m8 NATIONAL FIRE ALARM AND SIGNALIN
ted to the system with 4 hours of capacity arranged in
accordance with 10.6.10
10,6.7.3.2 Secondary circuits that provide power to the
control unit and are not integral to dhe unit shall be protected
aginst physical damage.
10.6.7.4 Secondary Power Supply for Supervising Station
Facilities.
10.6.7.4.1. The secondary power supply shall consist of one of
the following:
(1) Storage batteries dedicated to the supervising station
‘equipment arranged in accordance with 10.6.10
(2) Avbranch circuit of an automatiestarting, engine-driven,
generator arranged in accordance with 10.5.1132.1 and
10.6.11.9.22, and storage bateries dedicated to the
supervising station equipment with 4 hours of capacity
arranged in accordance with 10.6.10
(8) A branch circuit of multiple enginedriven generators, at
least one of which is arranged for automatic starting in
accordance with 10.6.11.32.1 and 10.6.11.3.22
10.6.7.4.2 Where a secondary power supply for supervising
station facilities in accordanee with 10,67:4.1(8) is Wed, the
following shall apply:
(1) Each generator shall he capable of supplying the energy
required.
(2) Generators that are started manually shall be arranged in
accordance with 10.6.11.32.3and 10.11.32,
(3) When manualstart generators are employed, a person
trained in the procedure of starting the generator shall
be on duty atall times
10.6.8 Power Supply for Remotely Located Control Equip-
ment.
10.6.8.1" Additional power supplies required for system oper
ation shall comply with 10.6.1 dhrough 10.6.6 and with 10.6.9.
106.82 The location of remotely located power supplies shall
bo identified atthe master eontzol uni
10,6.8.8 The master contol unit display shall be permitted to
satisfy the requirement of 10.8.2
10.684 The location of remotely located power supplies shall,
be identified on the record drawings.
106.85 An uninterruptible power supply (UPS) listed to the
requirements of an applicable standard such as ULS64, Control
{Units and Accessories for Bre Alarm Stems, shall be permitted to
supply power to remotely located control equipment.
10.6.9 Monitoring Integrity of Power Supplies.
10.6.9.1. Unless otherwise permitted or required by 10.6.9.1.3
and 10,6.9.1.6, all primaty and secondary power supplies shall
hhe monitored for the presence of voltage at the point of
connection to the system,
10.6.9.1.1. Failure of either the primary oF secondary power
ipply shall result in a trouble signal in accordance with
Section 10.
10.6.9.1.2 Power faire indication for a digital alarm commu
nicator ransmitter (DACT) powered from a protected prem-
ises fire alarm system control unit shall be in accordance with
106.91.
2022 Eston
10.6.9.1.3 Monitoring shall not he required fora power supply
for supplementary equipment
10.69.14 Monitoring shall not be required for the neutral of
three. four, or Fiveswire ae oF de supply source,
10.6.9.1.5 Monitoring shall not be required for the main
power supply in a supervising station if its failure is otherwise
indicated and obsious to the operator on du.
106.9.1.6 Monitoring shall not be required for the ourput of
aan engine-driven generator that is part of the secondary power
Suppl, provided the generator is tested weekly in accordance
with Chapter 1,
10..9.2¢ Power supply sources and electrical supervision for
digital alarm communications systems shall be in accordance
with Section 10.6, 10.68), Section 10.19, and Section 12.6.
106.93 Supers y
to delay transmission of primary power Failure
6) minutes to 180 minutes unless a delay is not permitted by
he authority having jurisdiction,
10.6.9.4 Power supervisory devices sed to monitor the integ-
rity of power supplies shall not impair the receipt of fire alarm
‘or supervisory signals
106.10° Storage Batteries.
106.10.1 Marking.
106.10.1.1 Batteries shall be marked with the month and year
of manufacture using the month/year format.
106.10.1.2 Where the battery is not marked with the month/
year hy the manufacturer, the installer shall obtain the date-
ode and mark the battery with the month/year of battery
10.6.10.1.8° Effective January 1 rechargeable batteries
for the secondary power supply used in control units, devices,
and accessories shall be listed or component recognized by a
nationally recognized testing laboratory
10.6.10.2 Arrangement.
10.6.10.2.1 Storage batteries shall comply with the require-
iments of Article 480 of NEPA 70
10.6.10.2.2 Storage batteries shall be located so that the equip
rent, including overcurrent devices, is not adversely affetedt
by batery gases.
10.6.10.2.8. Batteries shall he insulated against ground! faults
10.6.10.24 Batteries shall be insulated to prevent short
sireuits herween muliple cells.
10.6.10.2.5 Batteries shall be protected from physical damage.
10.6.10.2.6. Batcery racks shall he protected against corrosion,
10.6.10.2.7 If not located in or adjacent to the control unit,
the hatieties and their charger location shall be permanent
identified atthe contro! un
106.10.8 Battery Charging.
106.10.8.1 Bauery charging equipment shall be provided to
keep the battery fully changed under normal conditions,FUNDAMENTALS, m9
10,6,10.3.2. Bauwery charging equipment shall be provided to
recharge batteries wilun 48 hours after fully charged batteries
Ihave been subject to 2 single discharge cele as specified in
106.72.
10.10.33 The battery charging equipment operation shall
not damage the battery
10,6.10.3.4% Batteries shall be charged hy listed means,
10.6.10.3.5 Provisions for repair or replacement of failed
batery charger equipment shall be maintained at supervising
slations and used to restore operation prior to depletion of
‘one-half of the battery capacity
10,6,104 Overcurrent Protection. Overcurrent devices shall
be provided to protect the hatteries from excesive load
10,6.10.5 Metering, The buttery charging equipment shall
inchide integral meters or readily accessible tetminals so that
porable meters can be used to determine battery voltage and
‘charging current,
10.6.10.6" Monitoring Integrity of Battery Charging Equip-
10,6.10.6.1. Means shall he provided to detect the failure of
Dawery charger
10,6.10.6.2 Failure of the battery charger shall result in a trou
ble sigial in accordance with Section 10.15,
10.6.1 Engine-Driven Generators.
106,11.1 Application and Installation. The application and
installation Of enginedriven generators shall he as specified in
10.6.11,2 through 10.6.11.7,
10.6.11.2 Primary Power Supply.
10.6.11.2.1. Enginedriven generators arranged as the primary
supply shall be designed in an approved manner
10.11.22. Enginedriven generators arranged! as the primary
supply shall be installed in an approved manner:
10,6,11.3 Secondary Power Supplies.
