 1 .................................77
Meeting the challenge of cable testing in Training and Education
in the COVID Era..................................... 76 Insulation assessment of motors
Bolivia......................................................56
through partial discharge testing and
The missing link in motor condition Excitation voltage options for PD analysis...................................................79
monitoring...............................................59 investigations on MV cables.................... 78
Surge and lightning arresters..................89
POWERED BY... Ken Petroff......................65 Book club............................................... 85
BOOK CLUB Part 2 .................................97
Protection testing the primary way...........66 Keeping a watchful eye on transformers.87
The IEEE GPECOM conference................99
Are your electrical workers Maximizing security of supply at Höchst
industrial park......................................... 95 Diagnostic testing of bushings..............107
up to par?................................................70
Static and dynamic resistance testing of The wrong call for contactors................114
Questions and answers - IEC61850..........72
transformer tap changers...................... 101 Understanding generator restricted
Read all about it.......................................74
Training opportunities and challenges:.. 110 earth fault (REF) protection and testing.......
............................................................117
Read all about it! .................................125
Q&A: Partial discharge..........................126
Motor inrush current.............................129
The importance of IEC 61850 in
relation to the smart grid......................135
Crossword corner.................................143

2
E
T
Letter from the Editor
Jill Duplessis

Dear readers,

I am very excited to bring you this latest issue of Electrical Tester magazine!

Before we begin, I’d like to recognise the excellent contributions from our
esteemed, non-Megger colleagues: Cedric Harispuru, Greg Steeves, Xicai Zhao,
Ersan Kabalci, Murty Yalla, Thierry Bardou, and Volker Leitloff. Thank you all!
Our ET readers are avid consumers of electrical testing content and are well-
served by having such varied voices discussing so many topics. Many years
ago, as a young engineer, I was tasked with leading the development of a
transformer field processing guide. What I would have given to have had Greg’s
article on this subject to aid me in sorting all of the approaches!

I also extend praises to my many Megger colleagues for their exceptional


articles. The process of producing such high quality content can be arduous and
is nothing short of a labour of love and care for our readers, who we hope will
be helped by their contributions.

As for such aforementioned topics, I’d like to highlight the article by Stan Zurek
and Dave Milner titled “What is a Knee Point?”. I commissioned this piece
as a dedication to my newly retired line manager, Jeremy Hewlett, and Stan
and Dave produced it beautifully. Jeremy was always one to emphasise the
importance of paying attention to ‘fundamental knowledge’ and I wanted to
honour that legacy in this article. Indeed, “what is a knee point?” was one of
his favourite examples! So whichever corner of the world this issue finds you,
Jeremy, this article is for you!

ET magazine is evolving and expanding, and to that end this issue features our
own Assistant Editor and Designer, Izzy Fraser-Underhill talking about her work
and life in our “Powered By” article. This is a great way to find out more about
her, and why she has my vote for President of the World! Furthermore, I’d like
to introduce you to my newest Assistant Editor for Copy, Léonie Alvey, who has
helped me proof and edit the articles in this issue and will continue to do so
going forward.

And finally, I am honoured to deliver a welcome message from Megger’s Group


Director, Andrew Dodds, which you can read on the next page. Andrew’s
extensive knowledge about the world of electrical testing is truly inspiring to me
and hopefully you’ll get a feel as to why.

My warmest regards to you all and enjoy this issue!

Jill

Letter from the full edition of ET I003

3
E
T

4 ARTICLE TITLE
E
T

Insulation
assessment of
motors through
partial discharge
testing and
analysis
By Markus Soeller and
Alexander Gorbunov

