Professional Documents
Culture Documents
21 PSC Design (Eurocode) - Completed Model
21 PSC Design (Eurocode) - Completed Model
21 PSC Design (Eurocode) - Completed Model
Position Information J
1.Design Condition
1.1 Design Parameters
- Partial factors for ultimate limit states (EN 1992-1-1:2004, 2.4.2.4)
Design Situations γc for concrete γs for reinforcing steel γs for prestressing steel
Persistent & Transient 1.500 1.150 1.150
Accidental 1.200 1.000 1.000
- factor αcc , αct : Coefficient for long term effects on Compression and Tensile Strength.
αcc = 0.850 (for the Compressive strength)
αct = 1.000 (for the Tensile strength)
- Calculate Fc , Fs , Fp
x = 172.9 mm
Fc = ( λㆍx )ㆍ( ηㆍfcd ) = 26642.188 kN
Fs'= fs'ㆍAs' = 3824.557 kN
Fs = fsㆍAs = 2076.188 kN
Fp = ∑Fpi = 28403.378 kN
where, x is neutral axis depth
■ Negative Moment
1 Check Moment Resistance, MR,d
- Design Load
Load Combination Name : ULS1
Design Situations : Persistent & Transient
Load Combination Type : MY-MIN
MEd = -53937.346 kNㆍm
- Calculate Fc , Fs , Fp
x = 421.9 mm
Fc = ( λㆍx )ㆍ( ηㆍfcd ) = 31095.692 kN
Fs' = fs'ㆍAs' = 2076.188 kN
Fs = fsㆍAs = 3824.557 kN
Fp = ∑Fpi = 29332.035 kN
where, x is neutral axis depth
3.Shear Resistance
■ Maximum Shear Force
1 Check shear resistance of Concrete, V_Rd,c
- Design Load
Load Combination Name : ULS1
Design Situations : Persistent & Transient
Load Combination Type : FZ-MAX
NEd = -12999.851 kN
VEd = 9297.999 kN
MEd = -49206.477 kNㆍm
Vp = -66.116 kN
- Design value for the shear resistance VRd,s (EN 1992-1-1:2004, 6.2.3(3)~(4))
VRd,max = αcwㆍbwㆍzㆍν1ㆍfcd / (cotθ + tanθ) = 13472.228 kN
VRd,s = (Asw / s)ㆍzㆍfywdㆍcotθ ≤ VRd,max
= 9500.443 kN ≥ VEd = 9297.999 kN OK
where, ν1 = ν = 0.504
αcw = 1 + σcp / fcd = 1.092 ( for 0 < σcp ≤ 0.25ㆍfcd )
σcp = NEd / Ac = 2.094 MPa
NEd = 12999.851 kN (if compression, NEd > 0)
Ac = ### mm2
ν = 0.6ㆍ(1 - fck/250)
ν1 is a strength reduction factor for concrete cracked in shear
αcw is a coefficient taking account of the state of the stress in the compression chord
- Design value for the shear resistance VRd,s (EN 1992-1-1:2004, 6.2.3(3)~(4))
VRd,max = αcwㆍbwㆍzㆍν1ㆍfcd / (cotθ + tanθ) = 13472.458 kN
VRd,s = (Asw / s)ㆍzㆍfywdㆍcotθ ≤ VRd,max
= 9500.443 kN ≥ VEd = 5614.402 kN OK
where, ν1 = ν = 0.504
αcw = 1 + σcp / fcd = 1.092 ( for 0 < σcp ≤ 0.25ㆍfcd )
σcp = NEd / Ac = 2.094 MPa
NEd = 13002.467 kN (if compression, NEd > 0)
Ac = ### mm2
ν = 0.6ㆍ(1 - fck/250)
ν1 is a strength reduction factor for concrete cracked in shear
αcw is a coefficient taking account of the state of the stress in the compression chord
4.Torsional Resistance
■ Maximum Shear Force
1 Design Load
Load Combination Name : ULS1
Design Situations : Persistent & Transient
Load Combination Type : FZ-MAX
NEd = -12999.851 kN
VEd = 9297.999 kN
TEd = 2101.376 kNㆍm
MEd = -49206.477 kNㆍm
- Design value for the shear resistance VRd,max (EN 1992-1-1:2004, 6.2.3(9))
VRd,max = αcwㆍbwㆍzㆍν1ㆍfcd / (cotθ + tanθ) / NWeb
= 6736.114 kN ≥ V*Ed = 4821.143 kN OK
where, ν1 = ν = 0.504
αcw = 1 + σcp / fcd = 1.092 ( for 0 < σcp ≤ 0.25ㆍfcd )
σcp = NEd / Ac = 2.094 MPa
NEd = 12999.851 kN (if compression, NEd > 0)
Ac = ### mm2
ν = 0.6ㆍ(1 - fck/250)
NWeb : Number of Webs = 2
ν1 is a strength reduction factor for concrete cracked in shear
αcw is a coefficient taking account of the state of the stress in the compression chord
Asl = 7855.400 mm 2
≥ ∑Aslreq = 4037.691 mm2 OK
where, Asl is the applied area of longitudinal reinforcement for torsion.
