IM SM Avanta Plus EN

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 64

P l u s

Av a n t a
Installation and service manual

R e m e h a
Remeha Avanta Plus
• Remeha Avanta Plus 28c

• Remeha Avanta Plus 35c

• Remeha Avanta Plus 39c

• Remeha Avanta Plus 24s

1
Remeha Avanta Plus

INTRODUCTION

1 SAFETY 5
1.1 General safety 5
1.2 Safety during assembly and installation 5
1.3 Safety during installation, inspection and maintenance 5

2 INSTALLATION 7
2.1 Scope of delivery 7
2.2 Mounting the boiler 7
2.2.1 Clearance requirements 7
2.2.2 Dimensions and connection points. 8
2.2.3 Mounting the Remeha Avanta Plus 10
2.3 Water-side connections 10
2.3.1 Water flow 10
2.3.2 Circulation pumps 11
2.3.3 Additional guidelines for the domestic and CH water 11
2.3.4 Water treatment 11
2.3.5 Safety valve discharge 12
2.3.6 Expansion vessel 13
2.3.7 Connecting DHW pipes (Combi-type only) 13
2.3.8 Connecting the ‘CH return’ 14
2.3.9 Connecting ‘CH flow’ 14
2.3.10 Connecting condensate drain 15
2.3.11 Connecting under floor heating 15
2.4 Gas-side connections 15
2.4.1 Additional guidelines for gas connections 15
2.4.2 Connecting the gas supply 16
2.5 Flue terminal and air supply connections 16
2.5.1 Flue terminal positions 16
2.5.2 Room sealed flue 17
2.5.3 Connecting the flue terminal and air supply 18
2.6 Electrical connection 19
2.6.1 The control unit 19
2.7 Connecting external controls 20
2.7.1 On/off control – room temperature (volt free switching) 22
2.7.2 Time control using an internal or external 230 V clock 23
2.7.3 Connecting a 230 V time clock in combination with a modulating room control 23
2.7.4 Modulating control – room or outside compensation 23
2.7.5 Connecting an outside temperature sensor 24
2.7.6 Connecting the DHW sensor/thermostat 25
2.7.7 Connecting a frost protection device 25
2.7.8 Connecting an external interlock 26
2.7.9 Connecting remote alarm and boiler run indication 26
2.7.10 Connecting a PC/PDA 26
2.8 Wiring diagram 27
2.9 Commissioning 27
2.9.1 Control Panel 27
2.9.2 Additional guidelines for commissioning 27
2.9.3 Putting the boiler into operation 27
2.9.4 Normal start-up procedure 33
2.9.5 Error during the start-up procedure 33
2.9.7 Adjust the boiler according to the system 35
2.9.8 Changing the parameters at service level (with access code) 35
2.9.9 Changing the maximum output (Hi) for CH operation 37
2.9.10 Restore factory settings 39

2
2.10 Putting the boiler out of operation 39
2.10.1 Boiler with frost protection, during longer periods of non-use 39
2.10.2 Boiler without frost protection, during longer periods of non-use 39

3 INSPECTION AND MAINTENANCE 40


3.1 Inspection 40
3.1.1 Checking the water pressure 41
3.1.2 Checking the flue pipes and air supply pipes for leaks 41
3.1.3 Checking the condensate siphon 42
3.1.4 Checking the ignition electrode 42
3.1.5 Checking the combustion 42
3.2 Maintenance 43

4 ERRORS 49
4.1 General 49
4.2 Error codes 49
4.3 Control stop or shut down 51
4.4 Error memory 51
4.4.1 Error read outs 52
4.4.2 Deleting errors 52

5 SERVICE PARTS 53
5.1 General 53

6 EC DECLARATION 56

7 REGULATIONS 57
7.1 EC regulations 57
7.2 Remeha factory test 57

8 TECHNICAL SPECIFICATIONS AND WORKING PRINCIPLE 58


8.1 Technical data 58
8.2 The boiler components 59
8.3 Working principle 59
8.3.1 Regulating 60
8.3.2 Advanced boiler control (‘abc®’-control) 60
8.3.3 Regulating the water temperature 61
8.3.4 Low flow / water protection 61
8.3.5 High Limit temperature protection 61

9 EFFICIENCY DATA AND GAS EFFICIENCY LABELS 62


9.1 Annual efficiency 62
9.2 Water-side efficiency 62

3
Remeha Avanta Plus

INTRODUCTION

The Remeha Avanta Plus is a series of high-efficiency fully


condensing central heating boilers, for wall mounting,
available in the following types:
• Remeha Avanta Plus 28c, 35c and 39c
- with integrated domestic hot water system (Combi-type)
• Remeha Avanta Plus 24s
- without integrated domestic hot water system
(System-type)

These technical instructions contain useful and important infor-


mation for the correct installation, operation and maintenance
of the Remeha Avanta Plus combi and system boilers.

o
Read these instructions carefully before putting the boiler into
operation, familiarise yourself with their control functions and
operation, strictly observing the instructions given. Failure to
do so may invalidate warranty or prevent the boiler from
operating correctly.

The installation, commissioning, inspection and servicing of the


boiler must be carried out by a competent Corgi registered engi-
neer who holds valid ACOPS certification and in accordance
with current gas safety (installation and use) regulations, the
building regulations and all other relevant codes of practice.
All electrical work must be carried out by a competent engi-
neer and to be installed in accordance with the current IEE
regulations.

o
On commissioning the certificate in the Boiler Service Log
book (supplied with the boiler) must be completed and left on
site with a copy send on to Broag Ltd for registration purposes.
LT.AL.W7H.000.001

If you have any questions, require an engineer to call on site,


or if you need more information about specific subjects relating
to this boiler, or it's installation please do not hesitate to con-
tact our technical help line 0118 978 3434.

o
When contacting Broag with a problem on the boiler, please
have available the boiler type, Serial No (located on the
bottom of the casing), and the symptoms or fault code (the
fault code is a series of flashing red digits in the display panel).

The data published in these technical instructions is based on


the latest information (at date of publication) and may be sub-
ject to revisions.
We reserve the right to continuous development in both design
and manufacture, therefore any changes to the materials or
technology employed may not be retrospective nor may we be
obliged to adjust earlier supplies accordingly.

4
1 SAFETY

1.1 General safety


The following pictograms are used in this Installation and Serv-
ice manual to specifically draw certain points to your attention:

Tip o Useful tip or practical advice.

Indication z Important instruction in carrying out a


particular operation.

Warning m Possible danger of personal injury or


material damage to the regulator,
building or environment.

Danger { Serious personal injury can occur


because of risk of electric shocks.

1.2 Safety during assembly and installation


Observe the appropriate safety measures, as given in these
instructions.

m
Can you smell gas? What to do:
• do not smoke and do not create any flame or sparks;
• do not use any electric switches;
• turn off the gas tap;
• open windows and doors;
• trace possible leaks and seal them.
Warning! If the leak is before the gas meter, alert your gas
supplier, TRANSCO, tel. 0800 111 999

m
Can you smell smoke or flue gasses? What to do:
• isolate power supply.
• open windows and doors;
• trace possible leaks and seal them.

1.3 Safety during installation, inspection and


maintenance
Under the current Gas Safety (Installation & Use) Regulations,
the Remeha Avanta Plus, in common with all gas appliances,
must be installed by a competent person in accordance with
that regulation.
Statutory regulations in any country, cannot be overridden by
any of the notes or instructions from the manufacturer.
Compliance with National Standards does not provide any
degree of immunity from legal obligations. In the UK, the
installation must be in accordance with the national and local
norms and requirements.

For any issues or circumstances not addressed within these


instructions, please call our Customer Care Department.

5
Remeha Avanta Plus

The Remeha Avanta Plus (combi and system) is a WRAS


(Water regulations) approved product.

Remeha Avanta Plus (combi and system) - PIN:


0063BQ3009
Gas Council numbers: Remeha Avanta Plus 28c: 47-673-02
Remeha Avanta Plus 35c: 47-673-03
LT.AL.W7H.000.074
Remeha Avanta Plus 39c: 47-673-04
Remeha Avanta Plus 24s: 41-288-05

Classification type for evacuation of the combustion products;


according EN 483: see Par. 8.1.

Health and safety information


• The weight of the Avanta Plus system and combi boilers
exceed the maximum lift weight for one person. Please
ensure all necessary care is taken when lifting the boiler on
to the wall mounting plate.
• All sealants and gaskets are free from harmful products. On
first firing the boiler, a smell from the sealants and gaskets
may be present and should cease after a short period.

6
2 INSTALLATION

2.1 Scope of delivery


The standard delivery of the Remeha Avanta Plus boiler
includes:

- the boiler (including pressure gauge and safety valve);


- mounting plate (including isolation valve set and washers);
- nylon plugs and screws for fixing mounting plate;
- copper tails 15/22 mm;
- mounting template;
- filling loop;
- Boiler Service Log Book;
- Installation and Service manual and Users guide.

This Installation and Service manual deals with the standard


supplied boiler only. For the installation or assembly of any
optional accessories supplied with the boiler, such as stand off
frame, pipework kits, cover plate, control kits, etc, please refer
to the Assembly Instructions supplied with these accessories.

2.2 Mounting the boiler


Packed in the box with the Remeha Avanta Plus box is
this Installation and Service manual. Read instructions and
remarks carefully. This section includes the guidelines and
instructions for the connection of gas, water, electricity, safety
devices, the regulator, control unit, flue discharge and air sup-
ply.

2.2.1 Clearance requirements


The gas and water connections are located on the bottom of
LT.AL.W7H.000.011 the boiler whilst the air in and flue gas outlet is located on the
top of the boiler. The boiler is supplied as standard with pipe-
40
work tails to allow connections facing downwards.
0
Optional stand off frame and pipework kits are available
to enable the pipework to run upwards behind the boiler if
required. For installation, servicing and inspection min. 600
mm in front of the boiler is required. If this free space is
mi
n. obtained by opening a door or removing a panel, the boiler
25
0 may be installed for instance in a closed cupboard.
For ease of installation we recommend clearances of 0.5 cm
at the side so that the unit is easy to open, with a free space
of 25 cm under the appliance and 25 cm above the appliance,
67 as the minimum requirement.
0
However once installed, it is possible to reduce these clear-
ances to 22 cm at the top, and 5 cm at the bottom provided
the boiler front panel can be removed and the isolating valves
are easily accessible without the use of tools”
mi
n.
25
0

0
30

00
n.6
mi

LT.AL.W7H.000.003

7
Remeha Avanta Plus

2.2.2 Dimensions and connection points.


system type
— Return connection Ø 22 mm
– Flow connection Ø 22 mm
œ Gas connection Ø 22 mm
 Combustion air inlet Ø 100 mm (concentric)
ž Flue duct Ø 60 mm (concentric)
Ÿ Condensate drain connection ¾”
(standard overflow pipe size)
º Connection safety valve Ø 15 mm

LT.AL.W7H.000.005

8
 combi type
— Return connection Ø 22 mm
– Flow connection Ø 22 mm
œ Gas connection Ø 22 mm
 Combustion air inlet Ø 100 mm (concentric)
ž Flue duct Ø 60 mm (concentric)
  DHW inlet (cold) connection Ø 15 mm
¢ DHW outlet (hot) connection Ø 15 mm
Ÿ Condensate drain connection ¾”
(standard overflow pipe size)
º Connection safety valve Ø 15 mm

z
• Based on the guidelines and the required installation space,
determine where to mount the Remeha Avanta Plus.
• In determining the boiler position, consider carefully the flue
outlet position and any pluming consequences.

LT.AL.W7H.000.002

9
Remeha Avanta Plus

2.2.3 Mounting the Remeha Avanta Plus

• Remove the mounting plate and template from the box.


