Air System Sizing Summary for 00 Dehumidify

Project Name: 0001 Allied Bank, Lahore 04/18/2023


Prepared by: asco 11:32AM

Air System Information


Air System Name ............................. 00 Dehumidify Number of zones ........................................................... 1
Equipment Class ........................................ CW AHU Floor Area .............................................................. 750.0 ft²
Air System Type ........................................... SZCAV Location ............................................. Lahore, Pakistan

Sizing Calculation Information

Calculation Months ................................. Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ............................................. Calculated Space CFM Sizing ........... Individual peak space loads

Central Cooling Coil Sizing Data 50,400 BTU/h

Total coil load ....................................................... 4.2 Tons Load occurs at ................................................. Jun 1500
Total coil load ..................................................... 50.4 MBH OA DB / WB ................................................. 114.0 / 85.0 °F
Sensible coil load ............................................... 46.5 MBH Entering DB / WB ........................................... 76.4 / 62.2 °F
Coil CFM at Jun 1500 ........................................ 2030 CFM Leaving DB / WB ............................................ 54.6 / 53.3 °F
Max block CFM ................................................. 2030 CFM Coil ADP .................................................................. 52.2 °F
Sum of peak zone CFM .................................... 2030 CFM Bypass Factor ........................................................ 0.100
Sensible heat ratio ............................................ 0.922 Resulting RH ............................................................... 45 %
ft²/Ton ............................................................... 178.5 Design supply temp. ................................................ 56.0 °F
BTU/(hr-ft²) ......................................................... 67.2 Zone T-stat Check ................................................. 1 of 1 OK
Water flow @ 12.0 °F rise .................................. 8.41 gpm Max zone temperature deviation ................................ 0.0 °F

Central Heating Coil Sizing Data


14,700 BTU/h
Max coil load ...................................................... 14.7 MBH Load occurs at ................................................. Feb 0800
Coil CFM at Feb 0800 ....................................... 2030 CFM BTU/(hr-ft²) ............................................................... 19.6
Max coil CFM .................................................... 2030 CFM Ent. DB / Lvg DB ............................................ 54.4 / 61.3 °F
Water flow @ 20.0 °F drop ................................. 1.47 gpm

Supply Fan Sizing Data

Actual max CFM ................................................ 2030 CFM Fan motor BHP ........................................................ 0.46 BHP
Standard CFM ................................................... 1979 CFM Fan motor kW .......................................................... 0.37 kW
Actual max CFM/ft² ............................................. 2.71 CFM/ft² Fan static ................................................................. 1.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................... 55 CFM CFM/person ........................................................... 27.50 CFM/person
CFM/ft² ............................................................... 0.07 CFM/ft²

Room Dimension :
L=75 ft; W=10 ft & H=10ft
Complete Partional Walls & No Infill added.

Q1: What will be the wet bulb across the


Heating Coil?

Q2: Do we have to recool the Air to achieve 55F


DB for terminally supplied air?

Hourly Analysis Program v4.80 Page 1 of 2


Air System Design Load Summary for 00 Dehumidify
Project Name: 0001 Allied Bank, Lahore 04/18/2023
Prepared by: asco 11:32AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 114.0 °F / 85.0 °F HEATING OA DB / WB 49.0 °F / 41.1 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 750 ft² 0 - 750 ft² 0 -
Partitions 1700 ft² 17365 - 1700 ft² 0 -
Ceiling 750 ft² 7661 - 750 ft² 0 -
Overhead Lighting 750 W 1975 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1125 W 3449 - 0 0 -
People 2 422 910 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 4631 137 0% 0 0
>> Total Zone Loads - 35503 1047 - 0 0
Zone Conditioning - 40459 1047 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2030 CFM 0 - 2030 CFM 0 -
Ventilation Load 55 CFM 2239 2912 55 CFM 1216 -5
Supply Fan Load 2030 CFM 1250 - 2030 CFM -1250 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 355 - 1% 0 -
>> Total System Loads - 44303 3958 - -34 -5
Central Cooling Coil - 46473 3958 - 0 0
Central Heating Coil - -2170 - - 0 -
>> Total Conditioning - 44303 3958 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.80 Page 2 of 2