∑Aslreq is the requierd area of longitudinal reinforcement for torsion.
- Design value for the shear resistance VRd,max (EN 1992-1-1:2004, 6.2.3(9))
VRd,max = αcwㆍbwㆍzㆍν1ㆍfcd / (cotθ + tanθ) / NWeb
= 6736.229 kN ≥ V*Ed = 2807.201 kN OK
where, ν1 = ν = 0.504
αcw = 1 + σcp / fcd = 1.092 ( for 0 < σcp ≤ 0.25ㆍfcd )
σcp = NEd / Ac = 2.094 MPa
NEd = 13002.467 kN (if compression, NEd > 0)
Ac = ### mm 2
ν = 0.6ㆍ(1 - fck/250)
NWeb : Number of Webs = 2
ν1 is a strength reduction factor for concrete cracked in shear
αcw is a coefficient taking account of the state of the stress in the compression chord
bw = 816.0 mm
S = 3213825045.025 mm3
fctd = αctㆍfctk,0.05 / γc = 1.637 MPa
fctk,0.05 = 0.7ㆍfctm
fctm = 0.3ㆍfck(2/3)
αl = 1.0
σcp = NEd / Ac ≤ 0.2ㆍfcd = 2.094 MPa
NEd = 13000.993 kN (if compression, NEd > 0)
Ac = 6208720 mm 2
- Design value for the shear resistance VRd,max (EN 1992-1-1:2004, 6.2.3(9))
VRd,max = αcwㆍbwㆍzㆍν1ㆍfcd / (cotθ + tanθ) / NWeb
= 6736.164 kN ≥ V*Ed = 3953.961 kN OK
where, ν1 = ν = 0.504
αcw = 1 + σcp / fcd = 1.092 ( for 0 < σcp ≤ 0.25ㆍfcd )
σcp = NEd / Ac = 2.094 MPa
NEd = 13000.993 kN (if compression, NEd > 0)
Ac = ### mm2
ν = 0.6ㆍ(1 - fck/250)
NWeb : Number of Webs = 2
ν1 is a strength reduction factor for concrete cracked in shear
αcw is a coefficient taking account of the state of the stress in the compression chord
5.Crack Width
■ Top
1 Calculate crack width, wk (EN 1992-1-1:2004, 7.3.4)
- Design Load
Load Combination Name : SLS_F1
Serviceability Load Type : Frequent
Load Combination Type : FX-MIN
Long/Short Term : Short-term
NEd = -13498.711 kN
MEd = 2132.419 kNㆍm
■ Bottom
1 Calculate crack width, wk (EN 1992-1-1:2004, 7.3.4)
- Design Load
Load Combination Name : SLS_F1
Serviceability Load Type : Frequent
Load Combination Type : FX-MAX
Long/Short Term : Short-term
NEd = -13497.154 kN
MEd = -16648.088 kNㆍm
mm2
mm2
mm2
mm2
mm2
Ep
(MPa)
200000.000
200000.000
200000.000
200000.000
Ratio
(C/T)
10.40764
5.12171
2.31992
1.09157
0.54829
0.81188
0.94450
1.01796
0.98121
0.99958
Fpi
(kN)
7333.009
7333.009
6404.352
7333.009
Ratio
(C/T)
1.84211
1.19846
0.93943
1.11478
1.05003
1.00046
Fpi
(kN)
7333.009
7333.009
7333.009
7333.009
nt is required
shear force.
ular to the shear force.
04, 6.2.3(3)~(4))
04, 9.2.2(5))
nt is required
shear force.
ular to the shear force.
04, 6.2.3(3)~(4))
04, 9.2.2(5))
2014 cl. 6.3.2 (1))
er hollow areas
≥ VRd,min
OK
OK
04, 6.2.3(9))
(cl.6.3.2 (103))
2014 cl. 6.3.2 (1))
er hollow areas
OK
OK
04, 6.2.3(9))
(cl.6.3.2 (103))
OK
04, 6.2.3(9))
(cl.6.3.2 (103))
Element Number 26
Position Information J
1.Design Condition
1.1 Design Parameters
- Partial factors for ultimate limit states (EN 1992-1-1:2004, 2.4.2.4)
Design Situations γc for concrete γs for reinforcing steel γs for prestressing steel
Persistent & Transient 1.500 1.150 1.150
Accidental 1.200 1.000 1.000
- factor αcc , αct : Coefficient for long term effects on Compression and Tensile Strength.