10.6,11.3.1 Protected Premises.
10611..1.1 Engine-triven generators used to provide secon
dary power for a protected premises fire alarm system or an
emergency communications stem shall comply with
NFPA'110 Chapter 4, requirements for a Type 10, Class 24,
Level I ster.
106,11.8.1.2 Installation of enginedriven generators used (0
provide secondary power for a protected premises fire alarm
system or an emergency communications system shall be in
accordance with NEPA 7/, Acticle 700,
106,118.18 Where pathway survivability is required by
another section of the Code, equal protection shall be provi
‘ded for power supply circuits
106.11.3.2 Supervising Station.
106,113.21 Automatiestarting, enginedriven generators
used to provide secondary power for a supervising station shall
‘comply with NEPA 110 Chapter 4, requirements for a Type 60,
‘Chass 24, Level 2 sistem,
10.6.11.3.2.2 Installation of automatiestarting, enginedriven
generators used to provide secondary power for a supervising
Station shall be in accordance with NEPA 70Anticle 701
10.6.11.3.2.8 Manualstarting, enginedriven generators used
to provide secondary power for a supervising station shall
‘comply with NFPA 110 Chapter 10, requirements for a Type M,
‘Chass 24, Level 2 stem,
10.6.11.3.24 Installation of manualstarting, enginedriven
generators used {0 provide secondary power for a supervising
Station shall be in accordance with MFPA 70, Asticle 702
106.114 Performance, Operation, Testing, and Maintenance.
The requirements for performance, operation, testing, and
maintenance of engincdriven generators shall conform to the
applicable prexisions of NFPA 110,
10.6.11.5 Capacity. The unit shall be ofa eapacity that is sth
Gent to operte the system under the maximum normal load
conditions in addition to all other demands placed upon the
10.6.11.6 Fuel. Unless otherwise required or permitted in
10.611.6.1 through 10.6,11,6.3, fuel shall be available in stor-
age sufficient for 6 months of testing phis the capacity specified
in 1067,
10.6.11.6.1 For public emergency alarm reporting ystems, the
requirements of Chapter 27 shall apply.
10.6.11.6.2. If 2 reliable source of supply is available at any
time on a Zhour notice, it shall be permitted to have fuel in
stonige sufficient for 12 hours of operation at full load,
10.11.63. Fuel systems using natural or manufacuired gas
supplied through reliable utility mains shall nor be required to
have fuel storage tanks unless the structure isa seismic design,
‘category C, D, E, or F as defined in ASCE/SEL 7, Minimum
Design Locals and Assriated Criteria for Buildings and Other Struc
10.6.11.7 Battery and Charger.
106.11.7.1. A separate storage battery and separate automatic
‘charger shall be provided for starting the enginedlriven genera-
tor and shall not he used for any other purpose.
10.6.11.7.2. ‘The battery shall be sized in accordance with 5.64
oF NFPA 110,
10.7 Signal Priority. The priority of signals shall he in accord-
ance with this section,
10.7.1 ECS priority signals when evaluated by stakeholders
through a risk analysis in accordance with 24,8.12 shall be
permitted to take precedence overall other signals.
10.72 Fire alarm signals shall tke precedence over all other
signals, exceptas permitted by 10.7.1 or 10.73.
10.7.8" Emergency mass notification signals and: messages
shall he permitted to have priority over fire alarm notification
signals in accordance with the requirements of Chapter 24.
10.74 Emergency mass notification signals and messages shall
have priority over supervisory and trouble signals in accord.
ance with the requirements of Chapter 24.
10.75 Carbon monoxide signals shall be permitted to take
precedence over supervisory and trouble signals
2022 Eton7.80 NATIONAL FIRE ALARM AND SIGNALING CODES
10.7.6 Prealarm signals shall take precedence over superv-
sory and trouble signals
10.7.7 Supervisory signals shall take precedence over trouble
signals.
10.7.8 Holdup alarms or other life-threatening signals shall
be permitted to take precedence aver supervisory and «rouble
signals where acceptable to the authority having jurisdiction
10.7.9 Where separate systems are installed, they shall be
permitted to achieve the priority of signals in accordance with
Section 107
10.7.10 Combination systems shall comply wi
10.8 Detection and Signaling of Conditions.
10.8.1 Abnormal Condition Detection. Where required by
this Gode, the system shall be provided with means to detect
and signal abnormal conditions.
10.82 Alarm Condition Detection. Where requived by this
Code, the system shall be provided with means to deweet and
signal alarm conditions,
1082.1 PreAlarm Condition Detection. Where required by
this Code, the system shall be provided with means to detect
and signal prealarm conditions.
10,82.2 Supervisory Condition Detection. Where required by
this Cade, the system shall be provided with means to detect
‘and signal supervisory conditions,
1082.8 Trouble Condition Detection. Where required by this,
Code, the system shall be provided with means to deieet and
signal trouble conditions.
10.824 Normal Condition Detection. Where required by this,
Codle, the system shall generate a restoration signal when the
device or signaling system returns to normal
Av.
10.9 Responses.
10.9.1 Alarm. The response to an
accordance with this Code,
farm signal shall be in
10.9.2 Pre-Alarm. ‘The response to a pre-alarm signal shall be
in accordance with this Code.
10.9.3 Supervisory. The response to a supervisory signal shal,
be in accordance with this Code.
10.9.4 Trouble. The response to touble signal shall be in
accordance with this Code.
10.10 Distinctive Signals.
1010.1 Priority alarm signals, fire alarm signals, carbon
monoxide alarm signals, supervisory signals, prealarm signals,
and trouble signaly shall he distinctively’ and. descriptively
fannuneiated,
10.10.2. Audible alarm notification appliances for a fire alarm
system shall produce signals that are distinctive from other
lar appliances used for other purposes in the same area
that are not part of the fire alarm or emergency communica-
10.10.3 Audible alarm notifiation appliances for a carbon
‘monoxide alarm system shall produce signals that are distine-
tive from other similar appliances used for other purposes in
2022 Eston
the same area that are not part of the eathon monoxide, fire
alarm, or emergency communications system.