• Using the template determine and mark the position of the
three mounting holes and center line of flue, making sure
the plate is absolutely level.
• Drill the (Ø 10 mm) holes.
• Fit the (Ø 10 mm) plugs.
• Fit (Ø 8 mm) screws into the plugs.
• Check the mounting plate is level and tighten the screws.
• Fit the valve set to the mounting plate.
• Fit fibre washers on the CH valves.
• Remove boiler from the box and suspend it on mounting
plate.
• Connect the valves to the boiler remembering to fit fibre
washers supplied.
• Connect the supplied copper tails to the isolating valves.

m
• The boiler should be mounted on a suitable vertical wall
which is able to support the weight of the boiler.
• The boiler should be mounted in a room which, even during
severe cold weather, remains frost-free.
• If the boiler is to be installed in a timber framed building,
please refer to British Gas publication: ‘Guide for Gas
Installations in Timber frame Housing’, reference DM2.
• In a new installation it is possible to fit just the wall plate
and valve set to enable the system pipework to be complet-
ed and tested before fitting the boiler at a later date (place
fibre washers supplied in a safe place for use when fitting
the boiler).

z
• Make sure the boiler and any open connections are protec-
ted from building dust etc. during the installation.
• There must be a 3 amp fused switched spur within 1m of
the boiler.
• Provision must be made for the condensate discharge.

2.3 Water-side connections

2.3.1 Water flow


An internal automatic flow by-pass is supplied in the Avanta
Plus to ensure correct operation on systems fitted with TRV’s
on all heat emitters. The ‘abc®’ control also monitors the tem-
perature difference across the flow and return connections and
the rate of temperature rise and will automatically regulate the
boiler output to ensure that it remains operational for as long
as possible without the need to ‘lock out’ requiring a manual
re-set.

LT.AL.W7H.000.012

10
2.3.2 Circulation pumps
The Remeha Avanta Plus 24s and 28c are fitted with the
Grundfos UPR 15-60 and the Avanta Plus 35c and 39c with
the UPR 15-70, two-speed circulation pumps. The control unit
ensures that when the hot-water function is active, the pump
runs at ‘high’. The factory setting of the pump for CH func-
tion is ‘low.’ If necessary, the service installer can adjust this
to ‘high’ by switching parameter 21 (from 0 to 1) see par.
2.9.8.

2.3.3 Additional guidelines for the domestic and CH water


Residual head UPR 15-60 • The system should be filled with mains cold water (for the
600
UK this will usually have a pH of between 7 and 8).
500 • Power flush the pipes and radiators thoroughly to remove all
Residual head [mbar]

dT 20°C 18kW fluxes and debris before connecting the boiler to the central
400 heating system in accordance with BS 7593 (1992).
Pump 'high'
300

m
Pump 'low'
200

• The temperature of the central heating pipes and the


100
radiators can rise to 95°C.
0 • Use untreated tap water only to fill the CH system.
0 200 400 600 800 1000 1200
CH-flow [l/h] • The pH value of the system water must be between 6
LT.AL.W7H.000.013 and 9.
• In case inhibitors are being used, please follow the
instructions given in par. 2.3.4.
Residual head UPR 15-70
700
2.3.4 Water treatment
600 If used correctly water treatment can improve the boilers
Residual head [mbar]

Pump 'high' dT 20°C 28kW


efficiency and increase the anticipated life expectancy of the
500
boiler. For further information a special document “Quality
400 requirements CH water” is available from Broag.
Pump 'low'
300
As most systems contain a variety of metals, it is considered
200
good practice to provide some form of water treatment in order
100 to prevent or reduce the following:
• Metallic corrosion
0
0 200 400 600 800 1000 1200 1400 1600 • Formation of scale and sludge
CH- flow [l/h]
• Microbiological contamination
LT.AL.W7H.000.014 • Chemical changes in the untreated system water

m
All scale deposits however small will reduce the efficiency of
the boiler and should be prevented.

Suitable chemicals and their use should be discussed with a


specialist water treatment company prior to carrying out any
work (environmental aspects, health aspects). The specifica-
tion of the system and manufacturers recommendations must
be taken into account, along with the age and condition of
the system. New systems should be flushed thoroughly to
BS 7593(1992) to remove all traces of flux, debris, grease
and metal swarf generated during installation. Care to be
taken with old systems to ensure any black metallic iron oxide
sludge and other corrosive residues are removed, again by
power flushing, ensuring that the system is drained completely
from all low points.

11
Remeha Avanta Plus

z
Please ensure that the new boiler plant is not in circuit when
the flushing takes place, especially if cleansing chemicals are
used to assist the process.

It is important to check the inhibitor concentration after installa-


tion, system modifications, filling the system and every service
in accordance with these instructions.

For the correct dosage and the suitability of inhibitors for use
with our boilers and for further information on water treatment
or system cleaning we advise direct contact with either of the
following companies:

‘Copal®’ manufactured by:


Fernox, Cookson Electronics
Forsyth Road
Sheerwater
Woking
Surrey GU21 5RZ
Tel No: 01483 793200
Fax No: 01483 793201
Email: sales@fernox.com
Web site: www.fernox.com

or:
Sentinal ‘X100®’ manufactured by:
BetzDearborn Ltd
Sentinal
Foundry Lane
Widnes
Cheshire WA8 8UD
Tel No: 0151 424 5351
Fax No: 0151 420 5447

2.3.5 Safety valve discharge


A pressure relief safety valve is fitted in the boiler set to the
maximum operating pressure of the boiler at 3 bar.
If the pressure in the boiler becomes too high the pressure is
relieved by releasing water outside via the safety valve dis-
charge pipe. A safety valve should be fitted in accordance with
the British standards. The safety valve discharge pipe must be
at least 15 mm Ø. The discharge should be terminated facing
downwards exterior to the building in a position where dis-
charging water will not create danger or nuisance but remains
in a visible position.

12
2.3.6 Expansion vessel
An 8 litre expansion vessel (with the vessel charge set to 1.0
bar) is fitted as standard within the boiler case and is suitable
for use in a heating system with a water content up to 100
litres, operating at a flow temperature of 80°C, a maximum
pressure of 3 bar and a maximum system static head of 5
metres above the boiler. If the system water content is greater
than 100 litres, or the system static head above the boiler is
greater than 5 m, an additional vessel must be installed in the
system to allow for the increase in expansion, see table 01.

m
Install additional vessel according BS 5449, part1.

Boiler Safety Valve Setting


(Bar) 3.0
Vessel Charge (Bar) 0.5 1 1.5
Heating System Water Content Expansion Vessel Size
(Litres) (Litres)
100 4.8 8.0 13.3
125 6.0 10.0 16.6
150 7.2 12.0 20.0
175 8.4 14.0 23.3
200 9.6 16.0 26.6
250 12.0 20.0 33.3
300 14.4 24.0 39.9
For other system volumes, mul-
tiply the system volume by the 0.048 0.080 0.133
factor across:
table 01 Expansion Vessel Size

2.3.7 Connecting DHW pipes

• Fit the outlet pipe for hot water to the DHW outlet ¢
15 mm Ø connection.
• Fit the inlet pipe for cold water to the DHW inlet   15 mm
Ø connection.

z
• The DHW pipes must be connected in accordance with
current regulations.
• For plastic pipes, follow the manufacturer’s instructions (for
connection).

LT.AL.W7H.000.015

13
Remeha Avanta Plus

2.3.8 Connecting the ‘CH return’

• Fit the inlet pipe for CH water to the ‘CH return’ — 22 mm


Ø connection.

o
The Remeha Avanta Plus has a drain cock built into the return
isolating valve
It is considered good practice to install an air separator / dirt
removal device in the return to the boiler.

LT.AL.W7H.000.016

2.3.9 Connecting ‘CH flow’

• Fit the outlet pipe for CH water to the ‘CH flow’ – 22 mm


Ø connection.


o
The Remeha Avanta Plus has a drain cock built into the flow
isolating valve.

LT.AL.W7H.000.017

14
2.3.10 Connecting condensate drain

• Connect the condensate drain outlet Ÿ to a suitable waste


water drain point using acid resisting pipe work (i.e. - ¾”
overflow) To enable the siphon in the boiler to be removed
/ serviced, the connection should not be a permanent one
(i.e. “push fit” system).
• To prevent the risk of freezing connect the condensate into
an internal vertical soil pipe using a tundish (air break) c/w a
min 75 mm water seal trap.
• If the condensate pipe has to run externally make sure
this is done by realizing the shortest possible route, and
increase the diameter to at least 1¼” or insulate it with
weather resistant insulation.
• The drain should slope at least 3 cm per meter, with a maxi-
mum horizontal length of 5 m.

z
• If connecting into an internal discharge branch (i.e. sink
waste etc) the connection must be down stream of the
existing waste trap.
• Fill the boiler siphon with water before operation, to
prevent flue gasses discharging into the room.
LT.AL.W7H.000.018 • The condensate drain must be connected in accordance
with current regulations.

2.3.11 Connecting under floor heating


The Remeha Avanta Plus can be connected directly to an
under floor heating system.
If plastic pipes have been used they must be made oxygen dif-
fusion proof in compliance with DIN 4726/4729
When installing under floor heating with a separate pump, the
layout should be such that the under floor heating pump can-
not cause a flow to the boiler if there is no heat demand. A low
loss header should therefore be fitted between the system and
the boiler.

z
Please ensure that the residual pump duty of the boiler is
sufficient for the resistance of the under floor system. If not a
low loss header should be used to separate the boiler from
the under floor circuit to allow a separate pump sized for the
resistance of the under floor system to be used.

2.4 Gas-side connections

2.4.1 Additional guidelines for gas connections

m
Before installation, check that the gas meter has sufficient
capacity for the demand. Remember to consider the
consumption of all household appliances.

15
Remeha Avanta Plus

2.4.2 Adjusting boiler to other gas-type


The Avanta Plus boilers are suitable for both natural gas and
propane firing. For the Avanta Plus 39c an optional LPG-set is
needed.
The boilers are supplied as standard set for natural gas
(H), therefore the following procedure must be carried out
BEFORE the boilers are fired and commissioned for the first
time on propane:
Adjust the fan speed (see Par. 2.9.8) and adjust the gas/air
ratio (see Par. 2.9.3).

2.4.3 Connecting the gas supply

• Before starting any work on the gas supply, turn off the main
isolation valve.
• Connect the gas supply œ to the 22 mm Ø boiler
connection.

m
• Make sure there is no dirt in the gas pipe. Blow through
the pipe before installation or tap well to purge.
• Make sure that the minimum gas service pressure is high
LT.AL.W7H.000.019 enough (in full load > 17 mbar).
• Preferably install a gas filter in the gas pipe to prevent the
gas block from getting dirty.
• The gas supply must be connected, tested for soundness
and purged by a qualified Engineer and in accordance
with BS6891.

2.5 Flue terminal and air supply connections


The Remeha Avanta Plus is only suitable for room sealed
operation with a standard concentric connection 60/100 mm Ø
or the optional 80/125 mm Ø connection.
Detailed recommendations for air supply and flue terminals are
given in BS 5440.

z
It should not be necessary to provide compartment ventilation
when the boiler is used with a standard concentric flue.

2.5.1 Flue terminal positions


The flue terminal must be located with care to ensure that the
products of combustion are dispersed properly in all weather
conditions and cause minimum nuisance to the building user
or any adjacent buildings. If the terminal is positioned less
than 2 m above the ground, balcony, or flat roof where access
by persons is possible a suitable guard must be employed.

z
The boiler will produce a water vapour plume during normal
operation.

Positions for the Remeha Avanta Plus are shown in the figure
and table 02.