ARTICLE TITLE 5
E
T

Stator winding insulation systems in motors are resistant this has a microscopic structure such that a multitude of
to the effects of partial discharge (PD) which makes them small areas delaminate as the stator is heat cycled. If the
very different from the insulation systems used in almost streamer inception field strength is reached locally, these
all other applications where the ideal operating state is small areas of delamination support PD, which means
PD-free. Stator insulation can typically tolerate PD activity that even healthy new insulation will show PD activity.
for many years without it leading to failure.
The epoxy-mica insulation system is, for the most part,
Because stator insulation systems are designed to operate stable in the presence of PD but, on the other hand, all of
in a PD environment, there are currently no standards the degradation processes associated with this insulation
that define acceptance criteria for PD activity in rotating system result in PD. This makes PD measurement an
machinery. PD testing on rotating machines is therefore ideal tool for assessing the condition of a stator winding
a matter of trending measured results and comparing with the proviso that because even a new machine may
them with available reference data. Nevertheless, defects show PD activity, determining only the level of PD is
in stator insulation cause specific types of PD activity insufficient.
and this makes PD analysis the ideal tool for condition
assessment of generators and large motors. Practical PD measurements for motors
Proper choice of the frequency band allows PD patterns In practice, PD measurements on motors are carried out
(ϕ-q-n patterns) to be acquired that offer reasonable with the machine off-line. In addition to looking at the
coverage of the entire winding while minimising the amplitude of the PD, testing also includes analysis of the
effects of interference from external noise sources. PD patterns which, as we will see, helps to determine the
This article discusses the inherent resistance to PD of root cause of any issues detected. While useful on their
the epoxy-mica insulation systems used in rotating own, the value of PD tests is further enhanced if they
machines and the importance of choosing an appropriate are combined with loss factor measurements and other
bandwidth for PD measurements. It then reviews typical dielectric tests.
failure modes for stator winding insulation and the PD
patterns that they produce. As has already been mentioned, a complicating factor
for PD testing of motors is the lack of standards defining

Epoxy-mica insulation systems acceptance criteria. This situation often leads to lengthy
discussions between the owners and manufacturers of
The stator winding insulation in rotating machines machines when test reports are submitted, even when
is usually formed of mica tapes or flakes, and, in the reports relate to factory tests. In relation to this, it is
modern machines, epoxy resin is the usual choice for important to bear in mind that, as was explained earlier
impregnating the mica layers. For large generators, the in this article, even new machines will exhibit PD activity
traditional resin-rich impregnation is most often used and, in most cases, this is not an indicator of problems.
and, for large motors in particular, vacuum impregnation
To perform off-line PD tests, the machine must be
of the entire stator coil has become increasingly popular
taken out of service and isolated. The stator windings
in recent decades.
are then energised from a high-voltage source, which
In most applications, epoxy resin exhibits ‘treeing’ should ideally be PD-free. If it is not, the results will be
when subjected to PD activity, which ultimately leads a combination of PD from the voltage source and PD
to electrical breakdown. In rotating machines, however, from the motor, and it may be impossible to separate
the large number of mica barriers means that the the two components. If the high-voltage source does
formation of trees is stopped after a very short distance. exhibit significant PD, it should be used in conjunction
Subsequently, treeing in the resin can continue only with a filter. When carrying out the test, it is important
slowly on the surface of the mica barrier until it reaches to remember that the measurement conditions differ
the corner of the barrier, when it can grow further in the from those present when the machine is in operation. For
direction of the electric field. Turning now to the mica, example, the conductors will be cold; the environmental

6 ARTICLE TITLE
INSULATION ASSESSMENT OF MOTORS THROUGH PARTIAL DISCHARGE TESTING AND ANALYSIS
E
T

40 – 800 kHz (IEC60270) 2 – 20 MHz 20 – 200 MHz


1215697 Counts 110843 Counts 2270 Counts

„ 1200 kW – 6600 V asynchronous motor „ Off-line PD measurement, 60 s PD pattern


with internal neutral connection acquisition (coupling capacitor)
„ New VPI impregnated stator winding „ Same test object and test voltage,
different band pass filters
Figure 1: Three tests on the same motor

„ 800 kW – 6600 V asynchronous motor


with internal neutral connection
„ Off-line PD measurement (conventional
„ Internal PD activity in the main circuit acc. IEC 60270)
insulation (ground wall)
„ Available signal up to 5.5 MHz

