Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

DAIKIN REFRIGERATION MALAYSIA SDN. BHD.

Time Code : 20230410151049


Project Name : NL AHU
AHU TECHNICAL REPORT AHU No. : LV Switchroom-2-B
Model Name : D DM2TB-0713B
D for DAIKIN

Software Version : EPOCH 5.0 Patch 8.03 Report Date : 19/4/2023 Unit Quantity : 1

*Supply Air Volume Unit Weight (approx) 517


Database Version : 2022.12.15 10100 m³/h 2.81 m³/s kg
Flow Rate : :

*Return Air Volume


Pricing Version : 2023.03.31 10000 m³/h 2.78 m³/s
Flow Rate :

Daikin Refrigeration Malaysia Sdn. Bhd is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. The range DMAHU is certified under the
number 09.11.441 and presented on www.eurovent-certification.com.
Certified in accordance with the AHRI Central Station Air-handling Unit Casing Certification Program, which is based on AHRI Standard 1350. Certified units may be found in
the AHRI Directory at www.ahridirectory.org
AHU specified in this report are manufactured by Daikin Refrigeration Malaysia Sdn. Bhd.

AHU Unit Specification


*This symbol is only for DRM internal use.
*Insulation Material
Cross Section (Bottom) : 1.62 m/s : Polyurethane-PU 40 kg/m³ *Delivery Mode : CBU
Air Velocity (Upper) : 0 m/s *Insulation Thickness : 50 mm Unit Orientation : Horizontal
*Inner Skin Thickness 0.5
::0.5 mm *Outer Skin Thickness : 0.5 mm Int Dim (Btm) : 1650Wmm
1050H x 1650Wmm
*Inner Skin Material GI
::GI *Outer Skin Material : GI Int Dim (Mid) : - mm
*Inner Surface Painted : No *Outer Surface Painted : Yes Int Dim (Top) : - mm
Recirculation units or units with design inlet temperatures always Design Winter
Application Type (Winter) : : 33 °C
> 9°C Outdoor Temp.
Application Type (Summer) Subgroup[1]
: - according to TCR - ECP-05-2020
Unit Length (Btm) : 2250 mm Unit Height (Btm) : 1230 mm Unit Width : 1750 mm

*Option Included : 80 mm GI Base Frame, SSTL Fastener at Frame,

CAL Class@(+400
Casing Strength Thermal Transmittance Thermal Bridging
Pa/ -400 Pa)
D1(M) L2(R) / L1(R) T2(M) TB2(M)
Eurovent Energy A+ N ⁽²⁰¹⁶⁾ / Int. Specific Fan Power : 3.54 W/(m³/s)
Efficiency Class
(Winter)⁽²⁰¹⁶⁾ /
D ⁽²⁰²⁰⁾ ErP Identification Code : NRVU-UVU
(Summer)⁽²⁰²⁰⁾
fs-Pref (Winter / Summer) 1 / 0.89
Thermal Transmittance
Casing Deflection CAL Class (+ve/
Class w/leakage / Thermal Bridging
Rating (+ve / -ve) -ve) @ 8''
w/o leakage
CD2 / CD2 CL2 / CL2 CT2 / CT2 CB2
Design dry-bulb temp (ASHRAE 2017 Climatic Design Conditions) 33
: °C Country : Singapore
Design dew-point temp (ASHRAE 2017 Climatic Design Conditions) 23.6
: °C Place : Singapore Changi Intl

Section Weights and Dimension

Section No #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12

Depth mm 2250

Weight kg 517

1 EXTERIOR FILTER

*Type AmWash
: Grade/Class
R50/M-Wash G4 : ePM Coarse / G4 Filter Brand AAF/MayAir
*Filter Media Yes
: (Factory Supply) Filter Face Velocity : 2.3 m/s
Casing Material : Aluminium
*Holding Frame Universal
: Initial or Clean
71.21 Pa
*Quantity (24'' x 24'') 2: Pressure Drop :
Media : Synthetic Final Pressure Drop :
*Quantity (20'' x 24'') 0: 121.21 Pa
Design Pressure
*Quantity (16'' x 24'') 0: Filter Energy Drop: 96.21 Pa
-
*Quantity (12'' x 24'') 3: Performance : Extra Pressure Drop 0.00
0
: .00 Pa

Page 1/4 Printed On 19/4/2023 3:49 PM


DAIKIN REFRIGERATION MALAYSIA SDN. BHD.Time Code : 20230410151049
Project Name : NL AHU
AHU TECHNICAL REPORT AHU No. : LV Switchroom-2-B
Model Name : D DM2TB-0713B
D for DAIKIN

Software Version : EPOCH 5.0 Patch 8.03 Report Date : 19/4/2023 Unit Quantity : 1

*Supply Air Volume Unit Weight (approx) 517


Database Version : 2022.12.15 10100 m³/h 2.81 m³/s kg
Flow Rate : :

*Return Air Volume


Pricing Version : 2023.03.31 10000 m³/h 2.78 m³/s
Flow Rate :

*Spare Filter Qty (set) 0: *Door Type :- *Door Handle Type ::--
2 WATER COOLING

GENERAL AIR SIDE WATER SIDE


*Coil Model : 2613-W1206RM-4 Air Volume : 10100 m³/h EWT / LWT : 18.00 / 25.00 °C
*Coil Medium : Water EDB / EWB : 33.00 / 26.00 °C Flow Rate (Total) : 1.25 L/s
*Rows/Fin per Inch : 6 / 12 LDB / LWB : 23.75 / 23.24 °C Tube Velocity : 0.29 m/s
Coil Layers : 1 ERH / LRH : 57.8 / 95.9 % Pressure Drop : 5.26 kPa
*Circuits per Coil : 39 Pressure Drop (Wet): 148.37 Pa Glycol Percentage : 0 %
Coil Volume : 27.030 dm³ Pressure Drop (Dry): 110.5 Pa ERH = Entering Air Relative Humidity