16
A Dimen- Terminal location Minimum
sions distance
600 mm
(in mm)
No flue must penetrate
600 mm
area within dotted lines to terminal
S round roof light
(room
2000 mm
G S sealed)
D,E
A Directly below an opening, air brick,
F B 300
C opening window, etc.
B Above an opening, air brick, opening
P A M 300
J window, etc.
H L
G J C Horizontally to an opening, air brick,
300
opening window, etc.
K,N
D Below a gutter or sanitary pipe work 40 1)
E Below the eaves 40 1)
F Below a balcony or carport roof 40 1)
G Above ground, roof or balcony level 300
LT.AL.W7H.000.020 H From vertical drain/soil pipe work 40 1)
J From an internal or external corner 40 1)
K From a surface or boundary facing the 2)
600
terminal
L Vertically from a terminal on same wall 1500
M Horizontally from a terminal on same
300
wall
N From a terminal facing the terminal 1200
P From an opening in a carport (e.g.
1200
door, window) into the building
R From a vertical structure on the roof n/a
S Above an intersection with the roof n/a
table 02 Minimum distances to terminal
1)
= We advise to use deflectors in case of these small dis-
tances.
2)
= Where the terminal is positioned directly opposite an
opening in the facing wall the min will be 2 m.
n/a = not applicable.

2.5.2 Room sealed flue


See table 03 for the maximum pipe length of flue ducts and air
supply pipes for this ‘room sealed’ application.
It is not necessary to provide combustion air to the room or
internal space in which the boiler is installed.

24s 28c 35c 39c


VRS roof Diameter in mm Ø 60/100 80/125 60/100 80/125 60/100 80/125 60/100 80/125
mounted
room sealed Maximum length ‘L’ allowed [m] 6 29 6 29 7 30 5 25
terminal
Eq. Length of 90° elbow
L
1.4

L
Eq. Length of 45° elbow
0.65
80/125 or 60/100

table 03 Maximum pipe lengths for flue duct and air supply in
room sealed application
17
Remeha Avanta Plus

z
For flue installations not covered by this booklet, please
contact our technical help line 0118 978 3434.

2.5.3 Connecting the flue terminal and air supply

• Check the depth of the wall and cut the terminal to suit
– taking note of the cutting instructions supplied with it
• Core drill a 125 mm Ø hole in the wall, fit the rubber closure
ø 125 mm plate at the exit end and slide the terminal through the wall
until the closure plate is clear of the outer edge of the wall
158 mm – pull back the terminal till the closure plate is flush then fit
inner wall closure to secure.

z
• All connections must be airtight and waterproof.
• Horizontal extension sections should slope towards the
boiler (at least 3 cm per metre).

1
2

LT.AL.W7H.000.021

18
2.6 Electrical connection
• Connect the boiler to the fused (3 amp) switch spur unit
adjacent to boiler.
• The switch unit must always be accessible.

{
When the switch spur is on the following components of this
230 V appliance can be live (230 V):
• electrical connection pump;
• electrical connection gas combination block;
• electrical connection three-way valve;
• most parts of the control unit;
• ignition transformer;
• X1, X2, X4, X5, X6 and X7 terminal strip;
• 230 V supply cable connection.

LT.AL.W7H.000.022

2.6.1 The control unit


The Remeha Avanta Plus has an electronic regulation and
control unit with an integrated ionisation flame detector. The
heart of the boiler control unit is a microprocessor, the ‘abc®’,
which controls and protects the boiler.

The maximum rated input is between 115 and 180 W (depend-


ing on boiler type).
The boiler is fully pre-wired internally, all external connections
can be made using the terminal strips X5 - X7 - X9 and 230
V input (X2 terminal). See the diagram for the position of the
connectors and fuse (F2) on the control unit.
The most important properties of the control unit are summa-
LT.AL.W7H.000.023 rized in table 04.

19
Remeha Avanta Plus
Manufacturer Sit Controls
Supply voltage 230 V – 1ph – 50 Hz
Pre-purge time 3s
Post-purge time 5s
Ignition time 2.5 s
Safety time 5s
Anti-cycling time 3 till 10 min.
Fuse value F1 (230 V) 2 AT
DC fan 24 VDC
table 04 Control unit characteristics

m
Any loads other than those specified above are only allowed if
an isolating transformer is used.

The output of the Remeha Avanta Plus can be controlled in


the following ways:
On/off control – volt free switching - The boilers internal
control will modulate the output to achieve the flow tempera-
ture set point of the boiler. This contact is on the X9 terminal
strip (low voltage only).
Modulated control – Open Therm - The external controls will
modulate the boiler’s output to achieve the flow temperature
determined by the modulating regulator. This contact is on the
X9 terminal strip (low voltage only).
On/off control – 230 V switching - The boilers internal con-
trol will modulate the output to achieve the flow temperature
set point of the boiler. This contact is on the X2 terminal strip
(230 VAC only).
2 Modulated control – Open Therm in combination with an
externally mounted simple 230 V switching time clock -
The boiler will provide room compensated heating and time
control over CH and DHW (System boiler).

z
• All connections on terminal X1, X2, X4, X5, X6 and X7
are 230 VAC.
• All connections on terminal X9 are low voltage only.
1

2.7 Connecting external controls


• Release the two screws at the bottom of the front casing
and remove the front casing.
• Feed the cables through the grommet in the base of the
boiler.
• Connect the cables to the relevant connectors, as shown in
the diagrams.

{
• Isolate power supply at the fused spur before carrying out
any work on the boiler controls.

LT.AL.W7H.000.024

20
Terminal
Block X6
L 230v - 3 Amp
N Power Supply X2
E
Terminal
Block X7

1
Common Alarm
X5
(Closes on alarm) Boiler Run
X6
2 X7
(Closes on run)
3 X9

Terminal
Block X5

1 Neutral
For external DHW priority
Open valve to DHW (230v) diverting valve on System boiler
2 when used in conjunction with
"Open Therm" compensation
3 Open valve to HTG (230v)

Terminal
Block X9

1 Outside sensor (red band) for direct boiler weather compensation


or when used in conjuction with a compatable Open Therm
2 control eg: Chronotherm or Celcia 20

3 DHW sensor (red band) or volt free thermostat (make on temp fall)
Remove existing link to use this function
4

Exist 5
External interlock (volt free)
links Remove existing link to use function
6

7 Modulating - using Open Therm control


eg: Honeywell Chronotherm or Celcia 20
On / Off - using volt free switching control
8 eg: Celcia 10 or low volt room thermostat

Terminal
Block X2

5 N
Power supply to external time clock -230v
4 L
Switch live (230v) from external time clock DHW demand
3 Remove existing link 4-3 to use this function
Exist
links 2
Switch live (230v) from external time clock HTG demand
1 Remove existing link 4-1 to use this function

NOTE: Terminal blocks are not in line as shown - diagramatic only

LT.AL.W7H.000.025

21
Remeha Avanta Plus

2.7.1 On/off control – room temperature (volt free


switching)

The Remeha Avanta Plus can be connected to a 2-wire on/off


thermostat, such as the Remeha Celcia 10.
Mount the thermostat in a reference room (usually the living
Terminal
Block X9
room).
• Remove existing link between connectors 7 and 8 of the X9
1
terminal strip before use;
2
• Connect the 2-wire 24 V room thermostat to connectors 7
3 and 8 of the X9 terminal strip.
X9
4

Exist
5 z
links 6 If a room thermostat with an anticipation resistor is being used,
7 Modulating - using Open Therm control
parameter p5 should be changed from 0 to 1, see par.
eg: Honeywell Chronotherm or Celcia 20 2.9.8.
8 On / Off - using simple volt free switching control

LT.AL.W7H.000.026

2.7.2 Time control using an internal or external 230 V


clock

{
When the switch spur is on, the terminal strip X2 will be live
(230 V).

• A 230 V two channel time clock for CH and DHW control


can be connected to the Remeha Avanta Plus.
Live 230 V supply for the time clock - connect to connectors
4 (L) and 5 (N) on X2 terminal strip.
X2 • For CH - remove existing link between connectors 4 and 1
of the X2 terminal strip and connect the 230 V output from
the time clock to terminal 1 on the terminal strip X2.
Terminal • For DHW - remove existing link between connectors 4 and
Block X2
3 of the X2 terminal strip and connect the 230 V output from
5 N
Power supply to external time clock -230v the time clock to terminal 3 on the terminal strip X2.
4 L
Switch live (230v) from external time clock DHW demand
3 Remove existing link 4-3 to use this function

m
Exist
links 2
Switch live (230v) from external time clock HTG demand
1 Remove existing link 4-1 to use this function For this option to function correctly a link or room control must
be fitted between connectors 7 and 8 of X9 terminal strip
LT.AL.W7H.000.027 (remove existing link before use).
For continuous DHW on, when using a combi boiler, the link
across connectors 3 and 4 MUST not be removed
If the 230 V supply for the external time clock is not taken from
the boiler – terminal block X2 connections 4 & 5, it must be
taken from the same phase as the boiler 230cv supply and
correct polarities observed.

22
2.7.3 Connecting a 230 V time clock in combination with
a modulating room control
With an externally mounted simple 230 V switching time clock
connected to connectors on X2 terminal strip and a Celcia 15
connected to connectors 7 and 8 of X9 terminal strip (remove
existing link between connectors 7 and 8 before use), the
Remeha Avanta Plus will provide room compensated heating
and time control over CH and DHW (System boiler).

o
An OpenTherm® room modulating control (Celcia 15) used
in conjunction with a simple external 230 V time clock will
provide easy to set up and operate - timed room
compensation heating

2.7.4 Modulating control – room or outside compensation

The Remeha Avanta Plus has an OpenTherm® interface. This


enables our modulating range of OpenTherm® room controls
(e.g. the Remeha Celcia 15 or 20) to be connected without
Terminal
Block X9 any further modifications.
1 • Mount the control in a reference room (usually the living
2
room).
3
• Connect the two-wire interface cables to connectors 7 and 8
X9 of the X9 terminal strip (remove existing link between
4
connectors 7 and 8 before use).
5
Exist • When using the Celcia 20 it is possible to add the outside
links 6
sensor to provide weather compensation with room
7 Modulating - using Open Therm control adjustment. Connect the outside sensor to connectors 1 and
eg: Honeywell Chronotherm or Celcia 20
8 On / Off - using simple volt free switching control 2 of the X9 terminal strip.

LT.AL.W7H.000.028

23
Remeha Avanta Plus

If the DHW water temperature on the OpenTherm® control can


be adjusted, then the Remeha Avanta Plus will supply water at
the temperature determined at the OpenTherm® with the maxi-
mum being set in the boiler.
OpenTherm® is an industry standard modulating control avail-
able from several control manufacturers.

z
The Remeha Avanta Plus can therefore be controlled directly
by any other controls with this OpenTherm® logo

Terminal
2.7.5 Connecting an outside temperature sensor
Block X9

1 Outside sensor (red band) for direct boiler weather compensation An outside temperature sensor can be connected to connec-
or when used in conjuction with a compatable Open Therm
2 control eg: Chronotherm or Celcia 20 tors 1 and 2 of the X9 terminal strip.
3
The boiler will regulate the output using the set point of the
internal heat curve.
4
This can be set as follows:
Exist 5
links
- Outside temperature minimum set point = -15°C (adjustable
6
with parameter p29 to between 0 and -30°C)
7
- Outside temperature maximum set point = 20°C (adjustable
8 with parameter p28 to between 0 and 40°C)
- Flow temperature set point at maximum outside tempera-
ture = 20°C (adjustable with parameter p27 to between
0 and 60°C)
X9 - Flow temperature set point at minimum outside temperature
= 20°C (adjustable with parameter p1 to between
LT.AL.W7H.000.029 20 and 85°C)

o
An outside sensor used in conjunction with a simple 230 V
75
time clock will provide easy to set up and operate - timed
60
weather compensation heating based on the above graph.
Factory setting