10.10.4° An audible notification appliance on a control unit,
‘on muliple control units that are interconnected to form. a
system, oF at a remote location, shall be permitted to have the
same audible characteristic forall alerting functions including,
but not limited to, alarm, wouble, and supervisory, provided
that the distinction beaween signals shall be by other means,
10,10.5 Supervisory signals shall be distinctive in sound from
other signals, and their sound shall not be used for any other
purpose except as permitted in 10.104.
10.106. Trouble signals required 1o indieate at the protected,
premises shall he indicated by distinctive audible signals, which
Shall he distinetive from alarm signals except as permitted in
10.1044
10.10.7 Alarm evacuation signals shall be distinetive in sound
from other signals, shall comply with the requitements of
18.42, and their sound shall not be used for any other
purpose,
10.108. Prealarm signals shall be distinetive in sound from,
other signals, and their sound shall not be used for any other
purpose except as permitted in 10.104.
1010.9 Carbon monoxide alarm signals shall comply with
1843.
10.11 Alarm Signals.
10.11.4 Actuation of alarm notification appliances or emer
gency voice communications, emergency control function
Interface devices, and annunciation at the protected prem
shall oceur within 10 seconds after the activation of an initiate
ing device.
1011.2 Visual notification appliances, textual visual notiiea-
tion appliances, and loudspeaker notification appliances loca
ted in the same area shall he activated and deactivated as 2
group unless otherwise required by an ECS emergency
response plan. (SIGECS)
10.11.38. Visual alarm notification appliances shall not be aeti-
vated when loudspeaker notification appliances are used as
permitted by 243.5 for noremergency paging. (SIGECS)
10.11.4% A coded alarm signal shall consist of not less than
three complete rounds of the number transmitted,
10.11.5 Each round of a coded alarm signal shall consist of
‘not less than three impulkes,
10.11.6* Resetting of alarm signals shall comply with 288,22.
10.11.7 ‘The subsequent oceurrence of a fault on an initiating
device circuit ora signaling line circuit used for other than the
interconnection of control units shall not affect previously
transmitted sntacknovwledged alarm signals,
10.118 An alarm signal that has been deactivated at the
protected premises shall comply with 10,11.8.L and 10.11.82.
10,11.8.1 The audible and visible alarm signal at the control
unit only shall automatically reactivate every 24 hours oF less
‘until alarm signal conditions are restored to normal
10.11.82 The audible and visible alarm signal shall operate
until i is manually silenced or acknowledged.FUNDAMENTALS, mat
10.12* Fire Alarm Notification Appliance Deactivation.
1012.1 A means for wining off activated alarm notification
appliance(s) shall be permitted,
10,12.2* When an occupant notification alarm signal deactiva-
tion means is actuated, both audible and visual notiheation
appliauices shall be simultaneously deactivated.
10,12.3 The fire alarm notification deactivation means shall
be key-operated or located within a locked cabinet, or arranged
to provide equivalent protection against unauthorized use
10.124 The means shall comply with the requirements of
101s
10,12.5 Subsequent Activation of Initiating Devices.
10,12.5.1. Subsequent activation of nonaddvessable initiating
devices on other initiating device circuits shall cause the notify
‘ation appliances to reactivate.
10.12.5.2. Subsequent activation of addressable alarm initiat
ing devices of a different sype in the same root or addressable
alarm initiating devices in a different room on signaling Tine
‘Grcuits shall cause the notification appliances to reactivate
1012.6 A fire alarm notification deactivation means that
remains in the deactivated position when there is no. alarm
Condition shall operate an audible trouble notification appli
ance until the means is restored to normal.
10.18 Carbon Monoxide Notification Appliance Deactivation.
A-carhon monoxide initiating device with an integral sounder
shall he permitted to he silenced locally if the carbon monax-
ide alarm or supervisory status continues to be displayed at the
‘control unit.
10,14 Supervisory Signals.
10,14.1 SelfRestoring Supervisory Signal Indication. Visible
and aulible indication of selErestoring supervisory signals and
Yisible indication of their restoration to normal shall be auto-
matically indicated within 90 second atthe following locations:
(1) Fire alarm control unit for local fire alarm systems
(2) Building fire command center for in-building fire emer-
gency voice /alarm communications systems
(3) Emergency command center for one oF more buildings
where responsible authorities receive and. disseminate
nformation
(4) Supervising station location for systems installed in
compliance with Chapter 26
10,14.2 Latehing Supervisory Signal Indication.
10,14.2.1. Visible and audible indication of latching supers:
sory signals shall be indicated within 90 seconds at the loc
lions specified in 10.141
10,14.2.2. Restoration of latehing supervisory signals shall be
indicated within 90 seconds at the locations specified in
10.141
10,14.8 Coded Supervisory Signal.
10.143.1 A coded supervisory signal shall be permitted to
consist of two rounds of the number transmitted to indicate a
supervisory offnormal condition.
10.14.8.2 A coded supervisory signal shall be permitted to
consist of one round of the number transmitted to indicate the
restoration of the supervisory condition to normal
10.144 Combined Coded Alarm and Supervisory Signal
Gireuits. Where both coded sprinkler supervisory signals and
coded fire or waterflow alarm signals are transmitted over the
same sigialing line circuit, provision shall be made to obtain
either alarm signal precedence or sufficient repetition of the
alarm signal to prevent the loss ofan alarm signal
10.14.5 Supervisory Notification Appliance Location. The
audible supervisory notification appliances shall be located in
an area where they are 10 be heard.
10.14.6 Supervisory Sigaal Reactivation. A supervisory signal
that has been deactivated at the protected. premises. shall
comply with 10.14.6.1 and 10.14.62
10.14.6.1 The audible and visible supervisory signal at the
‘control unit only shall automatically reactivate every 24 hours
for less until supervisory signal conditions are restored. to
normal
10,14.6.2. The audible and visible supervisory signal shall oper-
ate antl itis manually silenced oF acknowledged.