αcc = 0.850 (for the Compressive strength)
αct = 1.000 (for the Tensile strength)
- Calculate Fc , Fs , Fp
x = 179.1 mm
Fc = ( λㆍx )ㆍ( ηㆍfcd ) = 27601.758 kN
Fs' = fs'ㆍAs' = 3824.557 kN
Fs = fsㆍAs = 2076.188 kN
Fp = ∑Fpi = 29332.035 kN
where, x is neutral axis depth
■ Negative Moment
1 Check Moment Resistance, MR,d
- Design Load
Load Combination Name : ULS1
Design Situations : Persistent & Transient
Load Combination Type : MY-MIN
MEd = 0.000 kNㆍm
- Calculate Fc , Fs , Fp
x = 301.8 mm
Fc = ( λㆍx )ㆍ( ηㆍfcd ) = 24887.626 kN
Fs' = fs'ㆍAs' = 2076.188 kN
Fs = fsㆍAs = 3824.557 kN
Fp = ∑Fpi = 23157.407 kN
where, x is neutral axis depth
3.Shear Resistance
■ Maximum Shear Force
1 Check shear resistance of Concrete, V_Rd,c
- Design Load
Load Combination Name : ULS1
Design Situations : Persistent & Transient
Load Combination Type : FZ-MAX
NEd = -17209.592 kN
VEd = 1627.998 kN
MEd = 53150.944 kNㆍm
Vp = -0.895 kN
- Design value for the shear resistance VRd,s (EN 1992-1-1:2004, 6.2.3(3)~(4))
Skip checking shear resistance, VRd,s by shear reinforcement steel
- Design value for the shear resistance VRd,s (EN 1992-1-1:2004, 6.2.3(3)~(4))
Skip checking shear resistance, VRd,s by shear reinforcement steel
4.Torsional Resistance
■ Maximum Shear Force
1 Design Load
Load Combination Name : ULS1
Design Situations : Persistent & Transient
Load Combination Type : FZ-MAX
NEd = -17209.592 kN
VEd = 1627.998 kN
TEd = 188.171 kNㆍm
MEd = 53150.944 kNㆍm
5.Crack Width
■ Top
1 Calculate crack width, wk (EN 1992-1-1:2004, 7.3.4)
- Design Load
Load Combination Name : SLS_F1
Serviceability Load Type : Frequent
Load Combination Type : FX-MAX
Long/Short Term : Short-term
NEd = -17758.243 kN
MEd = 9789.273 kNㆍm
mm2
mm2
mm2
mm2
mm2
Ep
(MPa)
200000.000
200000.000
200000.000
200000.000
Ratio
(C/T)
2.77769
2.28969
1.79022
1.04191
0.54829
0.81188
0.92689
0.98440
1.01316
0.99878
1.00597
1.00237
1.00058
Fpi
(kN)
7333.009
7333.009
7333.009
7333.009
Ratio
(C/T)
3.96519
2.30389
1.25027
0.58255
0.92081
1.08927
1.01058
0.96562
0.98808
0.99933
Fpi
(kN)
3061.666
5429.724
7333.009
7333.009
nt is not required
shear force.
ular to the shear force.
04, 6.2.3(3)~(4))
04, 9.2.2(5))
nt is not required
shear force.
ular to the shear force.