40

20

-15 0 10 20

LT.AL.W7H.000.030

24
2.7.6 Connecting the DHW sensor/thermostat

Terminal
Block X9 • If an external DHW calorifier is being used with the Avanta
1
Plus system boiler a volt-free DHW control sensor or ther-
2
mostat can be connected to connectors 3 and 4 of the X9
terminal strip after removing the existing link. The control will
3
DHW sensor (red band) or volt free thermostat (make on temp fall)
Remove existing link to use this function automatically detect whether a sensor or a thermostat has
4
been connected.
Exist 5
links 6

7 2.7.7 Connecting a frost thermostat


8

The boiler must be installed in a frost-free area to prevent the


condensate drain from freezing. However if the temperature of
the CH water in the boiler drops too low, the integrated boiler
protection device is activated as follows:
- at a water temperature below 7°C: the circulation pump is
switched on;
X9
- at a water temperature below 3°C: the boiler is switched on;
- when the water temperature is above 10°C: the boiler is
LT.AL.W7H.000.031 switched off and the circulation pump runs for another
15 minutes.

o
• A frost thermostat should preferably be installed in rooms
Terminal with a high frost risk.
Block X9
• Connect the frost thermostat in parallel to the room ther-
1 mostat - connectors 7 and 8 of the X9 terminal strip (remo-
2 ve existing link between connectors 7 and 8 before use).
3

4
X9 z
5 If a 230 V switching time clock is connected to terminal strip
Exist
links 6
X2, the frost thermostat wired as indicated (on connectors 7
and 8 of the X9 terminal strip) it will not bring the boiler on if
7 Modulating - using Open Therm control
eg: Honeywell Chronotherm or Celcia 20 the time clock is in the OFF position. In these cases the frost
8 On / Off - using simple volt free switching control
stat must be connected in parallel with the time clock on con-
LT.AL.W7H.000.032 nectors 1 and 4 of the X2 terminal strip (frost stat contacts to
close on temperature fall).

m
• The integrated boiler protection described above will not
provide complete system or fabric protection.
• When a Celcia 20 control has been fitted to connectors 7
and 8 on X9 (see Par. 2.7.4) an outside sensor as detailed
in Par. 2.7.5) must be used to provide system and building
fabric frost protection. I
• If a frost thermostat is connected parallel to the Celcia on
connectors 7 and 8 on X9, when the frost thermostat calls
for heat (contact closed) it will override the Celcia 20 control
and cause an error message (OT ERROR) flashes in the
display and the boiler will operate continuously to achieve
the flow set point.

25
Remeha Avanta Plus

2.7.8 Connecting an external interlock

The Remeha Avanta Plus is supplied with an external interlock


function. A volt free switching device (i.e. external gas pres-
sure switch, safety thermostat for under floor heating) can be
connected to connectors 5 and 6 of the X9 terminal strip after
Terminal removing the existing link. When this circuit is open the boiler
Block X9
will shut down with the display showing (code 9) and will
1 restart when the circuit is closed.
2

3
X9
4

Exist 5 External interlock (volt free)


links Remove existing link to use this function
6

LT.AL.W7H.000.033

2.7.9 Connecting remote alarm and boiler run indication


As standard the boiler is supplied with 3 volt free connectors
on terminal X7. They can be used for an external gas valve,
remote alarm and boiler run indication.
• Common alarm signal connect to connectors 1 and 2 on
terminal X7. Contact closes on lock out. For this purpose set
parameter 24 from 0 to 1.
Terminal
Block X7
• Boiler run signal connect to connectors 1 and 3 on terminal
X7 X7. Contact closes on heat demand. For this purpose set
1
Common Alarm
(Closes on alarm) Boiler Run
parameter 24 from 0 to 2.
2
(Closes on run) • Connect an external gas valve to connectors 1 and 3 on
3
terminal X7. Contact closes when the gas valve is activated.
LT.AL.W7H.000.034 For this purpose set parameter 24 from 0 to 3.

2.7.10 Connecting a PC/PDA

Using the optional Recom interface package a PC or PDA can


be connected to the X10 “telephone connector”. Using the
Recom PDA service software you can load, change and down-
load various boiler settings and readings. See the user instruc-
tions supplied with the software/hardware.

X10

LT.AL.W7H.000.035

26
2.8 Wiring diagram
X9
X10 X8 X0 X6
X13 X7
X6 L N
X5 Power supply
X4 1 2 230V, 50Hz
X3 BL
N
X15 X0 L
BR

X2 GN/YW
X1

GN/YW

X1 X2 X3 X4 X5 X7 X8 X9 X13 X15
4 5 1 3 2 1 2 3 4 5 1 2 3 4 1 2 3 4 1 2 3 1 2 3 1 2 3 4 1 2 3 4 5 6 7 8 4 1 3 7 5 6 8 1 10

Blocking up entry
DHW sensor/thermostat

Compensator / Open Therm


NO.

NC.

BK BL BL BR
BR WH BR BK COMM. WH RD BL BK
GY BK RD GN WH WH BK
WH WH YW
OR
GN
Os S WH
T

1 2 3 1 5 1 5 4 2 1 2 1 2 1 2

X134 X133 X131


X22 X21 X81
GCV BP DV FAN

As Rs

X131A

1 2
1 2 3

X132 T

WIRE COLOURS BOILER COMPONENTS HLT


BK BLACK As Flow sensor 1 2 3
BL BLUE BP Boiler pump
BR BROWN Fs Flow switch
X132A 1 10
GN GREEN CP Circulation pump
GN/YW GREEN/YELLOW DV 3-way valve Fs
GY GRAY GCV Gas combination valve
RD RED HLT High limit thermostat
WH WHITE Os Outdoor sensor
YW YELLOW Rs Return sensor
---- Will not be supplied or wired.

LT.AL.W7H.000.234

* Remove existing link between connectors 7 and 8 before use

27
Remeha Avanta Plus

2.9 Commissioning

2.9.1 Control Panel


The control panel of the Remeha Avanta Plus has 4 function
keys and a LED display. The function keys are used to read
or change the settings and temperatures.

1 = display
2 = [reset] key
1 3 = [-] key
4 = [+] key
5 = [enter] key

The display has two positions and displays information on the


current operating status of the boiler and any errors.
Numbers, dots and/or letters can appear in the display. The
2 3 4 5 symbols above the function keys indicate what the function
LT.AL.W7H.000.036 of that particular key then is.

If no key is pressed for longer than three minutes with the


“boiler in stand-by mode”, only one dot is lit. With the “boiler
operating”, two dots are displayed.
• Press any key and the current boiler status and operation
code will appear in the display.
• In the event of a fault, the fault code is displayed instead of
the dots.

2.9.2 Additional guidelines for commissioning


• When commissioning, use the Boiler Log Book.
• Work through all the stages of this section, complete the
commissioning details in the supplied Boiler Log Book and
send a copy of the completed documents to Broag to regis-
ter the boiler.
• The boiler is supplied as standard for use with Natural Gas
and tested at an operating pressure of 20 mbar.

m
The boiler must not be put into operation with a different type
of gas without reference to Broag.

2.9.3 Putting the boiler into operation


This section details the procedure for putting the boiler into
operation. There are 7 stages to the procedure:
1. Isolating the power supply and opening the front cover;
2. Checking the connections and making the boiler operational;
3. Switching the boiler on and setting the controls;
4. Checking/setting the gas/air ratio at full load;
5. Checking/setting the gas/air ratio at low load;
6. Making the boiler ready for use;
7. Instructing the user.

28
1. Isolating the power supply and opening the front cover

• Switch off the boiler at the fused spur and remove the fuse;
230 V • Remove the front panel (release the two screws at the bot-
tom of the front panel, pull the bottom of the panel; forward
and lift off the two pins on the top of the main casing).

LT.AL.W7H.000.037

2. Checking the connections and making the boiler opera-


tional

z
Open the valves on all the radiators connected to the central
1 heating system before filling the system with water.
2
3

• Open the valves on all the radiators connected to the central


heating system;
• Fill the system with water to the design operating pressure
(normal for a one/two storey house 1.2 bar, minimum pres-
sure 1 bar, maximum pressure 2.5 bar);
• Whilst filling, air from the system will escape through the
automatic air vents and the pump.

1,2 bar

m
• When the vent caps start leaking water, close them with
the vent caps supplied attached to gas combination block
and replace the leaking vent cap(s) as soon as possible.
Check • Avoid water getting into the boiler.
LT.AL.W7H.000.038 • Check the condensate siphon. This should be filled to the
mark with clean water if necessary.

29
Remeha Avanta Plus

• Check the integral boiler pump – remove chrome centre


screw to vent pump and spin the shaft to check that the
impellor can move freely;
• Check that all boiler connections are watertight;

• Open the boiler gas valve and check the static pressure to
the boiler at the measurement point (C) on the gas block.

C
m
The boiler has been factory tested for natural gas at 20 mbar.
The minimum gas inlet pressure is 17 mbar for natural gas.

• Check that the gas supply to the boiler is gas tight (in com-
pliance with the current regulations, see Chapter 7 the maxi-
Check
mum test pressure at the gas pipe inlet, with the boiler gas
valve open, is 60 mbar.
LT.AL.W7H.000.039 • Vent the gas pipe by unscrewing the measurement point (C)
on the gas block (tighten it again as soon as the pipe is fully
vented).
• Check that the gas connections in the boiler are sealed.
• Check that all electrical connections, including the earth
connection, have been made correctly.
• Check the electrical connections to the thermostat and other
external controls.
• Check that the flue-gas and air-supply connections are
sealed.

LT.AL.W7H.000.040

3. Switching the boiler on and setting the controls

• Replace the fuse in the spur and switch on the 230 V power
supply.
• Set the controls to heat demand.
• The boiler will begin an automatic venting-programme
(which lasts approx. 3 minutes) and will do this every time
the power supply is isolated.
• The boiler now starts to run. The operational status is shown
in the display. The normal operating status finally shows 0
in the display.
230 V

LT.AL.W7H.000.041

30
4. Checking/setting the gas/air ratio at full load

The Avanta Plus boilers are suitable for both natural gas and
propane firing. For the Avanta Plus 39c an optional propane-
set is needed.
R The boilers are supplied as standard set for natural gas
(H), therefore the following procedure must be carried out
BEFORE the boilers are fired and commissioned for the first
time on propane:
- adjust the fan speed (for procedure; see Par. 2.9.8, for val-
A ues; see table 06 and table 08) and;
- adjust the gas/air ratio (for values; see table 06 and table 08).

A
Setting values O2/CO2 for natural gas H / L
Fan speed (rpm) O2 CO2
Boiler type Full load h3 *) % %
5.2 8.8
LT.AL.W7H.000.042 24s approx. 4300
± 0.1 ± 0.1
5.2 8.8
28c approx. 5500
± 0.1 ± 0.1
5.2 8.8
35c approx. 6300
± 0.1 ± 0.1
5.2 8.8
39c approx. 6700
± 0.1 ± 0.1
table 05 Setting values full load CO2 and O2 (front panel not
fitted)

Setting values O2/CO2 for LPG (propane)


Fan speed (rpm) O2 CO2
Boiler type Full load h3 *) % %
5.1 10.5
24s approx. 4100
± 0.1 ± 0.1
5.1 10.5
28c approx. 5200
± 0.1 ± 0.1
5.1 10.5
35c approx. 5800
± 0.1 ± 0.1
5.1 10.5
39c approx. 6500
± 0.1 ± 0.1
table 06 Setting values full load CO2 and O2 (front panel not
fitted)

*) On forced full load, the 2nd digit indicates the operating code

• Unscrew the flue gas sampling cap and connect the flue gas
analyser.
• Set boiler to full load;
• Press the [enter]- key, keep it pressed and also press the [+]-
key until h3 appears in the display; full load has been set.
• Once the unit has reached the full-load fan speed, measure
the O2/CO2-percentage and compare this to the values in
table 05.
• If the values are not in accordance with the table then cor-
rect the gas /air ratio controls using the adjusting screw A on
the gas block.
• If the value is too low turn the screw A anti clockwise; this
increases the gas rate – if the value is too high turn the
screw clockwise which decreases the gas rate
• Check the flame through the sight glass which should be
stable with a regular blue distribution
31
Remeha Avanta Plus

z
Ensure that the analysing probe has a gas tight seal in the
sampling point with the probe end in the centre of the flue
duct.

