Professional Documents
Culture Documents
Ger 4367
Ger 4367
Ger 4367
Overview
Summary
GE Multilin releases the F650 Feeder Management Relay & Bay Controller Firmware, Hardware &
Bootware version 5.40.
Highlights of this release include:
Note:
• Firmware version 5.40 is compatible with Enervista 650 Setup Software version 5.40 and
F650 relays with hardware version 01 or higher and Bootware version 5.40.
• Please refer to Chapter 8 of the Instruction manual for detailed directions on Bootcode and
Firmware upgrade. The F650 Instruction Manual is available at the GE Multilin website:
http;//gemultilin.com/
• For upgrade to new Hardware version 04, please contact Multilin Technical Support Team
for the appropriate hardware package.
• The hardware version of the F650 relay can be verified from the device identification label.
Alternately, it is also available from the EnerVista 650 Setup software version 3.00 or higher
(while communicating with the relay).
GE Multilin 1
F650 Relay Release Notes
Release details
In the following enhancement descriptions, a revision category letter is placed to the left of the description.
Refer to the Appendix at the end of this document for a description of the categories displayed.
• The Minimum Voltage settings of the 81U and the 81O have been reduced from 30V to 20V.
• Analogical GOOSE values configuration can be configured in the one line diagram screen for Graphic
HMI options in ordering code.
C IEC61850 improvements
• Reports dating issue correction when DST is active and SNTP synchronization is used.
• ConfRevNum correction when remote GOOSE was set to 0.
• File list retrieval process enhancement.
• Protocol initialization improvement
• Manufacturing date and serial number are available through modbus protocol.
• Revised for application and use with firmware version 5.40 and Bootware version 5.40.
2 GE Multilin
F650 Relay Release Notes
Upgrade paths
In order to take advantage of the enhancements and new features introduced in the latest F650 release, we
recommend that you upgrade to the new F650 Firmware version 5.40.
Firmware upgrades can be easily performed using 650 set up software. This upgrade can be done either
via EnerVista Launchpad or by direct download from the following site:
http://gemultilin.com/software/F650
For F650 relays with Hardware version 01 and above, the 5.40 Firmware release can be uploaded to the F650
relay CPU via the Enervista 650 Setup software.
Hardware Upgrade package must be obtained from GE Multilin to upgrade the relays from Hardware 01 to
Hardware 04.
For F650 relays with Hardware 00, an upgrade package must be obtained from GE Multilin to upgrade the relays
Please contact your local GE Multilin sales representative or GE MultilinTechnical Support Team for any
questions regarding this upgrade.
GE Multilin 3
F650 Relay Release Notes
Appendix
Change categories
This document uses the following categories to classify the changes.
Table 1: Revision categories
N New feature A separate feature added to the relay. Changes to existing features even
if they significantly expand the functionality are not in this category
G Change A neutral change that does not bring any new value and is not correcting
any known problem
D Changed, incomplete or false Changes to, or problems with text messages, LEDs and user pushbuttons
faceplate indications
R Changed, incomplete or false relay Changes to, or problems with relay records (oscillography, demand, fault
records reports, etc.)
C Protocols and communications Changes to, or problems with protocols or communication features
P Protection out of specification Protection operates correctly but does not meet published specifications
(example: delayed trip)
The revision category letter is placed to the left of the change description.
4 GE Multilin