10.14.7 Supervisory Notification Appliance Deactivation.
10.14.7.1 A means for deactivating supervisory notification
appliances shall be permitted.
10.14.7.2 The means shall be key-operated or located within a
locked ‘cabinet, or arranged to provide equivalent protection
against unauthorized use,
10.14.73 ‘The means for deactivating supervisory notification
appliances shall comply with the requirements of 10.18,
10.14.7.4. Subsequent activation of supervisory initaging devi
ces in other building zones shall cause supervisory notification
appliances to activate as required by the system input/output
10.14.7.5 A means for deactivating supervisory notification
appliances that remains in the deactivated position when there
is ho supervisory condition shall operate an audible trouble
notification appliance until the means isrestored to normal
10.15 Trouble Signals
10.15.1 Trouble signals and their restoration to normal shall
be indicated within 200 seconds at the locations identifica in
10.15.7 and 10.158.
10.15.2. Indication of primary power failure rouble signals
transmitted to a supervising station shall be in accordance with
10.693,
10.153 An audible wouble signal shall be permitted 0 be
intermittent provided it sounds at least once every 10 second,
with a minimum duration of second,
10.154 A single anclible trouble signal shall be permitted to
annunciate multiple Fault conditions,
1015.5. The audible trouble notifieation appliances shall be
located in an area where they are to he heard.
10.15.6 Activated notification appliances at the protected
premises shall continue to operate unless they are ‘manually
Silenced as permitted by 10.15.10.)
2022 Etonme NATIONAL FIRE ALARM AND SIGNALIN
10.15.7. Visible and audible trouble signals and visible indica-
tion of their restoration to normal shall be indicated at the
following locations:
(1) Fire alarm control unit for protected premises alarm
(2) Building fire command center for in-building fire emer-
‘gency voiee/alarm communications systems
(8) Emergency command center for one or more buildings
where responsible authorities receive and. disseminate
information
(4) Central station or remote station location For systems
installed in compliance with Chapter 26
10.5.8 Trouble signals and their restoration to normal shall
be visibly and audibly indicated at the proprietary supervising
station for systems installed in compliance with Chapter 26,
10.15.9° A trouble signal that has been deactivated at the
protected premises shall comply with 10,15..1 and 10.1
10.15.91. ‘The audible and visible wouble signal shall automac-
ally reactivate at the control unit every 24 hours or less until
trouble signal conditions are restored to normal
10.15.9.2 ‘The audible and visible wouble signal associated
with signaling the depletion or faihure of the primary battery of
A witeless system as required by 25.1621 and 23,1622 shall
automaticaly resound every 4 houts or less until the depletion
Signal is restored to normal
10.15.10 Trouble Notification Appliance Deactivation.
10.15.10.1 A means for deactivating wouble notification appli
ances shall be permitted,
10.15.10.2 The means shall be key-operated of located within.
locked cabinet, of arranged to provide equivalent protection
against unauthorized use
10.15.10.3 The means for deaetiating wouble notification
appliances shall comply with the requirements of 10.18.2
10.15.10. If an audible trouble notification appliance is also
used "to indicate a supervisory condition, as permitted by
10.104, a trouble notification appliance deactivation means
shall mot present subsequent actuation of supervisory notiiea-
tion appliances.
10.15.10.5 Subsequent trouble signals shall cause trouble noti-
fication appliances to activate as requited by the system input/
cust matrix.
10.15.10.6 A means for deactivating trouble notification appli-
ances that remains in the deactivated position when there ino
trouble condition shall operate an auclible trouble 1
appliance until the means is restored to norm
10.15.10.7* Unless otherwise permitted by the authority
having jurisdiction, trouble notification appliances at the
prover. premises of a supervising station fie alarm stem
arranged in accordance with Chapter 26, that have been
Silenced at the protected premises shall automatically reactivate
every 24 hours or less until fault conditions are restored to
normal.
10.16 Emergency Control Funetion Status Indicators.
10.16.1_ All contvols provided specifically for the purpose of
‘manually overriding any automatic emergency control function
2022 Eston
shall provide visible indication of the status of the associated
control circuits,
10.16.2° Where status indicators are provided for emergency
equipment of control funetions, they shall be arranged to
reflect the actual status of the associated equipment oF func-
10.17 Notification Appliance Circuits and Supervised Notifien-
tion Appliance Control Circuits.
10.7.1 An open, groundfault, or short-circuit fault on the
nstallation conductors of one alarm notification appliance
circuit shall not affect the operation of any other alarm ott
cation appliance eixenit for more than 200 seconds regardless
of whether the shortcircuit fault is present during the normal
for activated cirenit state,
10.17.2. Supervised notification appliance control cireuits shall
‘comply with all of the following
(1). A supervised notification appliance control eirenit shall
not serve more than one notification zone.
2) The supervised notification appliance contro! circuit shal,
be monitored for integrity in accordance with
Seotion 126
(3) A fault in the supervised notification appliance control
‘ircuit installation conductors shall result in a trouble
signal in accordance with Section 10.15,
10.18 Annunciation and Annunciation Zoning.
10.8.1 Alarm Annunciation. Where required by other
governing laws, codes, or standards, the location of a oper=
ated initiating device shall be annunciated by visible means,
10,18.1.1. Visible annunciation of the location of an operated
iniiating device shall be by at indicator lamp, alphanumeric
Aisplay, printout, or other approved means.
10.18.1.2* ‘The visible annuneiation of the location of oper
ated initiating devices shall not be canceled by the means used
odeactivate alarm notification appliances,
10.182 Supervisory and Trouble Annunciation. Where
required by other governing laws, codes, or standards, supers
sory of trouble conditions shall be annunciated by. visible
10.18.2.1 Visible annunciation shall be by an indicator lamp,
aan alphanumeric displ, a printout, or other means.