5. Checking/setting the gas/air ratio at part load

Setting values O2/CO2 for natural gas H / L


Fan speed (rpm) O2 CO2
Boiler type Part load l3 *) % %
5.2 8.8
R 24s approx. 1300
± 0,1 ± 0,1
5.2 8.8
28c approx. 1300
± 0,1 ± 0,1
5.2 8.8
35c approx. 1300
± 0,1 ± 0,1
B 5.2 8.8
39c approx. 1300
± 0,1 ± 0,1
B table 07 Setting values part load CO2 and O2 (front panel not
fitted)

Setting values O2/CO2 for LPG (propane)


LT.AL.W7H.000.043 Fan speed (rpm) O2 CO2
Boiler type Part load l3 *) % %
5.1 10.5
24s approx. 2000
± 0.1 ± 0.1
5.1 10.5
28c approx. 2000
± 0.1 ± 0.1
5.1 10.5
35c approx. 2000
± 0.1 ± 0.1
5.1 10.5
39c approx. 2000
± 0.1 ± 0.1
table 08 Setting values part load CO2 and O2 (front panel not
fitted)

*) On forced part load, the 2nd digit indicates the operating code.

• Set boiler to part load:


• Press the [enter]- key until l3 appears in the display, part
load has been set.
• Once the unit has reached the part load fan speed, measure the
O2/CO2-percentage and compare this to the value in table 07.
• If the values are not in accordance with the table then correct
the gas /air ratio controls using the adjusting screw B on the gas
block.
• If the value is too low turn the screw B clockwise; this increases
the gas rate – if the value is too high turn the screw B anti clock-
wise which decreases the gas rate
Check the flame through the sight glass which should be stable
with a regular orange distribution. Once the unit has been set to
part load, the ‘test at full load’ should be repeated.

z
Ensure that the analysing probe has a gas tight seal in the
sampling point with the probe end in the centre of the flue duct.

• Repeat the ‘test at full load’ and ‘test at part load’ as often as
necessary until the correct values are achieved without fur-
ther adjustments
32
6. Preparing the boiler for use
• Remove the analysing probe and replace the cap on the flue
gas sampling point.
• Refit the front panel and secure with the two screws again.
1 • Press [reset]-key for the boiler to return to the normal oper-
ating mode.

z
Following a manual override the boiler will return to normal
operating mode if no keys are pressed for 15 minutes.

• Run the boiler on heating until the system reaches approx


70°C
R
• Switch the boiler off (using the controls i.e. thermostat or
time clock)
• Once the pump has turned off vent the system once again.
• Check the water pressure and add more water through the
2 mains fill loop if necessary.
• Complete the type plate in the boiler by adding the gas
type.
LT.AL.W7H.000.044 • Fill in commissioning sheet and log book data.

The boiler is now ready for operation.

o
The Remeha Avanta Plus is delivered pre-tested and operat-
ing parameters set up with standard factory settings to suit the
most common systems. These setting can be adjusted to suit
specific site conditions but must not be changed without
reference to Broag or one of our approved contractors.

7. Instructing the user


• It is the responsibility of the installer as part of the com-
missioning procedure to instruct the user in the day to day
operation of the boiler and controls fitted to the system and
to hand over the completed Boiler Log Book and appropri-
ate documentation.

2.9.4 Normal start-up procedure


• Switch on the boiler at the fused spur unit and ensure that
the time control is in the on position and any other controls
(i.e. room thermostat etc) calling for heat
• The boiler will begin its start sequence.
The following sequence will appear in the display:
- A display test will briefly appear showing all segments of
the display.
f[ xx software version;
p[ xx parameter version;
- A venting cycle of 3 minutes now follows, the version
numbers will be displayed alternately;
- Next, the following will appear in the display;
[1 ; pre-purge stage
[2 ; Ignition stage
[3 ; operating in CH mode or
[4 ; operating in DHW mode
[7 ; pump run on after CH or DHW is satisfied
[0 ; stand-by mode
LT.AL.W7H.000.045

33
Remeha Avanta Plus

2.9.5 Error during the start-up procedure


• If the display is blank (should show dots or letters), check:
- 230 V main supply available to switch spur
- switch spur fuse
- cable and connections between the switched spur and the
boiler control unit
- fuse on the boiler control unit (F2 = 2AT, 230V)

• An error code appearing in the display can be recognised as


follows:
é 10, (the display alternately shows an é and a number
e.g. 10). The meaning of this error codes can be found in
the error table, see Chapter 4.
• Resolve the error first if possible.
• Press the [reset]- key and hold for at least 1 second to
restart the boiler.

z
After any error é1, é2, é7, é10 or é13 ; the 3
minute venting cycle will run first before starting
the boiler.

• Checking DHW function;


- Turn on a hot water tap, the display shows;
[1 ; pre-purge stage
[2 ; Ignition stage
[4 ; operating in DHW mode
- Close the hot water tap, after a short time the display
shows;
[1 ; pre-purge stage
[7 ; pump run on after CH or DHW is satisfied
[0 ; stand-by mode

• Checking CH function;
- Ensure the time control is in the CH on position
- Set the room thermostat on a high demanding tempera-
ture and, the display shows
[1 ; pre-purge stage
[2 ; Ignition stage
[3 ; operating in CH mode.
- Set the room thermostat back to a lower temperature (no
more heat demand), the display shows;
[4 ; operating in DHW mode (boost to DHW plate on
minimum load)
[5 ; waiting-time; 3 to 10 minutes (only when flow
temperature has already been reached and heating demand
is still existing)
[1 ; pre-purge stage
[7 ; pump run on after CH or DHW is satisfied
[0 ; stand-by mode

34
o
• If the boiler is set to the economy setting (see par. 2.9.8), it
will not supply a boost to DHW after CH is satisfied. The
display then shows; [1 ; pre-purge stage [6 ; pump run
on after CH [0 ; stand-by mode.
• If a two channel time clock is fitted and connected to a
combi boiler and the time control for DHW is in the “OFF”
position, the DHW production will be disabled unless the link
between connectors 2 and 3 on the X2 terminal is fitted
(normally factory fitted).

2.9.6 Read out settings


R The following settings can be read out in the ‘user menu’:
- t1 = flow temperature [°C];
- t2 = return temperature [°C];
- t3 = boiler temperature [°C];
- t4 = outside temperature [°C];
- fl = ionisation current [uA];
- ñf = fan speed [rpm] ;

• Press the [+] key, until t1 appears and, for example, 68


(68°C), the current flow temperature;
• Press the [+] key again until t2 appears and, for example,
45 (45°C), the current return temperature;
• Press the [+] key again until t3 appears and, for example,
50 (50°C), the current boiler temperature;
• Press the [+] key again until t4 appears and, for example,
18 (18°C), the current outside temperature;
• Press [+] key again until fl appears and e.g. ^0 (6uA),
the present ionisation current;
LT.AL.W7H.000.046 • Press [+] key again until ñf appears and e.g. 30 (3000
rpm), the present fan speed;
• Press [+] key again and the read-out cycle will start again
with t1, etc.;
• Press [reset] key to return to the display with the current
operating status.

35
Remeha Avanta Plus

2.9.7 Adjust the boiler according to the system


The operating parameters of the Remeha Avanta Plus have
been factory set to suit most systems. However it is possible
to adjust some of the parameters to enable the Remeha Avan-
ta Plus to operate more efficiently to match specific system
designs and site conditions. These parameters are split into
two specific sections
1. User level – Parameters p 1 to p 6; can be changed by
the user to suit CH and DHW comfort conditions
2. Service level – p17 to dF ; must only be changed by
Broag approved Engineer after consultation with the
system designer.

o
How to change the parameters at user level can be read in the
“User manual” provided and therefore will not be detailed in
this Installation and Service manual.

2.9.8 Changing the parameters at service level (with


access code)
To avoid non authorised adjustments, some parameter settings
can only be changed once the special access code 12 has
been entered. This code may only be used by qualified install-
ers. The following settings can be changed at user and service
level:

Setting range and notes where Factory settings


Codes in display Description
applicable 24s 28C 35C 39C
p 1 Tset flow 20 - 85°C 75°C
p 2 Tset DHW 40 - 65°C 55°C
0 = CHoff and DHWoff
Can also be changed by users

1 = CHon and DHWon


p 3 Boiler regulation 2 = CHon and DHWoff 2 1 1 1
3 = CHoff and DHWon
0 =
comfort setting
p 4 Eco or comfort setting 1 =
eco mode* 0
2 =
regulated by controller
0 =
no anticipated current
for thermostat on/off
p 5 Anticipated current
1 = anticipated current
2
for thermostat on/off
0 = display stays off
1 = display stays on
p 6 Display off automatically
2 = displaylight switches off auto-
2
matically after 3 minutes

36
Maximum fan speed CH 10 – 70
37 1 ) 37 1 ) 41 1 ) 50 1 )
(natural gas) X 100 rpm
p 17
Maximum fan speed CH 10 – 70
35 1 ) 37 1 ) 41 1 ) 48 1 )
(propane) X 100 rpm
Maximum fan speed DHW
Do not change *** 43 1 ) 55 1 ) 63 1 ) 67 1 )
(natural gas)
p 18
Maximum fan speed DHW Adjustments for
41 1 ) 52 1 ) 60 1 ) 65 1 )
(propane) propane firing
Minimum fan speed
(CH and DHW) Do not change *** 13
(natural gas)
p 19
Minimum fan speed
Adjustments for
(CH and DHW) 20
propane firing
(propane)

p 20 Starting fan speed Do not change 25 25 28 30

0 = low
p 21 Pump setting CH
1 = high
0

p 22 Pump running time after CH 1 - 99 minutes 2


Connection with Heat 0 = no connection with HRU
p 23 Recovery Unit (HRU) 1 = connection with HRU
0
To be changed by installer only

0 = off (connectors 1 and 2 closed)


1 = alarm signal
(connectors 1 and 2 closed)
State remote alarm
p 24 (X7 terminal)
2 = run indication 0
(connectors 1 and 3 closed)
3 = ext. gas valve
(connectors 1 and 3 closed)
0 = off
1 = on
2 = automatic (after putting boiler
p 25 Legionella protection into operation, it will run for
1 0 0 0
DHW operation 65°C once a
week)
p 26 DHW cut-in temperature 2 - 15°C 5
Heat curve set point
p 27 flow temperature
0 - 60 °C 20
Heat curve set point
p 28 outside temperature (min)
0 - 30 °C 20

Heat curve set point


p 29 outside temperature (max)
-40 - 0 °C - 15**

0 = combi
p 30 Boiler type
1 = system
1 0 0 0

P 31 DHW control stop 0 - 20 °C 15


On identification plate d f setting
X is shown. Change parameter X
into X will restore the factory set-
p df tings, see par. 2.9.10
(p d U Restore factory settings
is shown later) On identification plate d U setting
Y is shown. Change parameter Y
into Y will restore the factory set-
tings, see par. 2.9.10
table 09 Settings at service level
1
) Do not exceed this value
* the system boiler in combination with an external calorifier
will not warm up the calorifier in the Eco-mode.
** minus character is not shown in display.
*** only change for propane firing.

37
Remeha Avanta Plus

R
m
Changing the factory settings could result in the boiler not
working properly.