Figure 2: Frequency spectrum for PD test

conditions – in particular, the relative humidity – may be useful information about the type of fault a machine may
different; and the electric field distribution within the be experiencing.
machine will be different, as the test is carried out with a
single-phase voltage source. Choosing PD measurement frequency
The results obtained are either compared with factory and bandwidth
acceptance or historical test results. This procedure
The choice of measurement frequency and bandwidth is
provides invaluable insights into the condition of the
critically important if reliably informative PD test results
stator windings and, if a PD analyser capable of capturing
are to be obtained. To understand these factors, it is
synchronised PD patterns is used, it can also provide
useful to briefly review the way in which PD signals are

INSULATION ASSESSMENT OF MOTORS THROUGH PARTIAL DISCHARGE TESTING AND


ARTICLE
ANALYSIS
TITLE 7
E
T

Figure 3: Defect locations in stator bars

produced. Almost invariably, they start as a gas discharge By examining the spectrum, it is possible to choose
in a void in the insulation, simply because the breakdown a combination of bandwidth and frequency that will
strength of the gas in the void is lower than that of the provide results with a good signal-to-noise ratio and will
surrounding dielectric material. In the void, an electron not be unduly influenced by external noise.
avalanche occurs, which is, in effect, a high frequency
Before looking at some actual test results and showing
current impulse with a very short rise time. In nitrogen,
how they can be used to classify types of failure, it is
which is the major constituent of air, the rise time is
important to mention calibration. All PD measurements
typically around 1 ns, which corresponds to a range of
are relative, and calibration is, therefore, essential to
frequencies up to 350 MHz.
compensate for the attenuation and other characteristics
This description, however, applies only to the pulse at its of the test circuit. Calibration, which should be performed
source. By the time it has reached the terminals where for every motor being tested and every time the test set
the test instrument is connected, the characteristics of up is changed significantly, involves injecting a test pulse
the pulse will have been substantially modified by high- of defined magnitude and adjusting the response of the
frequency effects that include attenuation, reflection, PD instrument accordingly.
resonance, dispersion, and radiation. This means that
Strictly (according to IEC60270, which provides guidance
there are no easy rules for choosing the best frequency
on PD testing in general), calibration is only valid
and bandwidth for making PD measurements. Lower
when using a bandpass filter at frequencies up to 1
frequencies and bandwidths are more prone to HF noise
MHz. However, PDIX instruments also support quasi-
but tend to yield PD signals with a larger amplitude and
integration, which is effective at higher frequencies.
allow PD to be detected over the entire winding. Higher
frequencies are less affected by noise but may provide
only partial coverage of the winding. Some of these Failure types and locations
effects can be seen in Figure 1, which shows the results The majority of failures in stator insulation systems fall
from three tests on the same motor, using different into the following categories:
frequencies and bandwidths.
„ Internal discharge activity caused by:
A helpful aid to determining the best frequency and
bandwidth for analysing PD tests on a specific motor is n Delamination of main insulation
to examine the frequency spectrum of the PD signals or conductor binding
produced – an example of which is shown in Figure 2. n Micro voids

8 ARTICLE TITLE
INSULATION ASSESSMENT OF MOTORS THROUGH PARTIAL DISCHARGE TESTING AND ANALYSIS
E
T

Symmetrical electrode configuration

„ Multiple voids of different sizes


„ Increased test voltage
„ Voltage shaped clusters (line type pattern)
„ Void and surface discharge

Figure 4: Void discharges

n Thermal ageing these voids become ionised. This leads to discharges that
produce PD impulses, which can be measured.
„ End winding (overhang) discharge caused by:
When the PD pattern resulting from the presence of
n Surface discharge due to contamination
voids is examined, typical line patterns are seen. The
n Bar-to-bar activity screen capture at the upper left in Figure 4 is an example
showing a pattern that indicates the likely presence
n Vibration
of seven individual voids. Over time, as the PD activity
„ Slot discharge caused by: progresses, there is more carbonisation in the voids, and
the availability of free electrons increases. The line pattern
n Wedge problems then changes into a more distributed pattern. The screen
n Inadequate impregnation capture at the top centre of Figure 4 shows a mixture of
void discharges that have progressed to produce the thin
„ Slot exit discharge caused by field grading problems almost-vertical lines and surface discharge, indicated by
„ External high frequency disturbances the humped parts of the pattern.

