The Journal of Engineering - 2022 - Llamo Labor - A New Method To Calculate Corona Losses For Active Conductors Considering

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Received: 1 August 2021 Revised: 20 April 2022 Accepted: 9 May 2022 The Journal of Engineering

DOI: 10.1049/tje2.12155

ORIGINAL RESEARCH

A new method to calculate corona losses for active conductors


considering real transmission line unbalance

Héctor Silvio Llamo-Laborí Ariel Santos-Fuentefria

Electrical Engineering Department, Technological Abstract


University of Havana Jose Antonio Echeverría
(CUJAE), 114 Street, # 11901 / Ciclovía y Rotonda
This paper shows the characteristics of an algorithm that calculates the corona losses of
CP 19390, Marianao, Havana, Cuba transmission lines. The line can have up to four circuits, with any configuration, with sin-
gle or bundled conductors, and taking into account the line unbalance. This is achieved
Correspondence by modelling the lines in phase quantities, for active conductor, and calculating the corona
Ariel Santos-Fuentefria, Electrical Engineering
losses for each one. The results are given per active conductor and average per bundle.
Department, Technological University of Havana
Jose Antonio Echeverría (CUJAE), 114 Street, In lines with several conductors per phase the results are given per circuit and a total one.
# 11901 / Ciclovía y Rotonda CP 19390, Marianao, These characteristics allow choosing the most convenient configuration and spacing for the
Havana, Cuba.
conductor bundles, which will reduce and balance corona losses. The results found with
Email: asfuentefria@electrica.cujae.edu.cu
this method show that the value of the losses calculated with the formulas with transmis-
sion lines symmetrically transposed is conservative. The configuration and the number of
conductors per phase have a noted influence in the value and the asymmetry of the corona
losses. In double circuit lines, corona losses can be reduced by changing the arrangement of
the phases of circuit two in reference to circuit one, with the advantage that, at the design
stage, those changes are costless.

1 INTRODUCTION corona. Corona effect, produces audible hissing in the vicinity


of the transmission lines, power and energy losses, television
In a power transmission line, are two types of active power interference and corrosion in conductors and metal fitting of
losses: Transverse losses, due to corona effect [1, 2] and insu- lines [4, 6–12].
lator leakage, and longitudinal losses, due to the effective When a transmission line is modelled, through its π-
resistance of the conductors. When the transmission line is circuit, either Equivalent or Nominal, losses due to corona
designed, corona losses are taken into account. If is necessary, effect and insulator leakage are neglected because in a well-
the design is modified to reduce it to about 0.65 kW/km under designed transmission line such losses are negligible [13, 14].
fair weather conditions for lines at voltages higher than 138 kV However, such losses significantly contribute to the reduc-
[3]. Losses due to leakage currents in insulators are generally tion of the efficiency of the electrical energy transmission. In
negligible. overhead transmission lines at extra high voltages (345–750
If the conductors of a transmission line are subjected to kV), losses can reach 300 kW/km due to adverse weather
an increasing voltage, the potential gradient at the surface of conditions [15].
the conductor can reaches a value greater than the dielectric The occurrence and intensity of corona discharges, and hence
strength of the air. At that point, energy losses occur due to their losses, is affected by the following factors: The electric field
the current flowing through the air, that is, the air surround- gradient on the conductor surface [16, 17], the conductor sur-
ing the conductor is ionized. Everything happens as if the air face condition [6, 18], weather conditions [19–21], the relative
had become a conductor, causing a leakage current. In over- air density [22, 23], the effect of water on the conductor surface
head conductors, the effect is visible in the darkness, being [20, 22], the average operating voltage of the line [19, 24, 25],
possible to appreciate how they are surrounded by a luminous, the size of phase conductors [18, 26], bundled conductor lines
bluish, circular cross-section halo [1, 4, 5] in the form of a [5, 12, 16, 17], the existence or not of shield conductors [27],

This is an open access article under the terms of the Creative Commons Attribution-NonCommercial-NoDerivs License, which permits use and distribution in any medium, provided the
original work is properly cited, the use is non-commercial and no modifications or adaptations are made.
© 2022 The Authors. The Journal of Engineering published by John Wiley & Sons Ltd on behalf of The Institution of Engineering and Technology.