04, 6.2.3(3)~(4))
04, 9.2.2(5))
≥ VRd,min
2014 cl. 6.3.2 (1))
er hollow areas
≥ VRd,min
≥ VRd,min
Positive MEd
Elem. Part / Lcom Name Situation Type Check
Negative (kNㆍm)
16 J Positive ULS3 Persistent & Transient FX-MIN OK 0.000
16 J Negative ULS1 Persistent & Transient MY-MIN OK -53937.346
26 J Positive ULS2 Persistent & Transient MY-MAX OK 63238.203
26 J Negative ULS1 Persistent & Transient MY-MIN OK 0.000
MEd MRd
MEd/MRd
(kNㆍm) (kNㆍm)
0.000 21371.630 0.000
-53937.346 76763.576 0.703
63238.203 78717.490 0.803
0.000 20942.439 0.000
Positive VEd
Elem. Part / Lcom Name Situation Type Check
Negative (kN)
16 J MAX ULS1 Persistent & Transient FZ-MAX OK 9297.999
16 J MIN ULS3 Persistent & Transient FX-MIN OK 5614.402
26 J MAX ULS1 Persistent & Transient FZ-MAX OK 1627.998
26 J MIN ULS2 Persistent & Transient FZ-MIN OK -1484.155
VEd VRd VRd,c VRd,s VRd,max
VEd/VRd Asw,req / s ρw,min Sl,max
(kN) (kN) (kN) (kN) (kN)
9297.999 9500.443 2121.035 9500.443 13472.228 0.979 10.103 0.001 2205.0
5614.402 9500.443 4937.445 9500.443 13472.458 0.591 6.100 0.001 2205.0
1627.998 2295.371 2295.371 9532.759 13888.230 0.709 1.763 0.001 2212.5
-1484.155 2295.371 2295.371 9532.759 13888.230 0.647 1.607 0.001 2212.5
Positive TEd
Elem. Part / Lcom Name Situation Type Check
Negative (kNㆍm)
16 J V-MAX ULS1 Persistent & Transient FZ-MAX OK 2101.376
16 J V-MIN ULS3 Persistent & Transient FZ-MIN OK 0.000
16 J T-MAX ULS2 Persistent & Transient MX-MIN OK -3506.770
26 J V-MAX ULS1 Persistent & Transient FZ-MAX OK 188.171
26 J V-MIN ULS2 Persistent & Transient FZ-MIN OK -824.093
26 J T-MAX ULS1 Persistent & Transient MX-MIN OK -1777.352
TEd TRd,s VEd VRd,s TRd,c VRd,c TRd,max
Ratio Ratio Ratio
(kNㆍm) (kNㆍm) (kNㆍm) (kNㆍm) (kN) (kN) (kNㆍm)
2101.376 28993.229 0.072 9297.999 9500.443 0.979 21159.921 2121.035 4.483 80631.637
0.000 28993.229 0.000 5614.402 9500.443 0.591 21159.921 4937.445 1.137 80633.009
-3506.770 28993.229 0.121 7333.377 9500.443 0.772 21159.921 4937.288 1.651 80632.236
188.171 - - 1627.998 - - 21159.921 2295.371 0.718 -
-824.093 - - -1484.155 - - 21159.921 2295.371 0.686 -
-1777.352 - - -16.566 - - 21159.921 2295.371 0.091 -
TRd,max VRd,max
Ratio
(kNㆍm) (kN)
80631.637 13472.228 0.716
80633.009 13472.458 0.417
80632.236 13472.328 0.588
- - -
- - -
- - -
FT FB FTL FBL
Elem. Part Comp./Tens. Stage Check
(MPa) (MPa) (MPa) (MPa)
16 I Compression CS1 OK 4.433 0.938 4.433 0.938
16 I Tension CS4 OK 2.235 2.363 2.235 2.363
16 J Compression CS1 OK 3.553 1.887 3.553 1.887
16 J Tension CS1 OK 3.553 1.887 3.553 1.887
26 I Compression CS4 OK 4.298 2.564 4.298 2.564
26 I Tension CS2 OK 3.963 3.757 3.963 3.757
26 J Compression CS4 OK 4.403 2.278 4.403 2.278
26 J Tension CS2 OK 4.032 3.491 4.032 3.491
FTR FBR FMAX ALW
(MPa) (MPa) (MPa) (MPa)
4.433 0.938 4.433 15.666
2.235 2.363 2.235 2.389
3.553 1.887 3.553 15.666
3.553 1.887 1.887 1.440
4.298 2.564 4.298 24.000
3.963 3.757 3.757 2.135
4.403 2.278 4.403 24.000
4.032 3.491 3.491 2.135
Lcom FT FB FTL
Elem. Part Comp./Tens. Type Check
Name (MPa) (MPa) (MPa)
16 I Compression SLS_C3 MY-MAX OK 7.226 0.795 7.226