Coil - Wet Weight : 106 kg Mass Flow Rate : 12120.00 kg/h LRH = Leaving Air Relative Humidity

*Total Capacity : 36.72 kW Velocity : 2.41 m/s


Sensible Capacity : 31.31 kW Extra Pressure Drop : 0.00 Pa

TUBE FIN HEADER / FRAME


Material : Copper *Material : Aluminium *Header Material : Steel
*OD : 12.7 mm *Fin Protection : None *Connection Joint : Male Pitch Threaded
*Thickness : 0.406 mm Type : Corrugated *Header Size : 42 mm
Tube Height : 26 *Thickness : 0.115 mm Header Location : Right
Pattern : 31.75 x 27.5 *Height : 826 mm *Frame Material : GI
*Moisture Eliminator : None *Length : 1409 mm *Drain Pan Material : SSTL 304
ME Pressure Drop : - Pa *Width : 165 mm *Drain Pan Type : Standard
Drain Pipe Location : Right
*Connection Type : BSPT
*Flange JIS 10K : No
3 EMPTY SECTION

Name : access Opening Type : Opening Only *Rear/ Front Panel : No Panel
Drain Pan : No *Drain Pan Material : - Drain Pipe Location : -
*Top Opening (HxW) : - mm *Front Opening (HxW) -: mm *Rear Opening (HxW) -: mm
*Left Opening (HxW) : - mm *Right Opening (HxW) -: mm Pressure Drop : 0.00 Pa
Actuator Brand : NA Power Supply : NA Extra Pressure Drop: 0.00 Pa
Damper Torque : 0 Nm Section Depth : 500 mm
*Actuator : None
*Door Handle Type : Standard Door Size : 400 x 1000
*Door Type Removable
::Removable Drain Pan Width : -
4 EC SUPPLY FAN

GENERAL FAN MOTOR

*Supply Air Volume 10100.00 m³/h Type : Centrifugal Airfoil Electronically


*Motor Type :
Flow Rate : 2.81 m³/s Brand : EBM-Papst Commutated

*Altitude : 0.00 m *Model : K3G560PB3103 x 1ea *Eff Type : IE4


*Air Temperature : 20.00 °C Fan Size : 560 mm IP Rating :
Air Density : 1.20 kg/m³ Disch. Open (HxW) : 700x700 mm N Voltage : 400 V

Internal Static Total Efficiency : 69.0 % N Current : 6.6 x 1 fan A


244.58 Pa Page 2/4 Printed On 19/4/2023 3:49 PM
Pressure :
DAIKIN REFRIGERATION MALAYSIA SDN. BHD.Time Code : 20230410151049
Project Name : NL AHU
AHU TECHNICAL REPORT AHU No. : LV Switchroom-2-B
Model Name : D DM2TB-0713B
D for DAIKIN

Software Version : EPOCH 5.0 Patch 8.03 Report Date : 19/4/2023 Unit Quantity : 1

*Supply Air Volume Unit Weight (approx) 517


Database Version : 2022.12.15 10100 m³/h 2.81 m³/s kg
Flow Rate : :

*Return Air Volume


Pricing Version : 2023.03.31 10000 m³/h 2.78 m³/s
Internal Static Flow Rate :
244.58 Pa
Pressure : Static Efficiency : 63.1 % Fan Op. Current : 3.11 x 1 fan A

External Static Duct Velocity : 5.73 m/s Fan System Input


200.00 Pa 1.98 x 1 fan kW
Pressure : *Speed : 1284 RPM Power :

Other Static *Control Voltage : 6.43 V *Electrical Supply : 380-480V/3Ph/50/60Hz


0.00 Pa
Pressure : Min / Max Ambient : -25°C / 40°C Nominal Power : 4.4 x 1 fan kW
Velocity Pressure : 41.50 Pa Blade No. : 5 EC Elec junction box
*Electrical Panel :
Extra Pressure Drop: 0.00 Pa Specific Fan Power : 0.70 kW/(m³/s) panel

*Total Pressure : 486.08 Pa *Door Type : Hinged *Door Handle Type : Standard

# Design based on wet coil condition.

# The fan system effect is taken into account in the fan performance.

Sound Power
Sound Power, Lw 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Total (dBA)
In-duct Outdoor Air dB 73 75 75 68 70 71 73 65 78
In-duct Supply Air dB 76 78 75 75 78 74 75 69 82
Casing Sound Power Level dB 65 66 63 61 62 61 49 32 66

DOOR LOCATION

No Component Name Location No Component Name Location


1 Empty Section Right 1 Supply EC Fan Right

UNIT MODEL REMARK


CUSTOMER :
MANUFACTURER :

SPECIAL REMARK

No Component Name Remark


1. For unit total height exceeded 2550 mm, or section length and width exceeded 2250 mm, it will
be delivered in SKD/CKD with standard container unless specified by customer to be still in CBU
mode and using open-top/flat rack containers.
1 Unit Model
2. Electrical wiring design and installation on the unit are based on factory standard practice. All
installation activities must be carried out by qualified personnel, and shall ensure compliant with
relevant local laws and regulations.

Page 3/4 Printed On 19/4/2023 3:49 PM