J. Eng. 2022;2022:725–731. wileyonlinelibrary.com/iet-joe 725


20513305, 2022, 7, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/tje2.12155 by CAPES, Wiley Online Library on [08/05/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
726 LLAMO-LABORÍ AND SANTOS-FUENTEFRIA

the sag value of the phase and shield conductors [28], the line ing the asymmetry of the line and its unbalance. The proposed
unbalance and the type of structure. algorithm allows minimizing the losses due to corona effect,
Through empirical observations, Peek made the first although without an optimization process.
approach to the phenomenon of the corona effect, using for- The line is modelled through a matrix calculation per active
mulas for its quantitative study in the case of cylindrical, parallel conductor, with the following steps:
and smooth-surfaced conductors. The expression used by Peek
[29] depend, among other parameters, on the relative density 1. From the average line voltage at sending end, given as data,
of the air, the frequency of the system, the radius of the con- a vector of an order equal to the number of active conduc-
ductor, the effective distance between the phases, the voltage tors of the line is formed with the line-to-neutral voltages,
between the phase and the neutral and the critical or disruptive considering that they are balanced because they are those
voltage. However, this expression is only valid for one conduc- of a source of infinite capacity representing the power sys-
tor per phase and recommended for thin conductors, with less tem to which the line is connected. This vector, (Ue ), for a
than 25.4 mm in diameter, it is also not valid when the voltages double circuit line with two conductors per phase, and two
are similar. Peek also did not consider adverse weather con- shield wires, initially, would be of order fourteen and the
ditions in the proposed expression. For the calculation of the corona would be calculated with an admittance matrix of
critical voltage, the irregularities of the conductor are taken into order twelve. This characteristic makes the normal unbalance
account, whether it is perfectly smooth, if it is rough or aged, of the line be taken into account.
or if it is stranded, to give some examples. Peek’s formula has 2. Next, the matrix of the potential coefficients due to Maxwell
been used by several authors for the analysis of corona losses (P’) is calculated, which is initially of an order equal to the
[30–32]. It has also been used as a basis for the development of number of phase conductors plus the shield wires.
new calculation methods [22, 33, 34]. 3. The next step is to incorporate the effect of the shield con-
Another common approach is due to Peterson [35], who ductors to the matrix (P’) by reducing their order to the
proposed an expression for calculating corona losses that has number of active conductors in the line, thus forming the
become a classic part of the literature on the subject. With matrix (P). For a double circuit with two conductors per
some differences regarding Peek, this formula appears in [9, phase, it would be of order twelve.
30, 34]. Peterson takes into account conductor irregularities and 4. To continue, the matrix with the capacitive susceptances (B’)
the calculation is performed for good weather conditions and per active conductor is calculated using the Equation (1).
assuming that the line is symmetrically transposed.
There are other methods for the calculation of corona losses (B′ ) = j 𝜔(P)−1 = j 𝜔(C) (1)
in transmission lines, such as Ryan and Henline [36], Carroll
and Cozzens [18, 37, 38] and others, using different approaches. 5. Now, it is possible to calculate the vector of capacitive
Peterson, in 1933, in a AIEEE discussion, proposed a formula currents per active conductor through Equation (2). These
for fair weather corona loss which has been become a clas- currents appear with the real unbalance of the line.
sic part of the literature on the subject [28, 39–41]. However,
these methods have two main disadvantages, the first one is that (I′ ) = (B′ )(Ue) (2)
they perform the calculations in good weather conditions and
the second is that they assume that the transmission lines are 6. Once the vector of capacitive currents per active con-
symmetrically transposed. ductor has been calculated, the critical or disruptive cur-
In reference of the first issue, there are numerous research rents per active conductor must be calculated from the
that analyse corona losses taking into account different expression (3).
approaches and different weather conditions; fog [42], frost [43,
44], rain [22, 45], ice [15], snow [22, 46], and sand [5], to give ′
some examples reported in literature. ICr−i = 1, 858 ⋅ 10−2 m1 m2 𝛿 2∕3 ⋅ f ⋅ ai (A∕km) (3)
Most of these studies assume that transmission lines are
symmetrically transposed, so it is necessary to investigate how where:
line unbalance influences on corona losses. In this work, an “i”: is the number of the active conductors.
algorithm is developed to calculate the corona losses taking m1 : Factor to take into account the irregularities of the
into account practically all the elements that modify it, without conductor.
assuming that the line is symmetrical. A 220 kV double circuit m2 : Factor to take into account the irregularities of the
transmission line is used as an example. conductor according to the number of wires in the outer layer.
a: External radius of the conductor.
f: Frequency in Hertz.
2 MATERIALS AND METHODS d: Factor to take into account the air density, given by
Equation (4).
The algorithm calculates the corona losses per active con-
ductor, for lines with more than one conductor per phase 0, 386 ⋅ PB
𝛿= (4)
(bundled conductors) and with more than one circuit, consider- 273 + t
20513305, 2022, 7, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/tje2.12155 by CAPES, Wiley Online Library on [08/05/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
LLAMO-LABORÍ AND SANTOS-FUENTEFRIA 727

