Report for ABB Tmax XT5 MCCB with S200 MCB Combination Back up Selectivity
These techniques are applied to evaluate the selection of breaker for the installation.
1 of 6
Report for ABB Tmax XT5 MCCB with S200 MCB Combination Back up Selectivity
2 of 6
Report for ABB Tmax XT5 MCCB with S200 MCB Combination Back up Selectivity
This diagram is based on the fault level provided in the coordination study received.
For determining electro dynamic stress, the value of peak current shall be obtained by multiplying the
RMS value of AC application short circuit current by factor “n”. Factor “n” shall be obtained from below
table.
3 of 6
Report for ABB Tmax XT5 MCCB with S200 MCB Combination Back up Selectivity
4 of 6
Report for ABB Tmax XT5 MCCB with S200 MCB Combination Back up Selectivity
Figure-01
31.47 kA Peak Limit to 27.9 kA which is in RMS Value 13.95kA. ie. As per above table 27.9/2.0 = 13.95kA
Figure-02
Figure-03
5 of 6
Report for ABB Tmax XT5 MCCB with S200 MCB Combination Back up Selectivity
Back up chart for XT5 MCCB with S200 MCB at 415V AC. Refer below the details.
Table-01
Conclusion:
As validated from the above details and back up chart, the combination of XT5 MCCB with electronic trip
unit suitably selected with prospective fault level in the point of installation (selective main circuit breaker)
as upstream, with S200 series 32 Amp MCB 10kA as downstream, the backup protection is available up to
20kA.
Hence the MCCB limiting characteristics and back up protection shall work safely for the above
installation.
********************************************