Professional Documents
Culture Documents
Manual Inglês G7 EtherNet-IP
Manual Inglês G7 EtherNet-IP
Manual Inglês G7 EtherNet-IP
CM092
Applicable products: Yaskawa F7U, G7U, P7U, E7U, G5M (Spec F),
G5M(600V) and G5HHP drives.
1. Unpack the CM092 EtherNet/IP Option kit and verify that all
components are present and undamaged.
2. Connect power to the Yaskawa AC drive and verify that the drive
functions correctly. WARNING
This includes running the drive from the operator keypad. Refer to the Dangerous voltages in excess of 400VDC (230V drives) or 800VDC
appropriate drive technical manual for information on connecting and (460V drives) are present at the DC bus terminals of the drive.
operating the drive.
4. Remove the operator keypad and drive cover.
3. Remove power from the drive and wait for the charge lamp to be
completely extinguished. a. Remove the operator keypad.
Wait at least five additional minutes for the drive to be completely b. Remove the terminal and control covers.
discharged. Measure the DC bus voltage and verify that it is at a safe level. c. Remove the option card hold-down by carefully
compressing the top and bottom until it becomes free
of its holder. Lift it out.
9. Connect to the EtherNet/IP Option Card. end to the RJ-45 EtherNet/IP socket on the configuration device,
typically a controller, laptop or other PC.
Note: Due to the presence of high voltage in the area of the network
connection, insulating the RJ-45 M-F cable connection is required. 2. Connection through hub or switch: To connect through a switch,
a. Prior to connecting the RJ-45 M-F network cable, slide the supplied hub or router, connect the RJ-45 socket on the RJ-45 M-F cable to
insulated tubing (4"x1") over the female end of the supplied RJ-45 M-F the switch, hub or router using a standard CAT-5 patch cable.
cable. b. After the network connection is made, slide the insulated tubing
(4"x1" Insulated Tubing) over the connection and secure it in place using
1. Direct connection: To connect directly to the EtherNet/IP Option
the supplied cable ties.
Card, plug one end of a CAT-5 EtherNet/IP crossover cable into the
RJ-45 socket on the supplied RJ-45 M-F cable. Connect the other
10. Configure the EtherNet/IP network. b. If the network configuration requires that devices have a static IP
address, the EtherNet/IP Option Card's configuration can be changed to
a. The default configuration option for the EtherNet/IP Option Card is
USER and the appropriate static IP address can be entered via the
DHCP (Dynamic Host Configuration Protocol). Thus there must be a
EtherNet/IP Option Card's web pages as shown below.
DHCP Server connected to the network in order to have the IP address of
the EtherNet/IP Option Card set. For detailed information on how to set Note that the EtherNet/IP Option Card must first have been assigned an
up the Rockwell BOOTP/DHCP Server on a PC refer to the appropriate IP address via DHCP before its configuration can be changed.
Rockwell document or Yaskawa's Application Note AN.AFD.10.
IP address: 192.168.1.19
Configuration: USER
IP Address: 192.168.1.37
Subnet mask: 255.255.255.0
Enable Browser Interface
Gateway Usage Disabled
WARNING
Dangerous voltages in excess of 400VDC (230V drives) or 800VDC
(460V drives) are present at the DC bus terminals of the drive.
b. Place an insulated wire reset jumper between test points C and /LD on
the EtherNet/IP Option Card as shown in the figure to the right.
c. Reapply power to the AC drive and wait approximately 10 seconds for
the power-up cycle to complete.
d. Remove power from the AC drive and remove the jumper between C and
/LD on the EtherNet/IP Option Card.
e. Reapply power to the AC drive and wait approximately 10 seconds for
the power-up sequence to complete.
16. Important notes d. To simplify the drive configuration, EDS file can be obtained at
www.yaskawa.com. Select Downloads, By Inverter Drives, By
a. It is strongly recommended that shielded CAT-5 patch or crossover cable
Product, and Network Comms-Ethernet. Then select the appropriate
be used for all network cables. (Refer to step 9 above for the proper
EDS file based on the drive series and the latest version from those listed.
selection of patch or crossover cable).