where:
PB : Barometric pressure in millimetres of mercury.
t: Average ambient temperature in degrees Celsius.
273: Temperature of absolute zero in degrees Celsius.
In the algorithm, the barometric pressure is calculated as a
function of the height of the line trace above sea level using
expression (5).
[ ]
H
PB = log−1 log760 −
18336
[ ]
H
= log−1 2, 881 − mm of mercury (5) FIGURE 1 Double circuit transmission line with two phase conductors
18336

where:
H: Height of the line trace above sea level in meters.
760: Barometric pressure at sea level in millimetres of
mercury.

7. With the capacitive currents per active conductor, and


the critical capacitive current, as many Ii ′/I ′CR ratios are
calculated as there are active conductors.
8. With the ratios Ii ′/I ′CR the described subroutine is accessed
and the coefficients kC-i are obtained for each active
conductor.
9. Since all the terms are now available, the corona losses are
calculated for each of the active conductors of the line by
means of Equation (6) due to Peterson, but for each active
conductor “i”.
FIGURE 2 220 kV double circuit tower with two conductors per phase
567 ′ 2
ΔPi−PETERSON = kC −i I (6)
f i accumulated water drops due to dew, when the conductors
operate cold during the hours of minimum demand. When
where i = 1, 2, 3 — Numbers of active conductors. there is dew, the critical voltage is reduced by 20% and the
I ′: Nominal capacitive current of the line calculated from the corona losses increase as when it rains, but in the whole line.
capacitive susceptances to the positive sequence B ′1 For example, in a double circuit transmission line at 220 kV
kC : Experimental quantity calculated using the method found with 24 km with 0 h of dew per year, the corona losses are
in (3), entered with the ratio I ′/I ′CR and taken the coefficient 0.2404 kW/km. If it is augmented to 360 h of dew per year
kC for each active conductor. the corona losses will be 0.2450 kW/km, a 1.91% bigger.

10. In [3] it is stated that the critical or disruptive voltage of


the corona effect is reduced by 20% when it rains, so that 3 RESULTS AND DISCUSSION
corona losses increase. Relatively long transmission lines
are the ones with the highest corona losses. So that the To show the data input and algorithm results, a 220 kV double
calculated losses in a year are not much higher than the circuit transmission line with two phase conductors is used as
real losses, it is assumed that it does not rain over the an example. The two conductors per phase of steel reinforced
entire length of the line. Lizt and Pochop, in [3], propose aluminium with 400 mm2 , and steel shield wires with 70 mm2
to assume that it rains on one third of the line while the and 24 km length (see Figure 1).
remaining two thirds are under good weather conditions, The algorithm allows creating a new project to calculate the
but this relationship can be modified in the algorithm. To corona losses, read or modify a file already created, and it is also
calculate the maximum annual corona losses, in kilo Watt, possible to create a data file for the line structure. The algorithm
it is assumed that, when it rains, the critical or disruptive works with a series of stored structures, the corresponding
corona voltage is reduced by 20% and it can be chosen the configuration of the selected line (see Figure 2).
percentage of the line in which it is raining. Once the structure is selected, the database of stored conduc-
11. Another option of the algorithm is that it is possible to tors and shield wire is accessed. Two 400 mm2 steel-reinforced
choose the number of hours per year that the bottom aluminium conductors per phase and two 70 mm2 steel shield
surface of the conductors of the line is assumed to have wires were selected, whose data are shown in Table 1.
20513305, 2022, 7, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/tje2.12155 by CAPES, Wiley Online Library on [08/05/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
728 LLAMO-LABORÍ AND SANTOS-FUENTEFRIA

TABLE 1 Data of phase conductors and protective cables of the


transmission line under study

Resistance in Geometric Mean


ohm per Diameter in Radius in
Conductor kilometre. millimetres millimetres.