10,18.2.2 The visible annunciation of supervisory oF trouble
conditions shall not he canceled by the means used to deacti-
sate supervisory or trouble notification appliances,
10.183 Anmunciator Access and Location.
10.18.3.1 All required annunciation means shall b
accessible to responding personnel
10.18.3.2 All required annunciation means shall be located as
required by the authority having jurisdiction wo facilitate an
cfficient response tothe situation
10,184 Alarm Annunciation Display. Visible annunciators
shall be capable of displaying all zones in alarm,
10.18.4.1 If all zones in alarm are not displayed simuliane-
‘ously, the zone of origin shall be displayed.
readilyCARCUTS AND PATHWAYS mas
10,18.4.2. IF all zones in alarm are not displayed simutiane-
ously there shall he an indication that other zones are in
alum,
10,18.5* Annunciation Zoning.
10,18.5.1_ For the purpose of alarm annunciation, each Moor
‘of the building shall be considered as separate zone.
10.18.5.2 For the purposes of alarm annunciation, ifa floor of
the building is subdivided into multiple zones by fire or smoke
barriers and the fire plan for the protected premises allows
relocation of occupants from the 2one of origin to another
zone on the same floor, each zone on the floor shall be ansiin-
‘Gated separately
10,18.5.3 Where the sjstem serves more than one building,
‘each building shall he annunelated separately
10.18.6* Emergency Services Interfaces. Where required by
the enforcing authori; governing laws, codes, of standards: ot
other pars of this Code, annunciators, information display
‘stems, and controls for portions of a syntem provided for use
by emergeney service personnel shall be designed, arranged,
and located in accordance with the requirements of the organ
zations intended to use the equipment.
10,19 Monitoring Integrity of InBuilding Fire Emergency
Voice/Alarm Communications Systems.
10,19.1% Audio Amplifier and Tone-Generating Equipment. If
loudspeakers are used to produce audible fire alarm signals,
the required touble signal for 10,19.1.1 through 10,19.1.3
shall be in aecordance with Section 10.15
10.19.1.1 When primary power is available, failure of any
‘audio amplifier shall result ina trouble signal
10.19.1.2 When an alarm is present and primary power is not
available (ie., system is operating from the secondary power
source), failure of any audio amplifier shall result in a trouble
signal
10,19.1.3* Failure of any tone-generating equipment shall
result in a trouble signal, unless the tone-generating and ampli-
fying equipment are enclosed as integral parts and serve only a
single, listed loudspeaker:
10.19.2 Two Way Telephone Communications Circuits.
10.19.21 Twornay telephone communications eireuit install
lion conductors shall be monitored for open circuit fault
conditions that would cause the telephone communi
‘Geuit to become fully or partially inoperative,
10.19.2.2 Tworway telephone communications eixeuit install
tion conductors shall he monitored for short circuit fault
conditions that would cause the telephone communications
‘drcuit to become fully or partially inoperative.
10.19.23 Two-way telephone communications cireuit fault
conditions shall result in a trouble signal in accordance sith
Section 10.15.
10.20 Documentation and Notification.
10.20.1 Documentation shall be in accordance with Chap-
tee 7,
10,20.2 The authority having jurisdiction shall be notified
prior to installation or alteration of equipment or wiring.
10.21* Impairments.
10.21.1. The system owner or the owner's designated represen:
tative shall be notified when a system or part thereof is
impaired. Impairments to systems shall include outotservice
10.21.2 A record of the impairments shall be maintained by
the system over or the owner's designated representative for 8
petiod of I year from the date the impairment is corrected.
10.21.38 The supervising station shall report to the authority
having juriaicsion any system for which required monitoring
has been terminated,
10.21.4* ‘The service provider shall report to the authority
having jurisdiction any’sjstem that is out of service for more
than 8 hours,
10.21.5* Where required by the authority having jurisdiction,
mitigating measures shall be implemented for the period that
the system is impaired.
1021.6. The system owner of the owner's designated represen-
{ative and the anthority having jurisdiction shall be notified
‘when an impairment petiod ends.
10.22 Unwanted Alarms. For the purpose of reporting,
alarm signals that are not the result of hazardous conditions
shall be classified as Unwanted atid subclasified as one of the
following:
(1) Malicious alarm,
(2) Nuisance alarm
@)_ Unintentional alarm
@) Coknown alarm
Chapter 11 Cybersecurity
111% Cybersecurity. Where required by governing laws,
codes, oF standards, or other parts of this Code, eybersecurity
shall be provided for equipment, software, firmware, tool,
installation methods, physical security of and access to equip
‘ment, data pathways, testing, and maintenance.
Chapter 12 Ci
and Pathways
121 Application,
12.L.1 Pathymays (interconnections) shall be designated based
‘on the performance characteristics defined in this chapter
12.1.2 The requitements of Chapters 11 and 14 shall apply
122 General.
12.2.1¢ Performance and survivability of signaling: pathways
(interconnections) shall comply with the defined designations
of this chapter
12.22 A pathway (interconnection) chss designation shall be
dependent on the pathway (interconnection) capability 10
‘continute to operate during abnormal conditions
12.2.8 The installation of all pathway wiring, cable, and equip-
ment shall be in accordance with NFPA 70:and the applicable
requirements of 12.2.3] theough 122.34.
12.2.8.1. Optical ber cables installed as part of the fire alarm,
system shall meet the requirements of NFPA 70 Article 770, and
2022 Etonme NATIONAL FIRE ALARM AND SIGNALING CODES
be protected against physical damage in accordance with
NEPA TOAxticle 700,
12.232 Optical fiber cables entering from outside the baie:
ing or structure shall also comply with NFPA 70 Article 840.
12.23.8° Fire alarm gstem wiring and equipment, including
all circuts controlled and powered by the fire alarm system,
Shall be installed in accordance with the requirements of this
Corde and of NFPA 70 Article 760,
12.23.4° Wiring methods permitted by other sections oft
Code to resist attack by fire shall be installed in accordance
with manufietirer’s published instructions and the require-
‘ments of NEPA 70 Article 76 and Article 7
12.2.5 Where operational capability is required to be main-
tained or continued during the application of a fault, the
‘operational capability required in 10,111 shall be restored
‘within 200 seconds from the time the fault is introduced,
12.24 Ground Connections.
1224.1 Unless otherwise permitted by 12.2-42, all fire alarm,
systems shall test free of grounds
1224.2 The requirements of 122.4.1 shall not be requited
where pars of circuits or equipment ate intentionally and
permanently grounded in order t proside ground fault devec-
tion, noise suppression, emergency ground signals, and circuit
protection grounding,
12.24.3* On conductive pathways, operational capability shall,
be maintained dusing the application of a single ground
12.3¢ Pathway Class Designations. Pathymays shall be designa-
ted ay Class A, Class B, Class C, Class D, Class E, Class Ny or
Class X, depending on their performance.