EDS files for individual drive models are compressed into a single Zip
b. Switches implementing IGMP snooping are strongly recommended. file and need to be un-zipped into a temporary directory in order to be
When IGMP snooping is used, devices will only receive the multicast installed.
packets in which they are interested.
e. Refer to the appropriate user, programming or parameter access manual
c. The maximum number of simultaneous connections is: 1 for I/O, 4 for for a complete list of drive parameters and registers available. A list of
Explicit, 2 for Drive Wizard. applicable manuals is available at the end of this document.
a. Place the supplied MAC ID label on the side of the drive either above or below the drive nameplate.
Nameplate for all drives except G5HHP drives Nameplate for G5HHP drives
b. To simplify the drive configuration, EDS file can be obtained at www.yaskawa.com. Select Downloads, By Inverter Drives, By Product, and Network
Comms-Ethernet. Then select the appropriate EDS file based on the drive series and the latest version from those listed. EDS files for individual drive
models are compressed into a single Zip file.
18. EtherNet/IP Option Card fault codes
The table of EtherNet/IP Option Card fault codes returned by the drive is shown below. Refer to the appropriate drive user and/or programming manual(s) for drive
specific information on the fault returned.
Note: G5HHP drive differences are denoted by bold text inside carets <> in the following table.
EtherNet/IP
EtherNet/IP Fault Code Description Fault Code Description
[hex]
[hex]
0000h None 5300h OPE errors (01,02,03,05,06,07,08,09,10,11)
2120h Ground Fault (GF) 6320h EEPROM R/W Error (ERR)
2130h Short Circuit (SC) 7110h Dynamic Braking Transistor (RR) <Reserved>
2200h Inverter Overload (OL2) 7112h Dynamic Braking Resistor (RH) <Reserved>
Supported Output Instances for Assembly Note: G5HHP drive differences are denoted by bold text
Object Class 04 inside carets <> in the following tables.
0h - Net Reference Net Run/Stop - - Fault Reset Run Reverse Run Forward
<Not Available> <Not Available>
21 (15h) 1h Reserved
2h Speed Reference (Low Byte) [Scaled by parameter o1-03] [U1-01]
3h Speed Reference (High Byte) [Scaled by parameter o1-03] [U1-01]
0h - Net Reference Net Run/Stop - - Fault Reset Run Reverse Run Forward
<Not Available> <Not Available>
1h Reserved
23 (17h) 2h Speed Reference (Low Byte) [Scaled by parameter o1-03] [U1-01]
3h Speed Reference (High Byte) [Scaled by parameter o1-03] [U1-01]
4h Torque Reference (Low Byte) [0.1%] [U1-09]
5h Torque Reference (High Byte) [0.1%] [U1-09]
Running Fwd
0h - - - - - <Running 1 FWD> - Fault
1h Reserved
70 (46h) Output Frequency (Low Byte) [Scaled by parameter o1-03] [U1-02]
2h
<Speed Actual (Low Byte) [Scaled by parameter o1-03]>
0h Speed Net Net Run/ Drive Ready Running Rev Running Fwd Alarm Fault
Agree Reference Stop <Running 2 (REV)> <Running 1 (FWD)>
1h Reserved
71 (47h) Output Frequency (Low Byte) [Scaled by parameter o1-03] [U1-02]