As can be seen in Figure 3, most failures occur at the Conductor binding delamination
stator bar. The electrical field strength is highest at the
corners, so the insulation in these areas are particularly tFigure 5 illustrates delamination close to the inner
vulnerable. Potential problems include delamination at conductor and it can be seen that the PD pattern shows
the inner conductor and delamination within the tape asymmetrical partial discharge activity with the highest
layers. amplitude in the positive half-cycle of the applied voltage.
In bipolar mode (left hand screen capture), the PD activity
The different failure modes are readily recognisable from for the first half cycle is shown below the x-axis. Unipolar
the unique PD signatures they produce, as the following mode (right hand screen capture) shows the activity in
examples show. the same relative phase position but entirely above the
x-axis. This pattern of high PD activity in the positive half
Voids cycle of

A typical void (indicated by the red arrow) is shown in


the micrograph at the bottom right of Figure 4. When
exposed to a sufficiently strong electric field, the gases in

INSULATION ASSESSMENT OF MOTORS THROUGH PARTIAL DISCHARGE TESTING AND


ARTICLE
ANALYSIS
TITLE 9
E
T

„ Main pattern properties:


„ Asymmetrical pulse distribution for both cycles
„ Dominant positive cycle
„ Delamination at inner conductor circuit
„ Normal ageing: frequent load cycling
(e.g. pump storage stations)

Figure 5: Conductor binding delamination

Asymmetrical electrode configuration

„ Predominantly in the negative half cycle


„ Often typical triangular pattern
„ Strongly load dependent due to magnetic forces
„ Delamination at the slot corona prevention layer
„ Consequent high Ozone (O3) generation
causing ‘collateral damage’

Figure 6: Slot discharge at machine bars

10 ARTICLE TITLE
INSULATION ASSESSMENT OF MOTORS THROUGH PARTIAL DISCHARGE TESTING AND ANALYSIS
E
T

Symmetrical electrode configuration

„ Similar pattern for both half cycles „ Cross-coupling of adjacent phase


„ Equal polarities and amplitudes „ Main insulation delaminations/voids
„ Often typical triangular pattern

Figure 7: Thermally aged main insulation

Contaminated overhang

„ Similar, often triangular, PD pattern „ Contaminated or moist insulation surface


for both half cycles (90°/270°)
„ Insufficient spacing between windings
„ Strongly voltage dependent discharge magnitude
„ Insufficient grading by the semi-conductive layer

Figure 8: End winding surface discharge

the applied voltage and lower activity in the negative half highest in the negative half cycle of the applied voltage.
cycle is very typical for conductor binding delamination. The bipolar pattern, which this time is on the right, clearly
shows that the PD in the negative half cycle starts close
Slot discharge at machine bars to the zero crossing of the applied voltage and forms
a trianglar shape. For this type of determination to be
Figure 6 illustrates a defect in the outer area of the made, it is essential that the phase relationship between
insulation. It can be seen that, compared with Figure 5, the applied voltage and the pattern display is correct.
the PD pattern is reversed, with PD activity being at its Hence, the synchronisation signal from the coupler is as

INSULATION ASSESSMENT OF MOTORS THROUGH PARTIAL DISCHARGE TESTING AND


ARTICLE
ANALYSIS
TITLE 11
E
T

Defect mechanism with vacuum impregnation systems

„ Thermal stress causes „ Discharge level: 10 – 50 nC


surface cracks
„ Gap grows due to the PD
„ Initial state: surface discharge ‘consuming’ insulation

