Ger 4367

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

GE Digital Energy

F650 Feeder Management Relay


& Bay Control
Firmware, Software & Bootware Version 5.40
Release Notes
GE Publication Number: GER-4367
Copyright © 2010 GE Multilin

Overview
Summary
GE Multilin releases the F650 Feeder Management Relay & Bay Controller Firmware, Hardware &
Bootware version 5.40.
Highlights of this release include:

• Ethernet controller improvement.

• Frequency functions improvement.

• New Out of Service setting available.

• Analogic Gooses available on Graphic HMI.

• IEC 61850 improvements.

• Non-Volatile latches available.

• New Maintenance data available.

• Release Date: February 26th, 2010

Note:
• Firmware version 5.40 is compatible with Enervista 650 Setup Software version 5.40 and
F650 relays with hardware version 01 or higher and Bootware version 5.40.

• Please refer to Chapter 8 of the Instruction manual for detailed directions on Bootcode and
Firmware upgrade. The F650 Instruction Manual is available at the GE Multilin website:
http;//gemultilin.com/

• For upgrade to new Hardware version 04, please contact Multilin Technical Support Team
for the appropriate hardware package.

• The hardware version of the F650 relay can be verified from the device identification label.
Alternately, it is also available from the EnerVista 650 Setup software version 3.00 or higher
(while communicating with the relay).

Please contact your local GE Multilin Sales Representative or GE Multilin Technical


Support Department for any questions regarding this F650 Release.

GE Multilin 1
F650 Relay Release Notes
Release details
In the following enhancement descriptions, a revision category letter is placed to the left of the description.
Refer to the Appendix at the end of this document for a description of the categories displayed.

Firmware Version 5.40

C Ethernet controller improvement

• Enhancement in the master-slave communication through Ethernet to avoid communication issues


when the switch auxiliary supply is cycled off and on.

E Frequency functions improvement

• The Minimum Voltage settings of the 81U and the 81O have been reduced from 30V to 20V.

• Frequency measurements accuracy improvement to +/- 0.03 Hz of the reading in frequency


measurements from 30Hz to 80Hz.

N New Out of service setting available

• New out of service setting available.

E Analogic Gooses available on Graphic HMI

• Analogical GOOSE values configuration can be configured in the one line diagram screen for Graphic
HMI options in ordering code.

C IEC61850 improvements

• Reports dating issue correction when DST is active and SNTP synchronization is used.
• ConfRevNum correction when remote GOOSE was set to 0.
• File list retrieval process enhancement.
• Protocol initialization improvement

N Non-Volatile latches available

• 16 Latched Virtual Outputs are available for customer configuration.

N New Maintenance data available

• Manufacturing date and serial number are available through modbus protocol.

Enervista Set up Software Version 5.40

• Revised for application and use with firmware version 5.40 and Bootware version 5.40.

2 GE Multilin
F650 Relay Release Notes
Upgrade paths

In order to take advantage of the enhancements and new features introduced in the latest F650 release, we
recommend that you upgrade to the new F650 Firmware version 5.40.

Firmware upgrades can be easily performed using 650 set up software. This upgrade can be done either
via EnerVista Launchpad or by direct download from the following site:
http://gemultilin.com/software/F650

If using EnerVista Launchpad, follow these steps:


1. Open EnerVista Launchpad
2. Click “IED Setup”
3. Click “Check Updates”. Note: this will check for updates to all of the IED setup software shown.
4. Select the F650 version 5.40 upgrade for download.

Upgrade path for Hardware version 01 and above

For F650 relays with Hardware version 01 and above, the 5.40 Firmware release can be uploaded to the F650
relay CPU via the Enervista 650 Setup software.

Hardware Upgrade package must be obtained from GE Multilin to upgrade the relays from Hardware 01 to
Hardware 04.

Upgrade path for Hardware Version 00

For F650 relays with Hardware 00, an upgrade package must be obtained from GE Multilin to upgrade the relays

CPU to hardware 01 to 04.

Please contact your local GE Multilin sales representative or GE MultilinTechnical Support Team for any
questions regarding this upgrade.

GE Multilin 3
F650 Relay Release Notes

Appendix
Change categories
This document uses the following categories to classify the changes.
Table 1: Revision categories

Code Category Comments

N New feature A separate feature added to the relay. Changes to existing features even
if they significantly expand the functionality are not in this category

G Change A neutral change that does not bring any new value and is not correcting
any known problem

E Enhancement Modification of an existing feature bringing extra value to the application

D Changed, incomplete or false Changes to, or problems with text messages, LEDs and user pushbuttons
faceplate indications

R Changed, incomplete or false relay Changes to, or problems with relay records (oscillography, demand, fault
records reports, etc.)

C Protocols and communications Changes to, or problems with protocols or communication features

M Metering Metering out of specification or other metering problems

P Protection out of specification Protection operates correctly but does not meet published specifications
(example: delayed trip)

U Unavailability of protection Protection not available in a self-demonstrating way so that corrective


actions could be taken immediately

H Hidden failure to trip Protection may not operate when it should

F False trip Protection may operate when it should not

B Unexpected restart Relay restarts unexpectedly

The revision category letter is placed to the left of the change description.

GE Multilin technical support


GE Multilin contact information and call center for product support is shown below:
GE Multilin Technical Support
215 Anderson Avenue
Markham, Ontario
Canada L6E 1B3
Telephone: 905-294-6222 or 1-800-547-8629 (North America), +34 94 485 88 00 (Europe)
Fax: 905-201-2098 (North America), +34 94 485 88 45 (Europe)
E-mail: multilin.tech@ge.com
Home Page: http://www.GEmultilin.com

4 GE Multilin