Calculation Months ................................. Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ............................................. Calculated Space CFM Sizing ........... Individual peak space loads
Total coil load ....................................................... 4.2 Tons Load occurs at ................................................. Jun 1500
Total coil load ..................................................... 50.4 MBH OA DB / WB ................................................. 114.0 / 85.0 °F
Sensible coil load ............................................... 46.5 MBH Entering DB / WB ........................................... 76.4 / 62.2 °F
Coil CFM at Jun 1500 ........................................ 2030 CFM Leaving DB / WB ............................................ 54.6 / 53.3 °F
Max block CFM ................................................. 2030 CFM Coil ADP .................................................................. 52.2 °F
Sum of peak zone CFM .................................... 2030 CFM Bypass Factor ........................................................ 0.100
Sensible heat ratio ............................................ 0.922 Resulting RH ............................................................... 45 %
ft²/Ton ............................................................... 178.5 Design supply temp. ................................................ 56.0 °F
BTU/(hr-ft²) ......................................................... 67.2 Zone T-stat Check ................................................. 1 of 1 OK
Water flow @ 12.0 °F rise .................................. 8.41 gpm Max zone temperature deviation ................................ 0.0 °F
Actual max CFM ................................................ 2030 CFM Fan motor BHP ........................................................ 0.46 BHP
Standard CFM ................................................... 1979 CFM Fan motor kW .......................................................... 0.37 kW
Actual max CFM/ft² ............................................. 2.71 CFM/ft² Fan static ................................................................. 1.00 in wg
Room Dimension :
L=75 ft; W=10 ft & H=10ft
Complete Partional Walls & No Infill added.