Figure 9: Slot-exit PD activity – initial stage

important as the PD signal itself. This type of PD activity seen in the bottom right-hand photograph, where the
often produces ozone, and the longer the PD activity is white powder is again visible.
allowed to continue, the more damage this ozone will
cause. Slot-exit PD activity
Thermally aged main insulation The last example in this article concerns slot-exit PD
activity, and Figure 9 shows the initial phase of this.
Figure 7 shows a typical PD pattern for thermally aged
The activity has started at the point marked ‘A’ in the
main insulation. This pattern is symmetrical because the
photograph. At this time, the semiconductor tape is
PD activity occurs in the middle of the insulation layers
only partially destroyed, and the PD plot exhibits an
– in the tape layers – and is neither close to conductors
asymmetrical pattern with higher activity in the negative
nor to ground potential. The level of PD activity and the
half cycle of the applied voltage. Later, surface discharge
number of PD pulses is substantially the same in the
starts between the semiconductor tape and the inner
positive and negative half cycles. The right-hand screen
part of the stator bar. Ultimately, after a few months or a
capture in this figure demonstrates how useful high-
year, the condition develops to the point where the tape
resolution voltage measurement can be, as it reveals that
is eaten away completely, and the situation changes to
harmonics can have a strong influence on the PD pattern,
that shown in Figure 10.
in this case producing vertical striations.
The PD pattern is now different because there are
End winding surface discharge floating potentials. The pressure finger discharges directly
to the conductor, as illustrated in the upper left-hand
Figure 8 illustrates end winding surface discharge. The diagram in Figure 10. This floating activity affects the
white powder that can be seen in the photograph PD pattern so that it becomes flatter but with a much
at the top centre is either dust or the result of ozone greater amplitude than at the previous stage – typically
action, and it leads to surface discharge. At first sight 100 to 200 nanocoulombs (nC) compared with just a few
the PD pattern looks quite similar to that in Figure 7, nanocoulombs.
but closer inspection reveals that it is shifted a little to
the right, so that the maximum PD activity coincides
with the maximum applied voltage. This is because
surface discharge, which is due to contaminated or moist
insulating surfaces, is strongly voltage dependent. Surface
discharge can also occur when there is insufficient
spacing between interphases. An example of this can be

12 ARTICLE TITLE
INSULATION ASSESSMENT OF MOTORS THROUGH PARTIAL DISCHARGE TESTING AND ANALYSIS
E
T

Figure 9: Slot-exit PD activity – initial stage

Defect mechanism with global vacuum impregnation

„ Loss of dielectric strength to ground potential


„ Discharge to the pressure finger, plate or stator core
„ Final stage: floating potential discharge
„ Strong discharge amplitude Qp > 100 nC

Figure 10: Slot-exit PD activity – final stage

Summary
These off-line measurements provide dependable
We have seen that stator winding systems are PD
verification of insulation condition in machines at every
resistant and can tolerate PD activity for many years
stage in their life cycle: after manufacturing, during
without this leading to failure. Nevertheless, dielectric
the first months of operation and during subsequent
assessments are just as important as vibration
maintenance outages. Further, they are an excellent
measurement when it comes to ensuring the future
guide to the need for repairs to maintain machine
reliability of rotating machines. PD detection and
performance and reliability. PD testing is a practical
analysis can make an important contribution to these
solution for practical problems and, used appropriately, it
assessments, but it is necessary to trend the results and
can lead to big savings and big reductions in unplanned
compare them with available reference data because
downtime.
there are currently no defined acceptance criteria for PD
testing.

To ensure that PD testing gives the best possible results,


careful attention must be given to frequency and
bandwidth selection, to calibration, and to the use of
recommended measurement circuits. Provided that this
is done, analysis of the phase-resolved partial discharge
pattern will give invaluable information about the type or
types of partial discharge within a machine and locations
involved.