The parameters can be changed from the stand-by status as


follows:
• Press the [enter]-key and briefly the [reset]- key until codes
c and 0 appear alternately in the display.
• Press the [+]-key until access code 12 is displayed.
• Press the [enter]-key until p1 appears (codes p [ and
[ 1 are displayed alternately);
• This parameter can now be changed as follows;
• Press the [enter]-key; the set value for the maximum flow
temperature now appears e.g.; 75 (75°C).
• Press the [+] or [-]-key to change this value, for example to
65 (65°C).
• Press [enter]-key to confirm the value; codes p [ and [
1 are displayed alternately.
• Press the [+]-key to change the next parameter, etc.
• Press [reset]-key to return to the operating mode.

LT.AL.W7H.000.047

o
The boiler will automatically return to the normal operating
mode if no keys are pressed for 10 minutes.

2.9.9 Changing the maximum output (Hi) for CH


operation
The maximum output for CH operation can be changed with
R
parameter p 17 (maximum fan speed) and is set standard
to a speed of 3700, 4100 or 5000 rpm. See the speed-input
ratio figures.

This parameter can be changed from the stand-by status as


follows:
• Press the [enter]-key and briefly the [reset]- key until codes
c and 0 appear alternately in the display.
• Press the [+]-key until access code 12 is displayed.
• Press the [enter]-key until p1 appears (codes p [ and
[ 1 are displayed alternately);
• Press the [+]-key to go to parameter 17.
• Press the [enter]-key until p17 appears (codes p [
and 17 are displayed alternately);
• Press the [+] or [-]-key to change this value for Avanta Plus
28c, for example to 46 (4600 rpm corresponds with
22 kW).
• Press [enter]-key to confirm the value.
• Press [reset]-key to return to the operating mode.

LT.AL.W7H.000.048

38
Avanta Plus 24s
Speed-input ratio
30.0

25.0

20.0
Hi input [kW]

15.0

10.0

5.0

0
1000 1500 2000 2500 3000 3500 4000 4500
Fan speed [rpm]
LT.AL.W7H.000.049

Avanta Plus 28c


Speed-input ratio
35.0

30.0

25.0
Hi input [kW]

20.0

15.0

10.0

5.0

0
1000 2000 3000 4000 5000 6000
Fan speed [rpm]

LT.AL.W7H.000.050

Avanta Plus 35c


Speed-input ratio
45

40
35

30
Hi input [kW]

25

20

15
10

0
1000 2000 3000 4000 5000 6000 7000
Fan speed [rpm]

SPEED RATIO 35C

Avanta Plus 39c


Speed-input ratio
45

40
35

30
Hi input [kW]

25

20

15
10

0
1000 2000 3000 4000 5000 6000 7000
Fan speed [rpm]

LT.AL.W7H.000.051

39
Remeha Avanta Plus

2.9.10 Restore factory settings


The factory settings can be restored in the service level as fol-
lows:

R 1. After parameter p31 has shown, press the [+]-key; d


f and xx appear alternately;
2. Press l-key; xx appears;
3. Read boiler identification plate for value of d f ; press [+]
or [-] key to reach this value;
4. Press l-key to confirm; d U and yy appear alter-
nately;
5. Read boiler identification plate for value of d U ; press [+]
or [-] key to reach this value;
6. Press l-key to confirm; boiler restarts with original factory
settings.

2.10 Putting the boiler out of operation


The boiler must be switched off and allowed to cool down
before any maintenance or repairs are carried out. If the cen-
tral heating system is not going to be used for a long time
(during the holidays, for instance, or frost-free periods) it is
advisable to put the boiler out of operation.

LT.AL.W7H.000.052 2.10.1 Boiler with frost protection, during longer periods


of non-use
• Set the room thermostat to a low temperature, e.g. 10°C,
• Switch setting p4 to 1 (Eco mode), this will switch off
the heat retention function.
Now the boiler will only start working to protect itself against
freezing. With external frost protection, the boiler can also
prevent the central heating system from freezing.

2.10.2 Boiler without frost protection, during longer


periods of non-use
• Turn time clock off and allow system to cool down then iso-
late mains power supply at the fused spur unit.
• Isolate the gas supply at the boiler valve.

m
Drain the boiler and central heating system if you will not be
using the home for a long period and there is a chance of
night frost.

40
3 INSPECTION AND MAINTENANCE

The Remeha Avanta Plus is practically maintenance free but


should be inspected annually.

z
If during the annual inspection the flue gas analysis indicates
that the values are outside the figures given in table 10,
maintenance work should be carried out as described in
par.3.2. Also carry out maintenance if the ionisation read-out
value is lower than 3 or higher than 9μA, or when the flame
core is not satisfying.

Only Remeha spare parts/materials should be used.


All service and maintenance must be carried out by a quali-
fied Engineer with the relevant training and certification (i.e.
CORGI - ACS - IEE registrations etc).

3.1 Inspection

The annual inspection of the Remeha Avanta Plus can be lim-


ited to the following checks:
- check the water pressure, see par. 3.1.1;
- check the flue pipes and air supply pipes for leaks, see par.
3.1.2.;
- check and clean (if necessary) the condensate siphon, see
par.3.1.3.;
- check the ignition electrode and ionisation, see par. 3.1.3;
- check the combustion and flame colour, see par. 3.1.5;
- fill in the Boiler Log Book.

> 1 bar

LT.AL.W7H.000.053

41
Remeha Avanta Plus

3.1.1 Checking the water pressure


Min. 1 bar The water pressure should be checked against the commis-
sioning entry in the Boiler Log Book (min 1 bar)
• If necessary, re-fill system to design pressure and re-set red
pointer to match fill pressure 2 bar.

z
Check system for leaks if the system needs re-filling more
than 3 times per year.

2 bar

LT.AL.W7H.000.054

3.1.2 Checking the flue pipes and air supply pipes for
leaks
• Check that the flue and air-supply connections and
pipes are sealed and the terminal exit is clear.

LT.AL.W7H.000.055

42
3.1.3 Checking the condensate siphon
• Check the condensate siphon. Remove any dirt resi-
dues and refill with clean water to the mark.

LT.AL.W7H.000.0233

3.1.4 Checking the ignition electrode

• Check the ionisation /ignition electrode for:


- deposits (remove any white deposits with abrasive cloth);
- the adjustment of the ignition electrode (between 3 and 4
mm);
- the quality of the gasket and condition of the porcelain
(this should not be cracked);
3 à 4 mm
• Check the ionisation current after 1 minute on the display
code fl, see par. 2.9.6.
If the read-out value is lower than 3 or higher than 9μA,
check cable and connections are sound if OK replace the
ignition electrode.
>1 min
z
The ignition cap is fixed on the ignition electrode and therefore
cannot be removed.
LT.AL.W7H.000.056

3.1.5 Checking the combustion


• Measure the O2/CO2 percentage and the flue gas tempera-
ture at the flue gas sample point.
Do this as follows:

- heat the water temperature in the boiler to approx. 70°C;


- unscrew the top of the flue gas point of measurement;
- measure the O2/CO2 percentage and compare this to the
check values in table 10.

z
Ensure that the analysing probe has a gas tight seal in the
sampling point with the probe end in the centre of the flue
duct.

LT.AL.W7H.000.057

43
Remeha Avanta Plus

Checking values O2/CO2 for natural gas H / L


Fan speed (rpm) O2 CO2
Boilertype Full load h3 Part load L3 % %
5.2 8.8
24s ca. 4300 ca. 1300
± 0.2 ± 0.3
5.2 8.8
28c ca. 5500 ca. 1300
± 0.2 ± 0.3
5.2 8.8
35c ca. 6300 ca. 1300
± 0.2 ± 0.3
5.2 8.8
39c ca. 6700 ca. 1300
± 0.2 ± 0.3
table 10 Checking values O2/CO2 (front panel not fitted)

Checking values O2/CO2 for LPG (propane)


Fan speed (rpm) O2 CO2
Boilertype Full load h3 Part load L3 % %
5.1 10.5
24s ca. 4100 ca. 2000
± 0.2 ± 0.3
5.1 10.5
28c ca. 5200 ca. 2000
± 0.2 ± 0.3
5.1 10.5
35c ca. 5800 ca. 2000
± 0.2 ± 0.3
5.1 10.5
39c ca. 6500 ca. 2000
± 0.2 ± 0.3
table 11 Checking values O2/CO2 (front panel not fitted

z
The O2/CO2 - values in table 10 are checking values. For
setting values see table 05 and table 07.

If the flue gas analysis readings are within the values in table
10 the boiler combustion is OK. However if the readings are
outside the given values, then adjust the gas air ratio control to
the given values, see table 05 and table 07 in par.2.9.3.
If the adjustments cannot achieve the mentioned values, the
boiler will require a full service please refer to the maintenance
instructions in par. 3.2.
- check the flame via the inspection glass; in full load the
flame should be stable with an even blue colour and in part
load should be stable with an even orange colour.

3.2 Maintenance
To conduct maintenance:

z
Ensure that a service gasket set and new ignition/ionisation
electrode is available before carrying out this procedure.

{
• Isolate power supply at the fused spur before carrying out
any work on the boiler.

44
1. Open the boiler

• Isolate the 230 V supply at the switched spur and remove


230 V the fuse
• Isolate the gas supply at the boiler gas valve
• Remove the front panel (release the two screws at the bot-
tom of the front panel, pull the bottom of the panel forward
and lift off the two pins on the top of the main casing).

Gas
1

LT.AL.W7H.000.058

2. Maintenance of the ignition/ionisation electrode

• Disconnect the earth wire from the electrode mounting


plate.
• Release the two screws on the electrode and remove the
assembly.
• Inspect, clean re-gap or replace the electrode, see par
3.1.3.

2x

LT.AL.W7H.000.059

45
Remeha Avanta Plus

3. Dismantling the front plate of the heat exchanger

• Release the ignition transformer mounting plate and remove


it completely.
4x • Disconnect the electrical connection on the gas block.
• Release the union nut from the gas pipe on the outlet to the
4
gas block.
• Release the four nuts on the heat exchanger front plate
• Carefully pull the front plate assembly c/w fan, gas block,
venturi pipe and burner unit away from the heat exchanger
by approx. 10 cm.
• Disconnect the electrical plug on the back of the fan, so it
becomes accessible.
• Remove the front plate assembly completely.

1
3
2

LT.AL.W7H.000.060

4. Maintenance to the burner

• Carefully clean the burner with pressured air (do not keep
the nozzle to close to the surface).
• Visual inspection of the burner for any damages or cracks
on the surface. If you see any damages, then replace the
burner.

LT.AL.W7H.000.061

46
5. Maintenance to the heat exchanger (CH)

• Check the seal between the front plate and the heat
exchanger and the insulation section. Replace sealing.
• Handle the fragile front-plate insulation and the back-plate
insulation of the heat exchanger with great care and do not
let them get wet.
• Visual inspection of the heat exchanger for scale or dirt. If
you see obvious deposits, than clean the heat exchanger
carefully. Carefully remove any loose dirt with a vacuum
cleaner.
• Then brush the coils of the heat exchanger (if required a
cleaning brush is available as an accessory) and remove
the loosened particles with a vacuum cleaner.

6. Cleaning plate heat exchanger (DHW) and non return


valve with filter
Scale deposits on the plate heat exchanger cannot be totally
excluded, depending on such variables as tap water quality
LT.AL.W7H.000.062 and operation mode.
We recommend annual inspections under standard circum-
stances. Please note that following factors may influence the
frequency of inspection:
• Water hardness
• Chemical composition of scale deposit
• Boiler operation hours
• DHW usage pattern
• DHW set temperature

47
Remeha Avanta Plus

If a cleaning operation becomes necessary, please proceed as


follows:
• Turn off the mains cold water supply and drain off the resid-
ual DHW;
• Release two socket head screws and remove plate heat
exchanger;
• Clean plate heat exchanger with scale solvent (e.g. citric
acid, pH 3); a special cleaning tool (optional accessory) can
be used;
• Thoroughly cleaning afterwards with clean water;
• Remove non return valve with filter from on the right hand
side of the hydro block and also clean with the scale sol-
vent; afterwards thoroughly cleaning with clean water.