12.3.1° Class AL A pathway shall be designated as Class A
when it perform as follows:
(1) Ieincludes a redundant path
(2) Operational capability continues pasta single open, and
the single open fant results in the annnunciation of a trot
ble signal.
(8) Conditions that affect the intended operation of the path
are annneiated asa trouble signal
(4) Operational capability on metallic conductors is main-
tained dusing the application of a single ground fault
(6) Asingle ground condition on mesallie conductors results,
in the annunciation of a trouble signal
12.8.2 Class B. A pathway shall be designated as Class B when
it performs as follows:
(1) Idoes not inelude a redundant path,
(2) Operational capability stops ata single open.
(8) Conditions that affect the intended operation of the path
fare annunciated asa trouble signal
(A) Operational capability on metallic conductors is main-
tained during the application of a single ground fault
A single ground condition on metallic conductors results
in the anniinciation of a trouble signal
12.3.3° Class C. A pathway shall be designated as Class C
when it performs as follows:
2022 Eston
(1) ILineludes one or more pathways where operational eapa-
bility is verified via enc-toend commun
integrity of individual path
(2) Alos of endioend communication is annus
twouble signal
12.8.4 Glass D. A pathway’ shall be designated as Class D.
when it has failsafe operation, where no fault is annunciated,
but the intended operation is performed in the event of a path
12.3.5* Glass EA pathway shall be designated as Class E
when itis not monitored for integrity.
el as a
12.3.6 Glass N, A pathway shall be designated as Cass N when
it performs as follows
(1)# Teincludes two oF more pathways where operat
bility ofthe primary pathway and a redundant
each desice shall be Verified through end-to-end comma
Excaption: When only one device is served, any one pataoay
shal be nguined.
(2) Atos of intended communications between endpoints
shall he annunciated as-a trouble signal
(8) Assingle open, ground, short, or combination of fauls on.
‘one pathway shall not affect anyother pathway
(4)® Conditions that affect the operation of the primary pa
way(s) and redundant pathvay(s) shall be anmunciated ay
A trouble signal when the system's minimal operational
requirements cannot be met.
(5)* Primary and redundant pathways shall not be permitted,
to share traffie over the same physical segment
12.3.7 Clase X. A pathway shall be designated as Class X whet
it performs as follows
(1) Teincludes a redundant path.
(2) Operational capability continues pasta single open, and
the single open fault resuks in the annunciation ofa tot
bie signal
(8) Operational capability on metallic conductors continues,
pasta single shoreeircuit, and the single shortireuit fault
results in the annunciation ofa trouble signal
(4) Operational capability on metallic conductors continues,
pista combination open fault and ground fault.
(5) Conditions that affect the intended operation oF the path
are annunciated asa trouble signal
(6) Operational capabifiy on, metallic conductors is main-
tnined during the application of a single ground fauk,
(7) Asingle ground condlition on metallic conductors resulis
in the annunciation of a trouble signal
12.8.8° Class A, Class N, and Class X Pathway Separation.
‘Cliss A, Class N, and Class X eitcuits using physical pathways
shall be installed so that the primary and redundant, or ontgor
ing and retuen, conductors exiting from and returning (0 the
control unt, respectively are routed separately
12381 The ougoing and retum (redundant) ci
‘conductors shall be permitied in the same eable assembly (i,
‘multiconductor cable), enclosure, oF raceway only under the
following conditions:
(1) For a distance not to exceed 10 f (30 m) where the
‘outgoing and retum conductors enter oF exit the iniiat-
ing device, notification appliance, or control unit enclo-CARCUTTS AND PATHWAYS 785
(2) Single drops installed in the raceway to individual devices
‘orappliances i
(3)* In asingle room not exceeding 1000 f€ (93 m?) in area, a
drop installed in the raceway to multiple devices or appli
ances that does not include any emergency control func.
tion devices
12.4% Pathway Survivabiliy. All pathways shall comply with
NFPA 70,
124.1 Pathway Survivability Level 0, Level 0 pathways shall
not he required to have any provisions for pathway survivabil
124.2 Pathway Survivability Level 1. Pathay survivability
Level 1 shall consist of pathways in buildings that are fally
protected by an automatic sprinkler system in accordance with
NFPA 13 with any interconnecting conductors, cables, or other
physical pathways protected by metal riceways or metal
armored cables,
124.3% Pathway Survivability Level 2. Pathway survivability
Level 2 shall consist of one of more of the following:
(1) 2hour firerated creuit integrity (CI) oF reressive
cable
(2) 2hous frerated eable system [electrical civeut provetve
system(s]
(8), Zhou fireated enclosure or protected area
(4) Performance alternatives approved by the authority
having jurisdiction
124.4% Pathway Survivability Level 3. Pathway: survivability
Level 3 shall consist of pathways in buildings that are fully
protected by an automatic sprinkler sytem in accordance with
NFPA 13 and one or more of the following
(1) hour firexated circu
cable
(2) Mhour fire-rated cable system (electrical cireut protective
systern(s)]
(8). 2hour frerated enclosure or protected area
(4)* Performance alternatives approved by the authority
having jurisdiction,
124.5% Pathway Survivability Level 4. Pathway survival
Level 4 shall consist of one of more of the following:
integrity (Cl) or fire-resistive
ty
(1) Phour firerated circuit integrity (CI) or fireresistive
cable
(2) Phour fire-rated cable system [electrical eixeit protective
system(s) ]
(3) Phour frerated enclosure or protected asea
(4) Performance alternatives approved by the authority
having jurisdiction
12.5% Shared Pathway Designations. Shaved pathways shall be
designated as Level , Level 1, Level 2, or Level 3, depending
‘on their performance,
12.5.1 Shared Pathway Level 0. Level 0 pathways shall not be
required to segregate o prioritize life safety data from non-life
ssfety data
125.2% Shared Pathway Level 1. Level 1 pathways shall not be
required to segregate life safety data from non-life safety data,
Dut shall prioritize all life safety data over non-tife safety data.
