Product data sheet ACRD301S

Characteristics InRow DX 300mm 30kW

General

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Provided equipment Installation guide
Integrated network management
Network management card
Optional concrete pad
User manual
Compressor type Scroll
Air discharge option Horizontal
Intake air option Rear return
Refrigerant load 14.97 kg
Air flow 1604.62 l/s
Tube material Copper

Physical
Number of rack unit 42U
Depth 109.5 cm
Height 199.1 cm
Product weight 159.98 kg
Width 30 cm

Input
Number of feeders 2
Input power 850 W
Minimum circuit ampacity 20 A
Network frequency 50/60 Hz
Maximum overcurrent protection 25 A
Number of input connectors 2
Input voltage 100...120 V AC 1 phase
200...240 V

Conformance
Product certifications cUL listed

Sep 8, 2021
1
CE
UL listed

Environmental
Ambient air temperature for operation -25…46 °C
Ambient air temperature for storage -20…46 °C
Relative humidity 0…95 %
Operating altitude 0...10000 ft
Acoustic level 77.1 dBA

Communications & Management


Control panel Multifunction LCD status and control console
Alarm Audible and visible alarms prioritized by severity

Packing Units
Unit Type of Package 1 BOX
Number of Units in Package 1 1
Package 1 Weight 200.0 kg
Package 1 Height 2152 mm
Package 1 width 661 mm
Package 1 Length 1137 mm

Contractual warranty
Warranty 1 year on-site repair or replace with factory authorized Start-Up