1
2 230 V

LT. AL.W7H.000.231 + LT.AL.W7H..000.232

48
7. Re-Assembling the boiler and checking the combustion

• Re-assemble all the components in reverse order.

4x z
2 • Check that the packing between the front plate and the heat
exchanger has been fitted correctly.

• Fill the system with water.


• Switch the boiler back on.
• Check the CO2/O2-percentage, 2.9.3, point 4.
• Check the ionisation current by reading the display, see
par.3.1.3
• Check the connections on the gas block on gas-leaking.

4 z
3 5 Fill in the Boiler Log Book after conducting any maintenance.

230 V

Check

LT.AL.W7H.000.063

49
Remeha Avanta Plus

4 ERRORS
4.1 General
The Remeha Avanta Plus has an advanced control unit. The
heart of this control unit is a microprocessor, the abc®-con-
trol which both controls and protects the boiler. If an error is
detected anywhere in the boiler, it will lock-out and an error
code will appear in the display.

4.2 Error codes


The Remeha Avanta Plus displays the error codes as follows:
é 2 (the display alternately shows an é and a number e.g.
2) The meaning of the various error codes can be found in
the error table, see table 11.

How to deal with errors:


• Make a note of the displayed error code.

o
The error code is important for the correct and swift detection
of the nature of the error and for possible support from our
technical help line 0118 978 3434.

• Press the ‘reset’ key for 3 seconds. If the error code contin-
ues to appear, look for the cause in the error table below and
resolve it.
Error Description Possible cause Check / solution
code
Short circuit in the flow, Check the wiring and the connections of the sensors visually: are the
return or boiler temperature plugs all correctly in position? With a multimeter: measure the resist-
sensor. ance in the wiring and connection.
Flow or return
é0 Check that the sensors are working; take the sensors out * and
sensor fault. Defective or not (properly)
measure the resistance with a multimeter at room temperature (20
connected flow, return or
- 25°C); the sensor is working properly if the resistance is between
boiler temperature sensor.
12 and 15 kΩ.
Insufficient water. Check the minimum water pressure, read off the gauge.
Check that the pump is working; turn the spindle with a screwdriver,
Flow tempera- No through flow. if that works but the pump still does not respond, check the wiring; if
ture is higher that is in order the pump is faulty.
é1 than the set Too much air in the system. Vent the system.
maximum tem- Check that the sensors are working; take the sensors out * and
perature Deviation in the flow or measure the resistance with a multimeter at room temperature (20
return temperature sensor. - 25°C); the sensor is working properly if the resistance is between
12 and 15 kΩ.
Insufficient water. Check the minimum water pressure, read off the gauge.
Check that the pump is working; turn the spindle with a screwdriver,
No through flow. if that works but the pump still does not respond, check the wiring;
Return tempera- that is in order the pump is faulty.
ture is higher Too much air in the system. Vent the system.
é2
than the flow Sensors not wired correctly Check the wiring between sensors and control unit.
temperature Check that the sensors are working; take the sensors out * and
Deviation in the flow or measure the resistance with a multimeter at room temperature (20
return temperature sensor. - 25°C); the sensor is working properly if the resistance is between
12 and 15 kΩ.
Mains supply not correctly
Control unit or Check that the power supply from the switch spur is properly
é3 earthed.
earth fault earthed, if that is the case the control unit is faulty.
Control unit faulty.

50
Error Description Possible cause Check / solution
code
Check:
• the connection between the ignition wire and the ignition trafo;
No ignition spark.
• the ignition wire and electrode for ‘dielectric breakdown’;
• the inter-electrode distance, this should be 3-4 mm; that the
ignition electrode is properly earthed.
A spark but no flame. Check that:
• the gas tap is open;
• the gas pre-pressure is sufficient;
• the gas pipe is de-aerated;
• the gas valve is energised during ignition and opens;
More than 5 start • the electrode is correctly fitted and clean;
attempts without • the CO2 adjustment at low and full load;
é4
any flame forma- • there is no obstruction / fitting fault in the gas pipe;
tion. • there is no obstruction in the air supply or flue (e.g. a blocked
siphon); there is no recirculation of flue gasses
(either inside or outside the boiler).
There is a flame but no, or Check:
insufficient ionisation (lower • the flame, is the heart of the flame visible and the flame stable?
than 3 or higher than 9 μA) • the CO2 adjustment at low and full load;
• that the ignition electrode is correctly earthed;
• visual check of the ignition/ionisation electrode: look for white
oxide film (remove with sandpaper or a screwdriver); look at
the shape (are the pins still the original shape and is the distance
between the two ends of the pins between 3 and 4 mm).
CO2 wrongly adjusted Check:
No ionisation or • CO2 adjustment on the gas block;
ionisation failure • ignition/ionisation pin;
é5 more than 5 • flue/air-supply connections;
times during one • gas flow at full load;
heat demand. • if there is no recirculation of flue gasses (either inside or
outside the boiler).
Unwanted flame
é6 Faulty control unit, replace control unit.
formation
Check the minimum water pressure, read off the gauge and check
Insufficient water.
for leaks.
No water in the
Check that the pump is working; turn the spindle with a screwdriver,
boiler or the
é7 No through flow. if that works but the pump still does not respond, check the wiring;
pump is not
that is in order the pump is faulty.
working
Too much air in the system. Vent the system.
Wrong pump wiring. Check wiring from and to control unit.
Fan is not working Check:
• fan function;
• fan wiring and connection.
é8 Fan fault Fan does not stop Check:
• fan function;
• fan wiring and connection;
• excess chimney draught.
Insufficient water. Check the minimum water pressure, read off the gauge and check
for leaks.
No through flow Check that the pump is working; turn the spindle with a screwdriver,
No through flow
if that works but the pump still does not respond, check the wiring;
é10 during venting
that is in order the pump is faulty.
cycle
Too much air in the system. Vent the system.
Wrong pump wiring. Check wiring from and to control unit.

51
Remeha Avanta Plus

Error Description Possible cause Check / solution


code
Check:
• The sealing of the viewing glass;
Air box tempera- Air leakage from heat
é11 • Whether front plate of heat exchanger is properly tightened
ture to high exchanger to air box
• Front plate sealing;
• Whether ignition electrode is properly fitted
Heat-exchanger Heat exchanger faulty. Check wiring between heat exchanger fuse.
fuse protection
has responded; Insufficient water. Check the minimum water pressure, read off the gauge and check
é13 replace the heat for leaks.
exchanger after No through flow. Check that the pump is working; turn the spindle with a screwdriver,
finding and solv- if that works but the pump still does not respond, check the wiring;
ing the cause. that is in order the pump is faulty.
Replace d f / d U settings, see Par. 2.9.10
é43 Parameter limits Automation settings
If this error code still returns after resetting; please contact Broag.
Replace d f / d U settings, see Par. 2.9.10
é44 Parameter check Automation settings
If this error code still returns after resetting; please contact Broag.
Default param-
é45 Automation settings Replace boiler control unit.
eters
table 12 Error codes
* When sensors have been taken out, be sure to replace
them max. 40 mm underneath heat exchanger.
Temperature/resistance diagram
If you read out a not listed error, please report to Broag.

25000
4.3 Control stop or lock-out
The code 8 , 5 or 9 can appear in the display.
20000 • Code 8 is a control stop and will appear if the measured
flow temperature (t1) is higher than the flow temperature
resistance in Ω

15000 set (Tset flow). The boiler will start working again automati-
cally once the flow temperature falls below the flow tem-
10000
perature set.
• Code 5 is a control stop from 3 till 10 minutes and
appears if the set flow temperature (t1) has already been
5000
reached and the heating demand still exists.
• Code 9 is a lock-out and appears if the maximum tem-
0
perature rise is exceeded or if the dT between the sup-
10 20 30 40 50 60 70 80 90 100
temperature in °C
ply and return temperature ≥ 45°C or a rate of rise in the
SENSOR RESISTANCE flow temperature > 1°C/sec. And also at a boiler-start with
no through flow or insufficient water. The boiler will try to
restart after 10 minutes.

z
Every 10 minutes the boiler will try to restart until the cause
has been removed.

• Code 9 is a lock-out and can appear in the following


situation:
- the lock-out down input (between terminals 5 and 6 on X9)
has been activated (= opened).

z
The lock-out will disappear once the cause has been removed!

52
4.4 Error memory
The Remeha Avanta Plus control unit has an error memory,
in which the last 16 errors are stored. In addition to the error
code (é and a number xx).
The following data is also stored:
• the number of times the error occurred (n and a number
xx)
• the operating status of the boiler (5t and a number xx)
• the flow temperature (t1 and the value xx) return tem-
perature (t2 and the value xx) at the time the error
occurred.
To get access to the error memory, access code must be
entered.

R 4.4.1 Error read outs

• Press the [enter]-key and keep it pressed;


• Press the [reset]-key until codes c and 0 appear alter-
nately in the display;
• Enter the special access code 88 with the [+] or [-]- key;
• Press the [enter]-key; the display shows ér and the
number of the last error alternately, for
example 02.
• Press the [+] or [-]-key to go forwards or backwards in the
list of errors.
• Press the [enter]-key to take a closer look ot the error. The
display shows the error code as follows;
- first error code é with error number e.g. 12
- then status code 5t with status number e.g. 3 (burning
for central heating)
- then number of time that the error has occurred ñ and a
number e.g. 3
- then the flow temperature when the error occurred t1
and temperature e.g. 75
- final the return temperature when the error occurred t2
and temperature e.g. 60
This cycle continues to repeat itself.
• Press the [reset]-key to stop the cycle; the following
appears in the display;
ér and the last viewed errors e.g the numbers 1 and 8.
• Press the [+] or [-]-key to look at the following error data.

4.4.2 Deleting errors


The last message in the list, Er followed by cl will
appear in the display;
• Press the [enter]-key again, and the following will appear in
the display: 0
• Press the [+]-key to set the parameter to 1.
• Press the [enter]-key, to delete the error memory:
LT.AL.W7H.000.064 • Press the [escape]-key twice to exit the error memory.

o
When tracing an error, the cause can often be found more
quickly if the operating status at the time the error occurred
can be retrieved from the error memory.

53
Remeha Avanta Plus

5 SERVICE PARTS

5.1 General
If, following the annual inspection or maintenance any part of
the boiler is found to need replacing, use Remeha spare parts
only or spare parts and materials recommended by Remeha.

If the component to be replaced is covered by the Remeha


guarantee terms (see the Remeha General Terms of Sale
and Delivery) send the component to the Remeha Quality
department. Always enclose a fully completed return form, see
example below. This will enable Remeha to meet its guarantee
obligations more quickly and efficiently.

The enclosed (returned) component model* year/day/serialnr.*


comes from boiler: Avanta Plus 24s 05 094 000 000 087
Installation date of the boiler June 2005

Description (returned) component sort Brand type


Three-way valve Elbi VC 1650/1000
Problem description motor does not respond

Description (returned) component sort Brand type

Problem description

Description (returned) component sort Brand type

Problem description

Your details
Company name Smit
Address Londonstreet 1, London
Telephone
Reference Mr. Johnson
Your order number 530002004
Job number -
Project number 14 (Canal flats)
table 13 Return form example

* These details can be found on the boiler type plate; the type
plate is stuck to the bottom of the boiler.