12.5.3 Shared Pathway Level 2. Level 2 pathways shall segre-
gate all life safety data from non-life safety data
12.54% Shared Pathway Level 3. Level pathways shall use
equipment that is dedicated to the life safety system,
12.6% Monitoring Integrity and Gircuit Performance of Insta
lation Conductors and Other Signaling Channels.
126.1 Unless otherwise permited or required by 123.1
through 123.7 and 12.6.8 through 126.13, all means of inter
connecting equipment, devices, and appliances and wiring
connections shall be monitored for the integrity of the inter-
connecting conductors or equivalent path so that the occur
Fence of a single open or a single grouncfault condition in the
instalation conductors or other signaling channels is automat
cally indicated within 200 seconds.
1262 Unless otherwise permitted or required by 123.1
through 123.7 and 126.8 through 126.13, all means of inter
connecting equipment, devices, and appliances and wiring
connections shall be monitored for the integrity of the inter
‘connecting conductors or equivalent path so that the restora-
tion to normal of a single open or a single groundaul
condition in the instalation conductors or other signaling
channels is tutomatically indicated within 200 seconds,
Shorts between conductors shall not be requited 10 be
less required by 126. 6.16,
1264 Monitoring for integrity shall not be required for a
noninterfering shunt circuit, provided that a fault circuit
condition on the shunt circuit wiring results only in the Toss of
the noninterfering feature of operation,
12.6.5 Monitoring for integrity shall not be required for
connections 10 and herween supplementary system compo-
nents, provided that a single open, groundfaull, of short
conditions of the supplementary equipment or
cting means, or both, do not affect the requited
‘operation of the fire alarm and/or signaling system,
12.6.6 Monitoring for integrity shall not be required for the
Greuit oF an alarm notification appliance installed in the same
room with the control equipment, provided that the notifies
tion appliance circuit conductors are installed in conduit or are
‘equivalently protected against mechanical injury.
12.6.7 Monitoring for integrity shall not be required for a
lwouble notification appliance circu
12.68% Monitoting for integrity shall not be required for the
interconnection between listed equipment within a common
enclosure.
12.6.9 Monitoring for integrity shall not be required for the
interconnection between enclosures containing control equip
‘ment located within 20. (6 m) of each other where the
conductors ate installed in conduit or equivalently protected
‘against mechanical injury
126.10 Monitoring for integrity shall not be required for the
conductors for groundfault detection where a single ground-
fault does not prevent the required normal operation of the
126.11 Monitoring for integrity shall not be required for
pnetimatic rateofrise sstems of the continuous line wype in
‘which the witing terminals of such devices are connected in
multiple aevosselectically supervised circuits.
2022 Eton72.86 NATIONAL FIRE ALARM AND SIGNALING CODES
126.12 Monitoring for integrity shall not be required for the
interconnecting wiring of a stationary computer and the
computer's keyboard, video monitor, mouse-lype device, or
touch screen, as long as the interconnecting wiring does not
exceed 8 1. m) in lengthy is a listed computer/data
processing cable as permitted by NFPA 70; and failure of eable
does not cause the failure of the required system Funetions not
ited from the keyboard, mouse, or touch sereen,
126.13 Monitoring for integrity of the installation conductors
for groundfault condition shall not be requited for the
‘communications and transmission channels extending from
supervising station to a subsidiary starion(s) or protected prem-
Jses, or both, shat comply with the requirements of Chapter 26
and are electrically isolated from the fire alarm system (or
‘ircults) by a transmiter(s)
126.14 Interconnection means shall be arranged so that a
ngle break or single ground-fault does not cause at alarm,
gna,
1.6.15 A wireto-wire short-circuit fault on any alarm notifica-
sion appliance circuit shall result in a trouble signal in accord-
ance with Section 10.15, except as permitted by 126.5, 126.6,
or 26.11
126.16 Where «wo or more sjstems are interconnected, the
systems shall be connected using Class A, B, N, or X ezeuits as
described in Section 123
12.7% Nomenclature, The following nomenclature shall be
used to identify the required properties of the system(s) intes-
connections and pathway survivability:
(1) Systems) interconnections
(2) Pathway survivability levels (not required if Level 0)
(8) Shared pathway levels (noc required if Level 0)
(A) Pathway class designation
Chapter 18. Reserved
Guapter 14. Inspection, Testing, and Maintenance
14.1 Application,
14.1.1 The inspection, testing; and maintenance of systems,
their initiating’ devices, and’ notification appliances. shall
comply with the requirements of this chapter
14.1.2 The inspection, testing, and maintenance of single-and,
muliiplestaion alarms and household alarm systems shall
comply with 14.4.5 and 114.6. (SIGHOU)
14.1.8 Procedures that are required by other parties and that
exceed the requirements ofthis chapter shall be permitted.
14.14 The requirements of shis chapter shall apply to both,
new and existing systems,
14.15 The requirements of Chapter 7 shall apply where refer:
enced in Chapter 14.
14.2 General.
14.2.1 Purpose.
14.21.18 The purpose for initial and reacceptance inspee-
tions shall be to ensure compliance with approved design doc
2022 Eston
‘ments and 10 ensure installation in accordance with this Code
‘and other required installation standard,
142.1.2% The purpose for inital and reacceptance tests of fire
alarm and signaling systems shall be w ensure system operation
in accordance with the design documents,
142.1.8° The purpose for periodic inspections shall be to
assure that abyious damages or changes that might affect the
system operability are visually identified,
14.2.1.4 ‘The purpose for periodic testing shall be to statisti-
cally assure operational reliability
14.2.2 Performance.
14.2.2.1 Performance Verification. To ensure operational
integrity, the system shall have an inspection, esting, and main-
tenance program,
M422.1.1 Inspection, testing, and maintenance programs
shall satisty the requirements of this Code and conform to dhe
‘equipment manufacturer's published instructions
142.2.1.2* Inspection, testing, and maintenance programs
shall verify eorreet operation of the system,
142.22 Impairments. Where an automatic function of a fire
alarm oF signaling sjstem is taken out of service for testing and
‘manual means or other compensatory measures are wnavail-
bie, the stem or portion thereof is impaited and shall comply
with the requirements of Section 10.21 until the automatic
function is restored
14.2.2.8 Deficiencies.
14.2.2.5.1 System deficiencies shall be corrected,
142.2.3.2 Ifa deficiency is not corrected at the conclusion of
system inspection, testing, or maintenance, the ystem owner or
the owner's designated representative shall be informed of the
deficiency in writing within 24 hours,
1422.88 In the event that any equipment is observed to be
part of a recall program, the system owner or the system
‘owner's designated representative shal he notified in writing,
42.2.4 Observations.
14.2.2.4.1 Ifobservations are noted, they shall be permitted t0
bbe communicated to the system owner
142.242 The stem owner shall not be required to address
such observations unless the observations become an impair.
