MCB
2 Trip-free mechanism, device operation 6 Heat dissipation gap provides better cooling
can not be defeated by holding the
operator in the ON position
1.2 Selection
Technical data of the network at the point considered:
the earthing systems (TNS, TNC),
short-circuit current at the circuit-breaker installation point,
which must always be less than the breaking capacity of
this device,
Network normal voltage.
Tripping curves:
B curve (3-5In)
protection for people and big length cables in TN and IT
systems.
C curve (5-10In)
protection for resistive and inductive loads with low inrush
current.
IEC/EN 60898-1 AC type B curve IEC/EN 60898-1 AC type C curve Let-through I2t/A2S I2t
t(s) t(s)
10000 10000 63A
105
5000 5000 50A
1h 1h 32A 40A
2000 2000 25A
5 20A
1000 1000
500 500
16A
10A
200 200
100 100 6A
4
50 50 10
20 20 4A
10 10 3A
5
5 5
2 2
1 1
0.5 0.5 2A
3
0.2 0.2 10
0.1 0.1
0.05 0.05 1A
0.02 0.02
0.01 0.01
0.005 0.005
0.002 0.002
2 3 4
0.001 0.001 10 5 10 5 10
0.5 1 2 3 4 5 7 10 20 30 50 70 100 200 I/In 0.5 1 2 34 5 7 10 20 30 5070100 200 I/In
Short-circuit current ip/A
2.2
Standard IEC/EN 60898-1
≤2
20
1.2
25
4
36
>12
50
>12
63
Is (kA)
>12
80
>12
100
>12
125
>12
160
>12
A
3 0.7 1.2 3.8 5.3 6 6 6 6 6
4 0.6 0.9 2.5 3.8 6 6 6 6 6
6 0.5 0.8 1.9 2.5 4.5 5 6 6 6
Load side: NB1-63G
10 0.7 1.4 2.2 3.2 3.6 6 6 6
16 1.2 1.8 2.6 3 5.6 6 6
20 1.5 2.2 2.5 4.6 6 6
25 1.3 2 2.2 4.1 5.5 6
32 1.7 1.9 3.8 4.5 6
40 1.7 3 4 5
50 1.5 2.6 3.5 4.5
63 2.4 3.3 4.5
25 40 40 40 40 30 30 30
32 40 40 40 40 30 30 30
40 40 40 40 40 30 30 30
50 30 30 30 30 30 30 30
63 20 20 20 20 15 15 15
Ambient temperature
-35℃ -30℃ -20℃ -10℃ 0℃ 10℃ 20℃ 30℃ 40℃ 50℃ 60℃ 70℃
Rated current(A)
1 7.80 7.56 7.38 7.14 6.84 6.60 6.24 6.00 5.76 5.64 5.28 4.98
2 13.20 12.70 12.50 12.00 11.50 11.10 10.60 10.00 9.60 9.30 8.90 8.40
3 21.12 20.48 20.00 19.20 18.40 17.76 16.96 16.00 15.36 14.88 14.24 13.44
4 26.40 25.60 25.00 24.00 23.00 22.20 21.20 20.00 19.20 18.60 17.80 16.8
6 33.00 32.00 31.25 30.00 28.75 27.75 26.50 25.00 24.00 23.25 22.25 21.00
10 42.56 41.28 40.00 38.72 37.12 35.52 33.92 32.00 30.72 29.76 28.16 26.88
16 53.20 51.20 50.00 48.00 46.40 44.80 42.40 40.00 38.40 37.20 35.60 33.6
20 67.00 65.50 63.00 60.50 58.00 56.00 53.00 50.00 48.00 46.50 44.00 41.50
25 83.79 81.90 80.01 76.86 73.71 70.56 66.78 63.00 60.48 58.90 55.44 52.29
When several simultaneously operating circuit breakers are mounted side by side in a small enclosure,
the temperature rise inside the enclosure causes a reduction in current rating.
You must then assign the rating (already derated if necessary according to ambient temperatuer) a downrating factor of 0.8.
-1.4
0
86
0 0 0 0
49.5±0.31 18 36 54 72
-0.43 -0.62 -1.2 -1.2
0
78
-1.2 1P 2P 3P 4P
1. General
A
1.1 Function
protection of circuits against short-circuit currents,
protection of circuits against overload currents,
switch,
isolation.
1.2 Selection
Technical data of the network at the point considered:
the earthing systems (TNS, TNC),
short-circuit current at the circuit-breaker installation point,
which must always be less than the breaking capacity of
this device,
Network normal voltage.
Tripping curves:
B curve (3-5In)
protection for people and big length cables in TN and IT
systems.
C curve (5-10In)
protection for resistive and inductive loads with low inrush
current.
2. Technical data
2.1 Curves
200 200
100 100
50 50
20 20
10 10
5 5
2 2
1 1
0.5 0.5
0.2 0.2
0.1 0.1
0.05 0.05
0.02 0.02
0.01 0.01
0.005 0.005
0.002 0.002
0.001 0.001
0.5 1 2 3 4 5 7 10 20 30 50 70 100 200 I/In 0.5 1 2 3 4 5 7 10 20 30 50 70 100 200 I/In
mm2 10
Installation Terminal size top/bottom for busbar
AWG 18-8
N·m 2
Tightening torque
In-Ibs. 18
Temperature compensation coefficient 1.20 1.15 1.10 1.05 1.00 0.95 0.90 0.875 0.85
45±0.31
-1.4
0
86
0
18 5.5 44±0.31
-0.43
60.7±0.37
0
76
-1.2
CB-60
Design number
A
Circuit breaker
3. Operating conditions
3.1 Ambient temperature: -35 ℃ ~ +70 ℃
3.2 Relative humidity: ≤ 95%
3.3 Class of pollution: 2
3.4 Altitude of the installation site does not exceed 2000m.
4. Technical data
4.1 Main classification
4.1.1 According to the rated current In, to divide into: 1A, 2A,
3A, 4A, 5A, 6A, 10A, 15A, 16A, 20A, 25A, 32A, 40A, 50A,
CB-60 60A, 63A.
4.1.2 According to number of poles, to divide into: AC: monopole,
Miniature Circuit Breaker dipole, triode, tetrode;DC: monopole, dipole.
4.1.3 According to standards compliant, to divide into:
1. General a.AC:GB10963.1, IEC60898-1, EN60898-1
b.DC:GB10963.2, IEC60898-2, EN60898-2
CB-60 miniature circuit breakers are suitable for AC
4.1.4 According to the instantaneous trip type, to divide into(see
50Hz/60Hz power distribution lines with the rated voltage
table 1)
of not exceeding 400V, rated current of not exceeding 63A,
Table1
and rated short-circuit capacity of not exceeding 6000A, and
Trip type AC range DC range
also for power distribution lines with DC voltage monopole
of not exceeding 110V, dipole of not exceeding 220V, rated B 3In<I≤5In 4In<I≤7In
014