PICKUP - QCM:: Test Module
PICKUP - QCM:: Test Module
PICKUP - QCM:: Test Module
qcm:
Test Module
Name: OMICRON QuickCMC Version: 4.00
Test Start: 08-Feb-2022 11:19:10 Test End: 08-Feb-2022 11:23:51
User Name: Manager:
Company:
Test Results
Title: PU OCR
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct IR 2,650 A 0,00 ° 50,000 Hz
IS 2,650 A -120,00 ° 50,000 Hz
IT 2,650 A 120,00 ° 50,000 Hz
Generator Settings
IR 2,650A 0,00° +90°
IS 2,650A -120,00° IT
IT 2,650A 120,00°
IR
180° 0°
IS
3,0 A -90°
Binary Inputs
Name Slope Time
Trip 0
Start 0
Overload 0
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct IR 2,550 A 0,00 ° 50,000 Hz
IS 2,550 A -120,00 ° 50,000 Hz
IT 2,550 A 120,00 ° 50,000 Hz
Generator Settings
IR 2,550A 0,00° +90°
IS 2,550A -120,00° IT
IT 2,550A 120,00°
IR
180° 0°
IS
3,0 A -90°
Binary Inputs
Name Slope Time
Trip 0
Start 0
Overload 0
Title: PU GFR
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct IR 248,0 mA 0,00 ° 50,000 Hz
IS 0,00 A -120,00 ° 50,000 Hz
IT 0,00 A 120,00 ° 50,000 Hz
Generator Settings
IR 0,248A 0,00° +90°
IS 0,000A -120,00°
IT 0,000A 120,00°
IR
180° 0°
300,0 mA-90°
Binary Inputs
Name Slope Time
Trip 0
Start 0
Overload 0
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct IR 241,0 mA 0,00 ° 50,000 Hz
IS 0,00 A -120,00 ° 50,000 Hz
IT 0,00 A 120,00 ° 50,000 Hz
Generator Settings
IR 0,241A 0,00° +90°
IS 0,000A -120,00°
IT 0,000A 120,00°
IR
180° 0°
300,0 mA-90°
Binary Inputs
Name Slope Time
Trip 0
Start 0
Overload 0
Summary
4 tests passed, 0 tests failed, 0 tests not assessed 100,00% passed
Test passed (manually assessed!)