INSULATION ASSESSMENT OF MOTORS THROUGH PARTIAL DISCHARGE TESTING AND


ARTICLE
ANALYSIS
TITLE 13
E
T

Electrical Tester team


Jill Duplessis Isobel Fraser-Underhill
Editor Designer and Assistant Editor

Jill Duplessis is the Global Technical this, she gained over 17 years of experience The Group Graphic designer for Megger,
Marketing Manager for Megger. Her in the condition assessment of substation Isobel graduated University of Kent in
focus is on content strategy and content assets, first as a Principal Engineer at Doble 2005 with BA Hons in Visual design and
development for marketing and business Engineering Company and following as a Advertising, working within the design
segment initiatives. Jill is editor of Megger’s Primary Manager and Regional Application industry for over 15 years in various B2B
Electrical Tester magazine. She is the Specialist, Transformers, for OMICRON and B2C companies. Isobel joined Megger
primary author of Megger’s Transformer electronics USA. She has prior electric in July 2013 focusing on the companies
Life Management (TLM) bulletin series utility work experience (with Florida Power Visual Identity and Creative operations.
and author of many articles, papers and Corporation, now part of Duke Energy, Isobel has been the Designer and Assistant
a book titled Electrical Field Tests for the and Georgia Power Company), where she Editor of the Electrical Tester publication
Life Management of Transformers. Prior to enjoyed an exposure to a wide breadth of since 2013.
her move to Megger, Jill was Director of engineering functions. Jill received a BSEE
Power Programs for a start-up company degree from Georgia Institute of Technology
in Washington D.C., where she was in 1991 and completed extensive master
responsible for developing, testing and studies in electrical power engineering at
deploying new applications of (intensity Rensselaer Polytechnic Institute, Troy, NY.
modulated) optical monitoring systems for
transmission and distribution utilities. Before

14 ARTICLE TITLE
E
T

Editorial contributors

Léonie Alvey Keith Wilson The rights of the individuals Views expressed in Electrical
attributed in Electrical Tester are not necessarily
Assistant Editor Technical Copywriter/Editorial Tester to be identified as the views of Megger.
Contributor authors of their respective
Prior to working as the Group Content articles has been asserted All trademarks used herein
Editor for Megger, Léonie graduated from Keith is a qualified electrical engineer with by them in accordance are the property of their
with the Copyright, Designs respective owners. The use
Swansea University in 2010 with BA Hons experience in designing and commissioning and Patents Act 1988. of any trademark in this text
in Egyptology and Classical Civilisations. control systems, principally for mechanical © Copyright Megger. does not imply trademark
Shortly after this time, she began a career handling and process plant. He is a lifelong All rights reserved. No ownership rights in such
part of Electrical Tester trademarks, nor does use
writing, editing and proofreading for PR member of the Institution of Engineering may be reproduced in of such trademarks imply
agencies, magazines, web content and and Technology and is now a well-known a retrieval system, or any affiliation with or
technical author. transmitted in any form or endorsement of Electrical
sales content across a wide range of by any means, electronic, Tester by such owners.
industries, both B2B and B2C. Since joining mechanical, photo-copying,
Megger in 2016, Léonie has concentrated Oana Baetica recording or otherwise Megger Limited
without the prior written Archcliffe Road Dover
on improving the quality of written work Copywriter/Editorial Contributor permission of Megger. Kent CT17 9EN
across all sectors of the business while also T +44 (0)1304 502100
Oana is an experienced technical To request a licence to E electricaltester@
growing and maintaining Megger’s global
content contributor. She holds an MA use an article in Electrical megger.com
LinkedIn channel. Tester, please email www.megger.com
in Communication and PR, speaks five electricaltester@Megger.
languages and is currently studying for a com, with a brief outline of
PhD in Linguistics. the reasons for your request.

ARTICLE TITLE 15
ELECTRICAL
TESTER SPECIAL

ELECTRICAL TESTER MAGAZINE I003 2021 - EXTRACT


The rights of the individuals attributed in Electrical Tester to be identified as authors of their respective articles has been asserted by them in accordance with
the Copyright, Designs and Patents Act 1988. © Copyright Megger. All rights reserved. No part of Electrical Tester may be reproduced in a retrieval system, or
transmitted in any form or by any means, electronic, mechanical, photo-copying, recording or otherwise without the prior written permission of Megger.

You might also like