54
2010 2007

2030 2008
1005

1012
2032
2017

2024 2004

2001
2009

2014
1003
2002 2033

2023
2035
2015
2034
2003
3010 1010
2016 3001
2029 2006 3004
2020
3009
2018 3008
2009 3011
2005 2013 3002
2024 3006 3007
2028 3003
2039 3012
2036 3005
2040 2021
2032 2042 4003
2037 4008
5017 5001
3009 5008
2027 2038 3004 4010
2019
2025 5010 5018
1004 5013 5029
1001 2011
2012 3013
5004 4004 5028
2041 5006
5011 5002
2022
5009
5012
4006 5033
4011 5014 5018 5017
5015 2019
4001
1006 5003
4005 1009 5011
5012

1008
1002
4007
4014
1007
4012
5026 5027
4013 1009 5031 5032
1002
4007
5019 5030 5027
4002 3017 5032
5020
3014
5022
3016
5021 3014 5030
2026 5022
5020
4009 5023 5026
4007 5021 5031
5019
5024
3015 5020
5020
4004 5025
5023

LT.AL.W7H.000.065

55
Remeha Avanta Plus

Break down parts kit


Part No Description Position
S62743 Electrode ignition/ionisation 2004
S62728 Vent auto air bleed device 2010
S62746 Pump for 24s and 28c 2011
S62747 Pump for 35c and 39c 2011
S58733 Sensor temperature (2 pcs.) 2013
S62733 Gauge pressure c/w capilliary 2026
S58684 Fan assembly 24VDC 3001
S58685 Gas combination block 3005
S62734 Control board 4001
S62739 Display print board 4002
S62750 Transformer ignition 4003
S43561 Fuse glass 2 amp slow (10 pcs.) 4011
S59132 Actuator three way valve 5002
S59133 Sensor DHW flow 5006
S62763 Safety pressure relief valve with pipe 5015
S62781 Flowswitch + hall sensor 5033
table 14 Break down parts kit

56
6 EC DECLARATION

EC – DECLARATION OF CONFORMITY

Manufacturer : Remeha B.V.


Address : Kanaal Zuid 110
Town, Country : Postbus 32, NL-7300 AA Apeldoorn

- hereby declares that the appliance(s) : Remeha Avanta Plus

comply / complies with the specifications of the following EEC directives:

EEG Directive: 90/396/EEG applied standards:

(pr)EN 297(1994), 483(1999), 625(1995), 677(1998)

73/23/EEG (pr)EN 50165(1997), 60335-1(1994)

92/42/EEG

89/336/EEG EN 50165(1997), 55014-1(2000), 55014-2(1997)


EN 61000-3-2(2000), 61000-3-3(1995)

97/23/EG (Art.3, sub 3)

Apeldoorn, July 2005

W.F. Tijhuis
Approval Manager

57
Remeha Avanta Plus

7 REGULATIONS
7.1 EC regulations
The boiler meets the requirements of the EC regulations at the
following directives:
- 90/396EEC Gas appliances directive
- 92/42/EEC Efficiency directive
- 73/23/EEC Electrical low voltage directive
- 89/336/EEC EMC directive
- 97/23/EEC Pressure equipment directive (art. 3, sub. 3)

Classification type for evacuation of the combustion products;


according EN 483

7.2 Remeha factory test


Before it leaves the factory, each Remeha Avanta Plus boiler
is optimally adjusted and tested for:
- electrical safety;
- CO2- adjustment;
- hot water function
- water tightness;
- gas tightness;
- automation parameters.

7.3 Additional guidelines


In addition to the regulations and guidelines as mentioned in
par.7.1 the following guidelines in this documentation should
also be observed.

It applies for all regulations and guidelines, mentioned in this


Installation and Service manual, that any additions or new
regulations and guidelines at the time of installation will also
apply.

58
8 TECHNICAL SPECIFICATIONS AND WORKING PRINCIPLE

8.1 Technical data

24s 28c 35c 39c


Appliance type Remeha Avanta Plus
system combi combi combi
General
Gas council numbers - 41-288-05 47-673-02 47-673-03 47-673-04
Boiler control modulating or on/off
Nominal output Pn (80/60°C) (CH) kW 21.6 21.6 29.4 33.3
Nominal output Pn (50/30°C) (CH) kW 23.0 23.0 31.3 35.5
Nominal input Qn Hi kW 5.8 - 22 5.8 - 22 6.1 - 30 6.3 - 34
Nominal input Qnw Hi kW - 28.0 35.0 39.0
Assembly dry weight kg 29.0 30.5 32 34.5
Noise level at distance of 1m from the boiler
dB(A) < 44
(at full load)
Gas and flue details
Classification due to discharging flue gases - C13, C33, C83
Gas type permitted - II2H 3P (natural gas and propane) *
Gas inlet pressure natural gas mbar 20 - 30
Gas consumption natural gas maximum mn3/h 2.3 3.0 3.5 3.9
Gas flue rate kg/h 37 47 57 62
Gas inlet pressure propane mbar 37 - 50
3
Gas consumption propane maximum mn /h 0.85 1.2 1.3 1.6
NOx Class 2) - 5 1)
NOx annual emission (n = 1) ppm < 30
mg/kWh < 53
Residual fan duty (full load) Pa 50 100 100 140
CH side
Water capacity heat exchanger and piping l 1.8 1.8 2.0 2.2
Expansion vessel size l 8
Minimum operating water pressure bar 1
Maximum operating water pressure PMS bar 2.5
Water temperature maximum °C 110
Operating temperature maximum °C 95
Residual head dT = 20°C mbar ^ 250 ^ 250 ^ 250 ^ 200
2
Domestic hot water side )
Tap capacity D (dT = 35°C) l/min - 11.4 14.2 15.9
Minimum tap flow l/min - 1.2 1.2 1.2
Operating pressure PMW min. - max. bar 0.5 - 8 0.5 - 8 0.5 - 8
Water resistance (nom. output) incl. flow restrictor bar - 1.3 - -
Water resistance (nom. output) excl. flow restrictor bar - 0.1 0.1 0.1
Electrical
Main supply V/Hz 230 / 50
Power consumption W maximum W 115 115 150 180
in stand-by status W <3
Degree of protection IP X4D
table 15 Summary of technical data
1
) Measured according EN 483 (Class 5 complies with a
limited concentration of NOx < 70 mg/kWh)
2
) This data applies for natural gas.
* For 39c a propane kit is required.

59
Remeha Avanta Plus

8.2 The boiler components

1 1. Automatic air vent


2. Flue / Air inlet connection
2 3. Flue gas measuring point
4. Heat exchanger
3 5. Front plate heat exchanger
6. Air inlet tube
7. Gas combination block
4 14 8. Two channel time clock (optional)
9. Control panel
5 10. Pressure gauge
11. Circulation pump
13 12. Expansion vessel
13. Ignition/ionization electrode
6 12 14. Stand off frame (optional)

7
8.3 Working principle
The Remeha Avanta Plus casing serves as a sealed air box,
with air drawn in by the fan. On the outlet side of the fan is
11 a venturi, into which a measured quantity of gas is injected
8
based on the volume of air available. The fan speed con-
9 trol is dependent on the settings of the external control, the
10 advanced boiler controller ‘abc®’ and the prevailing tempera-
tures (measured by the temperature sensors).

LT.AL.W7H.000.202 This method of gas/air ratio control ensures that the gas
quantity is precisely adjusted to the air quantity. Thus creating
optimum combustion over the whole heat input range. The gas
and air is mixed in the venturi and then passes into the spe-
cially designed pre-mix burner. After combustion, the hot flue
gas is directed through a specially designed, high efficiency
helicoil stainless steel heat exchanger with a large surface
area, and transfers it’s heat to the system water circulating
around the coils. In the condensing part of the exchanger the
water vapour in the flue gas condenses within it and the heat
released during this process (the so-called latent or condens-
ing heat) is also transferred to the system water. The conden-
sate water so formed is discharged from the heat exchanger
via a siphon.

60
o
In normal operation, the boiler’s flue gas discharge will
produce a visible white condensing “plume” and therefore care
should be taken when choosing a location for the terminal.

Combi boiler operation


The Remeha Avanta Plus 28c, 35c and 39c are combination
boilers with an integral plate heat exchanger providing instant
domestic hot water. On opening a hot water tap, detected by
a flow sensor, which is located on the cold water inlet side of
the heat exchanger detects the demand. This sensor then acti-
vates the motorised three-way valve to divert primary flow to
the plate heat exchanger which raises the temperature of the
cold water supply by a minimum of 35°C to provide domestic
hot water. Once the demand for hot water stops the motorised
valve automatically returns to the DHW position. This three-
way valve is electrically controlled by the ‘abc®’ control and
only consumes power when it is changing to a different posi-
tion.
The plate heat exchanger is protected from debris by two fil-
ters one in the cold water supply and one in the primary flow
to the diverting valve – Note: the primary flow filter self cleans
when the flow reverts back to heating mode.

System boiler operation


The Remeha Avanta Plus 24s the same design and layout
as the combi range without the DHW components (three way
valve and plate heat exchanger).

8.3.1 Regulating
The Remeha Avanta Plus is a fully modulating boiler and can
be regulated using one or more of the following methods;
1. Open Therm – 2 wire interface compatible with the
Remeha Celcia 15 room compensator and the Remeha
Celcia 20 outside weather compensator or with any other
proprietor’s OpenTherm® controls.
2. Open Therm thermostat in combination with an external
time clock.
3. On/Off room thermostat – volt free (on the X9 terminal
strip).
4. On/Off room thermostat – 230 V (on the X2 terminal strip).
5. 230 V Switching time clock - compatible with the Remeha
two channel time clock or with any other proprietor’s time
clock. For further details see par. 2.8.

8.3.2 Advanced boiler control (‘abc®’-control)


An intelligent advanced boiler control (‘abc®’) continuously
monitors the boiler conditions and ensures a very reliable
supply of heat. This control system is adept at dealing with
negative influences from the system such as flow reduction,
airflow problems and alike. In the event of such influences, the
boiler will not go to “lock-out” failure mode, but will in the first
instance modulate back, and if necessary, depending on the
nature of the circumstances, will temporarily switch off (shut-
down or control stop), and then after a short while simply try
again.

61
Remeha Avanta Plus

o
Provided that the situation is not actually hazardous, the
Remeha Avanta Plus will always try to supply heat.
The ‘abc®’- control prevents unnecessary additional call outs.

8.3.3 Regulating the water temperature


The Remeha Avanta Plus is fitted with an electronic tempera-
ture regulator with flow and return temperature sensors. The
flow temperature can be set to between 20 and 85°C, see
2.9.8 (factory setting 75°C) The boiler modulates it’s output up
and down to match the flow set point from internal or external
control. When the boiler is at it’s at minimum output and the
flow temperature still continues to rise, once the flow set point
is exceeded by 5°C the boiler will shut down on a controlled
stop (code 8).

8.3.4 Low flow / water protection


The Remeha Avanta Plus has a low-water protection based on
temperature readings. By modulating down as soon as there
is a risk of an insufficient water flow, the boiler will keep work-
ing for as long as possible. An insufficient water flow, however
caused, - indicated by a flow/return dt ] 45°C or a rate of
rise in the flow temperature > 1°C/sec – will be sensed by
the ‘abc®’ control which will shut the boiler down in a blocking
mode with the display showing (code 9) for 10 minutes and
before re-starting.
If there is no water in the boiler or if the pump is not running, it
will go to lock out (code é7) and require manual re-set.

8.3.5 High Limit temperature protection


If the flow temperature exceeds 110°C the high limit tempe-
rature protection device switches off the boiler in a lock out
mode with the display showing (code é1) This mode will
require a manual re-set.
When the fault is corrected, the boiler can be restarted by
pressing the reset-key on the control panel and holding for 3
seconds.

62
9 EFFICIENCY DATA AND GAS EFFICIENCY LABELS
9.1 Annual efficiency
Up to 110.5 % in relation to Hi at a load of 30% and a return
temperature of 30°C.

9.2 Water-side efficiency


Up to 98,3 % in relation to Hi at full load and an average water
temperature of 70°C (80/60°C).
Up to 104.4 % in relation to Hi at full load and an average
water temperature of 40°C (50/30°C).

63
P l u s
Av a n t a
R e m e h a

Broag Ltd.
Remeha House
© Copyright
Molly Millars Lane
All technical and technological information contained in these technical instructions, as