RC Beam Design Based On ACI 318 14
RC Beam Design Based On ACI 318 14
RC Beam Design Based On ACI 318 14
ANALYSIS
CHECK FLEXURAL CAPACITY
c = 0.003
Cover = 40 mm, (ACI 318 Table 20.6.1.3.1)
=
d = 735.50 mm
0.90 (ACI 318-14 21.2) 0.85 f c'
c =
A s' f s'
0.0030
s,max = 0.0050 (ACI 318-14 21.2.2)
1 = 0.804 (ACI 318-14 22.2.2)
Fc cab
0.85f'
a= 99.00 mm
c = a/ 1 = 123.20 mm Parabolic
t = 0.015
> 0.005, tension controlled OK!
Asfy
Mn = As fy (d - a/2)
Mn = 1003.75 kN-m
prov'd = 0.0095 max =
> 500 kN-m [Satisfactory]
min =
< 0.0253
[Satisfactory] > 0.0035 (ACI 318 9.6.1)
=
= 411.27 kN
where 0.75
200.0 < 424.8 kN [Satisfactory]
. 406.72 kN ,<== applicable
Check shear reinforcement (ACI 22.5 & 9.6.3.3)
V c A MIN , 100
0 , for V u
'
f
where, c 5.87
V d
2
Av 50b w 0.75 f 'c b w V c B MIN u , 1.0
s , for V u V c Mu
Re qD
fy
MAX , 0.294
fy 2
V u V c , for V c V u
df y
Av
s
Pr ovD
= 741.6 mm2 / m < 1131.0 mm2 / m [Satisfactory]
V u V c
Vs
0.00 kN, (ACI 22.5.1.1)
, 24) for V s 4b wd f c
d '
S max, shear
MIN (
2
MIN ( d , 12) for V s 4b wd f '
= 367.75 > S= 200 mm [Satisfactory]
4 c
CHECK TORSION CAPACITY
Check section limitation (ACI 22.7.7.1)
Pcp = 2,720
mm, (outside perimeter of the concrete cross
section.)
2
20.0 < 27.0 kN-m Acp = 448,000 mm (area enclosed by outside perimeter of
Torsional reinforcement NOT REQD. concrete cross section.)
,
0.00 mm2 / m < actual = 565.49 mm2 / m [Satisfactory]
Determine the corresponding area of longitudinal reinforcement (derived from ACI 22.7.6.1 & 9.6.4.3)
At
A L MAX Ph MAX
'
f yv 5 Acp f c f yv
s f yv
A 25 b
s
t w
, ,
Ph 4018.60 mm2
f yL f yL f yL