2h
<Speed Actual (Low Byte) [Scaled by parameter o1-03]>
@Running @Running
0h @Fault @Alarm @Drive Ready @Speed Agree @Reset Rev @Zero Speed Fwd
@Zero Servo Terminal M1-M2
1h Complete - Terminal M5-M6 Terminal M3-M4 <Terminals 53- @Local Undervoltage @OPE Error
<Terminals 20-50> <Terminals 19-50> Mode
<Zero Servo> 57>
2h Output Frequency (Low Byte) [Scaled by parameter o1-03] [U1-02]
151 (97h)
3h Output Frequency (High Byte) [Scaled by parameter o1-03] [U1-02]
4h Torque Reference (Low Byte) [0.1%] [U1-09]
5h Torque Reference (High Byte) [0.1%] [U1-09]
6h Output Current (Low Byte) [0.01A up to 11kW, 0.1A 15kW and above] [U1-03]
7h Output Current (High Byte) [0.01A up to 11kW, 0.1A 15kW and above] [U1-03]
Refer to 13h Error Alarm 1 (High Byte) [See Section 18 on Page 7 for a list of fault codes]
Table 2 for 14h Error Alarm 2 (Low Byte) [See Section 18 on Page 7 for a list of fault codes]
G5HHP
Error Alarm 15h Error Alarm 2 (High Byte) [See Section 18 on Page 7 for a list of fault codes]
Details 16h Error Alarm 3 (Low Byte) [See Section 18 on Page 7 for a list of fault codes]
17h Error Alarm 3 (High Byte) [See Section 18 on Page 7 for a list of fault codes]
A2-06 10B User Parameter 06 180h ~ 0 b5-07 19A PID Offset -100.0 ~ 0.0
+100.0
A2-07 10C User Parameter 07 180h ~ 0 b5-08 19B PID Delay 0.00 ~ 10.00 0.00
Dwell Reference at
A2-08 10D User Parameter 08 180h ~ 0 b6-01 19C 0.0 ~ 150.0 0.0
Start
A2-09 10E User Parameter 09 180h ~ 0 b6-02 19D Dwell Time at Start 0.0 ~ 10.0 0.0
Dwell Reference at
A2-10 10F User Parameter 10 180h ~ 0 b6-03 19E 0.0 ~ 150.0 0.0
Stop
A2-11 110 User Parameter 11 180h ~ 0 b6-04 19F Dwell Time at Stop 0.0 ~ 10.0 0.0
A2-12 111 User Parameter 12 180h ~ 0 b7-01 1A0 Droop Gain 0.0 ~ 100.0 0.0 FV
A2-13 112 User Parameter 13 180h ~ 0 b7-02 1A1 Droop Delay 0.03 ~ 2.00 0.05 FV
A2-14 113 User Parameter 14 180h ~ 0 b8-01 1A2 Energy Savings Gain 0 ~ 100 80
Energy Savings
A2-15 114 User Parameter 15 180h ~ 0 b8-02 1A3 0.0 ~ 150.0 0.0
Reference
A2-16 115 User Parameter 16 180h ~ 0 b9-01 1A4 Zero Servo Gain 0 ~ 100 5 FV
Zero Servo Completion
A2-17 116 User Parameter 17 180h ~ 0 b9-02 1A5 0 ~ 16383 10 FV
Width
A2-18 117 User Parameter 18 180h ~ 0 C1-01 200 Accel Time 1 0.0 ~ 6000.0 30.0
A2-19 118 User Parameter 19 180h ~ 0 C1-02 201 Decel Time 1 0.0 ~ 6000.0 30.0
A2-20 119 User Parameter 20 180h ~ 0 C1-03 202 Accel Time 2 0.0 ~ 6000.0 30.0
A2-21 11A User Parameter 21 180h ~ 0 C1-04 203 Decel Time 2 0.0 ~ 6000.0 30.0
A2-22 11B User Parameter 22 180h ~ 0 C1-05 204 Accel Time 3 0.0 ~ 6000.0 30.0
A2-23 11C User Parameter 23 180h ~ 0 C1-06 205 Decel Time 3 0.0 ~ 6000.0 30.0
A2-24 11D User Parameter 24 180h ~ 0 C1-07 205 Accel Time 4 0.0 ~ 6000.0 30.0
A2-25 11E User Parameter 25 180h ~ 0 C1-08 207 Decel Time 4 0.0 ~ 6000.0 30.0
A2-26 11F User Parameter 26 180h ~ 0 C1-09 208 Fast Stop Time 0.0 ~ 6000.0 30.0
A2-27 120 User Parameter 27 180h ~ 0 C1-10 209 Accel/Decel Unit Select 0~1 0
Accel/Decel Switch
A2-28 121 User Parameter 28 180h ~ 0 C1-11 20A 0.0 ~ 150.0 0.0
