Professional Documents
Culture Documents
AC Lab Experiment No. 3
AC Lab Experiment No. 3
College of Engineering
Mechanical Engineering Department
Refrigeration & Air-Conditioning Lab.
4th Year - Experiment No. (3)
2020/2021
University of Baghdad
College of Engineering
Mechanical Engineering Department
Refrigeration & Air-Conditioning Lab.
4th Year - Experiment No. (3)
Objective
Analyzing the thermal performance of cooling coils using the contact factor (CF)
and bypass factor (BF).
Introduction
In the test rig used in this experiment, air is drawn over a cooling coil by an axial
fan. The cooling coil consists of a series of four-tube rows through which chilled water
is flowing. A vapor compression refrigeration cycle located at the back side of the test
rig is responsible of supplying the chilled water. As air passes over the surface of the
cooling coil, it is cooled and dehumidified. The bypass factor is a function of physical
and operating characteristics of the conditioning apparatus and represents that portion
of the air which is considered to pass through the cooling coil completely unaltered.
2
The effect of varying the bypass factor (between 0.05 and 0.2) on the air
conditioning equipment can be summarized as follows:
Figure (1) illustrates the cooling and dehumidification process that can be
accomplished by using a cooling coil. Line (A-B) represents a cooling and
dehumidification process in which there is a simultaneous removal of sensible and
moisture (latent heat) from the air. Point (A) represents the conditions of the entering
air while point (B) represents the conditions of the leaving air. The intersection of line
(A-B) with the saturation line at point (C) represents the apparatus dew point. When
moist air is cooled to a temperature below its dew point, some of the water vapor will
condense and leave the air stream.
The bypass factor and contact factor can be evaluated mathematically by using
the following equations:
ℎ −ℎ 𝑡 −𝑡 ℎ𝐴 −ℎ𝐵 𝑡𝑑𝐴 −𝑡𝑑𝐵
𝐵𝐹 = ℎ𝐵−ℎ𝐶 = 𝑡𝑑𝐵−𝑡𝑑𝐶 and 𝐶𝐹 = =
𝐴 𝐶 𝑑𝐴 𝑑𝐶 ℎ𝐴 −ℎ𝐶 𝑡𝑑𝐴 −𝑡𝑑𝐶
The sensible heat factor is defined as the ratio of sensible heat to the total heat
(summation of sensible and latent heat), as shown in figure (2).
3
QS QS
SHF
QT QS QL
4
Measured Data
1
2
3
4
Discussion
1. What is the source of chilled water in the experiment? Explain briefly.
2. In the four cases studied in the experiment, explain the variations occurred to each
of the following factors: BF, CF, and SHR.
3. Can point (B) in figure (2) be located on point (C)? And why?
4. Do heating coils have bypass factor? How it can be calculated?
5. Explain the difference between room and apparatus sensible heat ratio.
Important Notes
1. Write (experiment name, your name, class, section, group, experiment date and
submission date on the first page of the report.
2. The report must be submitted within 7 days from the day of the experiment.
3. Two marks will be omitted for each delay day.
5
6