‘ment oF deficiency
14.23 Responsibilities.
1423.1 The propery or building or system owner or the
‘owner's designated representative shall he responsible for
inspection, testing, and maintenance of the system and for
alterations oF additions to this system,
1423.2 Where the propemy owner is not the occupant, the
property owner shall be permitted 10 delegate the authority
and responsibilty for inspecting, testing, and maintaining the
fire protection systems to the occupant, management firm, or
managing individual ihrough specific provisions in the lease,
written use agreement, or management contract.
1423.3 Inspection, testing, or maintenance shall be permit-
ted to be done by the building of sistem owner or a person orINSPECTION. TESTI
IND MAINTENANCE, mer
‘organization other than the building or system owner if
‘conducted under a writen conta
142.34 Where the building or ystem owner hus delegated
any responsibilities for inspection, testing, oF maintenance,
copy of the written delegation required by 14.233 shall be
provided to the authority having jurisdiction upon request.
14.235 Testing and maintenance of central station service
systems shall be performed under the contractual arrange
ments specified in 26.83,
14.2.8.6° Service Personnel Qualifications and Experience.
Service personnel shall be qualified and experienced in accord-
ance with the requirements of 10.
M24 Notification.
14.241 Before proceeding with any testing, all persons and
facilities receiving alarm, supervisory, or trouble signals and all
building occupants shall be notified of the testing to prevent
unnecessary response,
142.42 Av the conclusion of testing, those previously notified
{and others, as necessary) shall be notified that testing. as
been concluded
1424.3 The owner or the owner's designated representative
and service personnel shall coordinate system. testing 10
prevent intermuption of crtieal building systems or equipment,
14.2.5 System Documentation. Prior to system maintenance
for testing, the recont of completion and any information
required by Chapter 7 regarding the system and system altera-
tions, including specifications, wiring diagrams, and Moor
plans, shall be provided by the owner or a designated represen
Iative to the service personnel upon request
142.51 The provided documentation shall include the
‘current revisions of all fre alarm software and the revisions of
software of any systems with which the fire alarm software inter
faces.
14.2.5.2 The revisions of fire alarm software, and the revisions
of the software in the systems with which the fire alarm software
interfaces, shall be verified for compatibility in accordance with
the requirements of 23.2.2.1-1
14.26 Releasing Systems. Requirements pertinent to testing
the fire alarm sjstems initiating fire suppression system releas-
ing functions shall be covered by 14.2.6.1 through 14.2.6.
14.2.1 Testing personnel shall be qualified and experienced
in the specific arrangement and operation of a suppression
system(s) and a releasing function(s) and shall be cognizant of
the hazards asociated with inadvertent system discharge,
1426.2. Occupant notification shall be required whenever a
fire alarm system configured for releasing service is being sere
iced of tested,
4.2.6.8. Discharge testing of suppression systems shall not be
required by this Code,
14.264 Suppression systems shall be secured from inadver-
tent actuation, including disconnection of releasing solenoids
fo electric actuators, closing of valves, ather actions, or combi-
rations thereof, for the specific ystem, for the duration of the
fire alarn system testing
14.2.6. Testing shall include verification that the releasing
circuits and components energized or actuated by the fire
alarm system are electrically monitored for integrity and oper-
ate as intended on alarm,
14.2.6.6 Suppression stems and releasing components shall
be returned 10 their functional operating condition upon
completion of sytern testing,
14.2.7 Interface Equipment and Emergency Control Functions.
142.7. Testing personnel shall be qualified and experi
enced in the arrangement and operation of interface equip-
rmentand emergency control funcuons,
142.72 Testing shall be accomplished in accordance with
Table 144.82,
14.2.8 Automated Testing.
14.2.8.1 Automated testing arrangements that provide equiva-
lent means of testing devices to those specified in Table
14.43.2 at a Frequency at least equivalent to those specified in
Table 144.32 shall be permitted to be used to comply with the
requirements ofthis chapter.
4.282 Failure of a device on an automated ces shall result
ian audible and visual trouble signal,
14.2.9 Performance-Based Inspection and Testing. As an
alternate means of compliance, subject to the authority having
Jjurisdicion, components and stems shall be permitted to be
nspected and tested under a performance-based program,
142.10" Test Plan,
14.2.10.1 A test plan shall be developed to clearly establish the
scope af the testing for the fire alarm ar signaling system,
14.2.10.2 ‘The test plan and resus shall be documented with
the testing records
14.3 Inspection.
143.1% Unless otherwise permitted by 14.32, visual inspee-
tions shall be performed in accordance with the schedules in
‘Table 14.3.1 oF more ofien if required by the authority having
jtisdietion.
1.32% Devices of equipment that is inaccessible for sety
considerations (e., continuous process operations, energized
electrical equipment, radiation, and excessive height) shall be
permitted to he inspected during scheduled shutdowns if
approved by dhe authority having jurisdiction
4.3.8 Extended intervals shall not exceed 18 months.
14.34 Initial and reacceptance inspections shall be made to
censure compliance with approved design documents and to
fensure installation in accordance with this Code and other
required installation standards,
143.5 Periodic visual inspections in accordance with Table
14531 shall be made to assure that there axe no changes that
affect equipment performance
144 Testing.
144.1 Initial Acceptance Testing.
HA.L.1 AML new systems shall he inspected and tested in
accordance with the requirements of Chapter 14.
2022 Eton