ithin many refineries there is a grow- However, there are distinct limitations for these
ing tendency to process heavier crudes instrument types when a rag layer/emulsion
or blend these with lighter feedstocks. band occurs in the desalter. The principles of
During crude oil refining, it is advantageous to measurement of these instruments are examined
optimise the blend to reduce overall feedstock in more detail, including:
costs, while at the same time ensuring the final • Capacitance probes
mix can be adequately processed with minimal • Displacement interface gauges
upset. • Nucleonic gauges
One fundamental need within a refinery pro- • Guided wave radar.
cess is the efficient separation of wastewater
from crude feedstock using a desalter vessel Capacitance probes
after water washing the material to reduce chlo- Capacitance probes operate by measuring the
ride levels. In order to optimise this separation electrical characteristics of fluids that they con-
requirement, appropriate vessel and internals tact. As an interface level rises on the probe, the
design must be used alongside reliable level and measured capacitance changes as the probe goes
interface instrumentation. from complete immersion in oil (0% on the inter-
When applied to the relatively “dirty” ser- face level range) to complete immersion in water
vice experienced within a desalter, a number of (100% on the interface level range). One prob-
existing level and interface control instruments lem with this method of measurement is that if
have been found to demonstrate many short- the electrical characteristics of either fluid change
comings. Upon a request by a major oil refiner, significantly from the expected values, as will
the proprietary Tracerco Profiler instrument was happen when different feedstocks are introduced
redesigned. This instrument is commonly used to the vessel or when emulsions/rag layers are
in three-phase separation devices within the formed, the capacitance measured may change.
upstream oil and gas industry to withstand the This in turn can be interpreted incorrectly as a
elevated operating temperatures typically experi- change in level to operators and inappropriate
enced in a desalter vessel. control actions taken. In addition, capacitance
probes only measure a very small distance into
Common instruments used in desalter vessels a particular fluid. If the process material being
There are many types of level and interface measured is dirty and prone to surface coating,
instruments available that have been used to it can be rendered inoperable. As the capacitance
measure critical levels within desalter vessels. measurement requires contact with the process
The most common include displacement systems, fluid, any failure requires a shutdown for repair.
differential pressure, capacitance probes, micro- Therefore, this type of instrument is most
wave, guided wave radar, ultrasonic, thermal suited to measurement within fluids that are rela-
conductivity and nuclear. Out of this list, only tively clean and not prone to solids deposition. It
four have shown reasonable reliability for inter- is also advantageous to have a well-defined step
face measurement. These include displacement, change in density. In practice, this is rarely the
capacitance, guided wave radar and nuclear. case in a desalter.
Hazardous
area Safe area
Galvanic
10 V supply isolator Supply 24 VDC
Probe A
signal
processor
Power supply
Optional Fibre optic
to RS 232
signal cable converter Plant data
Probe B Allen Bradley
signal or Siemens
processor PLC Hard wired
Optional Fibre optic outputs
signal cable to RS 232
converter
H2O
Sand