16 I Tension SLS_C4 MY-MIN OK -1.671 3.428 -1.671
16 J Compression SLS_C2 MY-MIN OK -1.998 8.483 -1.684
16 J Tension SLS_C4 MY-MIN NG -3.170 5.453 -3.170
26 I Compression SLS_C3 MY-MAX OK 9.328 -0.639 9.328
26 I Tension SLS_C4 MY-MAX OK 3.129 -2.096 3.129
26 J Compression SLS_C3 MY-MAX OK 9.435 -0.894 9.435
26 J Tension SLS_C4 MY-MAX NG 3.236 -2.352 3.237
FTL FBL FTR FBR FMAX ALW
(MPa) (MPa) (MPa) (MPa) (MPa) (MPa)
7.226 0.795 7.226 0.795 7.226 24.000
-1.671 3.428 -1.671 3.428 -1.671 2.105
-1.684 8.649 -2.311 8.317 8.649 24.000
-3.170 5.453 -3.171 5.453 -3.171 2.105
9.328 -0.639 9.327 -0.639 9.328 24.000
3.129 -2.096 3.129 -2.096 -2.096 2.105
9.435 -0.894 9.435 -0.895 9.435 24.000
3.237 -2.352 3.236 -2.352 -2.352 2.105
Sig_P1 Sig_P2 Sig_P3 Sig_P4
Elem. Part Comp./Tens. Stage Check
(MPa) (MPa) (MPa) (MPa)
16 I Compression CS4 OK 2.235 2.235 2.363 2.363
16 I Tension CS4 OK 0.000 0.000 0.000 0.000
16 J Compression CS4 OK 0.996 0.996 3.987 3.987
16 J Tension CS4 OK 0.000 0.000 0.000 0.000
26 I Compression CS4 OK 3.789 3.789 1.627 1.627
26 I Tension CS4 OK 0.000 0.000 0.000 0.000
26 J Compression CS4 OK 3.876 3.876 1.401 1.401
26 J Tension CS4 OK 0.000 0.000 0.000 0.000
Sig_P5 Sig_P6 Sig_P7 Sig_P8 Sig_P9 Sig_P10 Sig_MAX Sig_AP
(MPa) (MPa) (MPa) (MPa) (MPa) (MPa) (MPa) (MPa)
2.368 2.368 2.511 2.511 2.479 2.479 2.511 40.000
-0.111 -0.111 -0.224 -0.224 -0.135 -0.135 -0.224 3.981
2.409 2.409 3.527 3.527 4.206 4.207 4.207 40.000
-0.914 -0.914 -1.336 -1.336 -0.668 -0.668 -1.336 3.981
3.435 3.435 2.920 2.920 1.966 1.966 3.789 40.000
-0.006 -0.006 -0.016 -0.016 -0.014 -0.014 -0.016 3.981
3.463 3.463 2.863 2.863 1.772 1.772 3.876 40.000
0.000 0.000 0.000 0.000 0.000 0.000 0.000 3.981
Sig_AP
(MPa)
40.000
3.981
40.000
3.981
40.000
3.981
40.000
3.981
Lcom Sig_P1 Sig_P2 Sig_P3
Elem. Part Comp./Tens. Type Check
Name (MPa) (MPa) (MPa)
16 I Compression SLS_C3 MY-MAX OK 7.225 7.225 0.795
16 I Tension SLS_C4 MY-MIN OK -1.670 -1.670 0.000
16 J Compression SLS_C1 MY-MIN OK 0.003 0.004 8.650
16 J Tension SLS_C4 MY-MIN OK -3.168 -3.169 0.000
26 I Compression SLS_C3 MY-MAX OK 9.327 9.327 0.001
26 I Tension SLS_C4 MY-MAX OK 0.000 0.000 -2.090
26 J Compression SLS_C3 MY-MAX OK 9.434 9.434 0.001
26 J Tension SLS_C4 MY-MAX OK 0.000 0.000 -2.346
Sig_P3 Sig_P4 Sig_P5 Sig_P6 Sig_P7 Sig_P8 Sig_P9 Sig_P10 Sig_MAX
(MPa) (MPa) (MPa) (MPa) (MPa) (MPa) (MPa) (MPa) (MPa)
0.795 0.795 2.377 2.384 2.021 2.035 0.928 0.946 7.225
0.000 0.000 -0.228 -0.242 -0.325 -0.344 -0.126 -0.136 -1.670
8.650 8.319 1.884 2.231 4.234 4.689 7.478 7.914 8.650
0.000 0.000 -1.380 -1.430 -1.612 -1.674 -0.610 -0.648 -3.169
0.001 0.001 3.715 3.712 2.220 2.212 0.074 0.053 9.327
-2.090 -2.090 -0.007 -0.005 -0.021 -0.016 -0.043 -0.030 -2.090
0.001 0.001 3.755 3.758 2.156 2.167 0.017 0.040 9.434
-2.346 -2.346 -0.002 -0.005 -0.007 -0.014 -0.015 -0.036 -2.346
Sig_MAX Sig_AP
(MPa) (MPa)
7.225 40.000
-1.670 3.509
8.650 40.000
-3.169 3.509
9.327 40.000
-2.090 3.509
9.434 40.000
-2.346 3.509
Elem. Part Top/Bottom Lcom Name Lcom-Type Type Long/Short Check