Frequency
A2-29 122 User Parameter 29 180h ~ 0 C2-01 20B S-Curve Accel at Start 0.00 ~ 2.50 0.20
A2-30 123 User Parameter 30 180h ~ 0 C2-02 20C S-Curve Accel at End 0.00 ~ 2.50 0.20
A2-31 124 User Parameter 31 180h ~ 0 C2-03 20D S-Curve Decel at Start 0.00 ~ 2.50 0.20
A2-32 125 User Parameter 32 180h ~ 0 C2-04 20E S-Curve Decel at End 0.00 ~ 2.50 0.20
b1-01 180 Reference Source Select 0~3 1 C3-01 20F Slip Comp Gain 0.00 ~ 2.50 0.00
Run Command Source
b1-02 181 0~3 1 C3-02 210 Slip Comp Time 0 ~ 10000 2000
Select
b1-03 182 Stopping Method Select 0~3 0 C3-03 211 Slip Comp Limit 0 ~ 250 200
H3-12 414 AI Terminals Filter Time 0.00 ~ 2.00 0.00 L7-02 49F Reverse Torque Limit 0 ~ 300 200 OLV, FV
AO Terminal 45 Function Forward Regen Torque
H4-01 415 1 ~ 33h 2 L7-03 4A0 0 ~ 300 200 OLV, FV
Select Limit
Reverse Regen Torque
H4-02 416 AO Terminal 45 Gain 0.00 ~ 2.50 1.00 L7-04 4A1 0 ~ 300 200 OLV, FV
Limit
DB Resistor Protection
H4-03 417 AO Terminal 45 Bias -10 ~ +10 0.0 L8-01 4A4 0~1 0
Select
AO Terminal 48 Function
H4-04 418 1 ~ 33h 3 L8-02 4A5 OH Pre-Alarm Level 50 ~ 110 95
Select
H4-05 419 AO Terminal 48 Gain 0.00 ~ 2.50 0.50 L8-03 4A6 OH Pre-Alarm Select 0~3 3
H4-06 41A AO Terminal 48 Bias -10.0 ~ +10.0 0.0 L8-05 4A8 Input Phase Loss Select 0~1 0
AO Terminal Signal Type Output Phase Loss
H4-07 41B 0~1 0 L8-07 4AA 0~1 1
Select Select
H5-01 41C Modbus Node Address 0 ~ 20 1F o1-01 500 User Monitor Select 4 ~ 33 6
Power-On Monitor
H5-02 41D Modbus Baud Rate Select 0~3 3 o1-02 501 1~4 1
Select
H5-03 41E Modbus Parity Select 0~2 0 o1-03 502 Display Scaling Select 0 ~ 39999 0
Serial Fault Stopping
H5-04 41F 0~3 3 o1-04 503 V/f Pattern Unit Select 0~1 0
Method
Serial Fault Detection Modbus Address
H5-05 420 0~1 1 o1-05 504 0~1 6
Select Display Select
Motor Overload Fault Local/Remote Key
L1-01 480 0~1 1 o2-01 505 0~1 1
Select Select
Motor Overload Time Stop Key Function
L1-02 481 0.1 ~ 5.0 1.0 o2-02 506 0~1 1
Constant Select
Power Loss Detection User Initialize Default
L2-01 482 0~2 0 o2-03 507 0~2 0
Select Select
Power Loss Ride-Thru Drive Model kVA
L2-02 483 0.0 ~ 2.0 1.0 o2-04 508 0 ~ FFh 4400
Time Select
Minimum Baseblock Operator MOP
L2-03 484 0.0 ~ 25.5 10.0 o2-05 509 0~1 0
Time Function Select
Voltage Recovery Ramp Operator Detection
L2-04 485 0.0 ~ 5.0 3.0 o2-06 50A 0~1 1
Time Select
Undervoltage Detection Elapsed Time Initial
L2-05 486 300 ~ 420 380 o2-07 50B 0 ~ 65535 0
Level Setting
Elapsed Time Function
L2-06 487 KEB Decel Time 0.0 ~ 100.0 0.0 o2-08 50C 0~1 0
Select
Stall Prevention Accel Initialization Mode
L3-01 488 0~2 1 o2-09 50D 0~2 1
Select Select
Stall Prevention Accel
L3-02 489 0 ~ 200 150 - - - - -
Level
Note: 1. Default values were determined through a 2-wire reset on drive model 4400. Default values may be different for different drive models.
2. Use address FFDDh for the ACCEPT command
3. Use address FFFDh for the ENTER command
IMPORTANT: Limit the use of the ENTER command. The drive has limited writes when using the ENTER command.