Phase 0.08 27.5 11.110


Shield wire 2.00 11.0 0.00015

TABLE 2 Additional data required for calculating corona losses FIGURE 3 Sectional section of the phase conductors of the transmission
line
Parameter Value

Type of curve described Parabole


TABLE 3 Capacitive currents per active conductor of the line under good
Average or nominal operating voltage of the line (kV of 245
weather conditions
L-L)
Height of the line trace in reference to the sea level (m) 0 Critical
Current capacitive
Average ambient temperature (Degrees Celsius) 26 Conductor Module current
Power system frequency (Hz) 60 number Abscissa (m) Ordered (m) (A RMS/km) (A RMS/km)
Reduction of critical corona voltage due to rainfall (%) 20 1 –5.9 25.27 0.305 0.5
Length of the line (km) 24 7 –5.5 25.27 0.303 0.5
Spacing between the bundle conductors (m) 0.4 2 –5.9 19.27 0.344 0.5
Factor to take into account conductor irregularities (From 0.83 8 –5.5 19.27 0.343 0.5
0.85 to 0.98)
3 –5.9 13.27 0.316 0.5
Factor to take into account conductor strands (From 0.74 0.74
9 –5.5 13.27 0.313 0.5
to 0.77)
4 5.5 25.27 0.303 0.5
10 5.9 25.27 0.305 0.5
5 5.5 19.27 0.343 0.5
The program performs an additional check to knowing if
there are no errors in the data of the conductors and shield 11 5.9 19.27 0.344 0.5
wires, and if there is no error, and additional data is added, for 6 5.5 13.27 0.313 0.5
example, these data are shown in Table 2. 12 5.9 13.27 0.316 0.5
The algorithm allows to change all these parameters, to
know what happens, for example, if the spacing between the
conductors is increased and compare the results.
The sag is chosen according to the weight of the conductors (see Figure 3). Table 3 shows the capacitive currents per active
and the length of the average span considered. When the ele- conductor.
ments of the admittance matrix that is initially formed by means In Figure 3, to facilitate the calculations and analysis, the main
of the potential coefficients due to Maxwell are calculated, then conductors are numbered from 1 to 6, while the sub conduc-
the average heights of the conductors that form the line from tors are numbered from 7 to 12. It can be seen that, although
its sags are calculated. the capacitive currents per active conductor are unequal to each
Once all the data has been entered, the program calculates the other, there is certain symmetry given by the configuration of
maximum operating voltage of the line which, in this example, the tower in reference to its Y axis. In the Table 3, can be seen
was 205.63 kV line to line. The critical or disruptive voltage per that the maximum difference, 13.53%, is between the capacitive
corona is 45.37% higher than the maximum operating voltage, currents of active conductors 2 and 11, with 0.344 A/km and 7
which is also much higher than the 12% recommended in [3]. and 4, with 0.303 A/km. All the values are beyond the critical
Once all the data has been entered, the program calculates the value (0.5 A RMS/km).
maximum operating voltage of the line which, in this example, Table 4 shows the abscissa and ordinates of the twelve active
was 205.63 kV line to line. The critical or disruptive voltage per conductors of the line, allowing to see in which active conductor
corona is 45.37% higher than the maximum operating voltage, the maximum and minimum electric field surface appear.
which is also much higher than the 12% recommended in [3]. Table 4 show the surface gradient of the critical electric field,
This result is due to the fact that the line has two conductors which does not depend on the location of the conductor in
per phase with a relatively high calibre. space, so that it can be known whether the calculated ones are
It shows the sectional section of the phase conductors of the greater or less. In this line, the calculate gradients are much
line under study, with mirror symmetry, in order to know how smaller compare with the critical value (24.832 kV RMS/cm),
the capacitive currents are distributed, in ampere per kilometre due to the use of multiple conductors.
20513305, 2022, 7, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/tje2.12155 by CAPES, Wiley Online Library on [08/05/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
LLAMO-LABORÍ AND SANTOS-FUENTEFRIA 729

TABLE 4 Surface electric field gradient per active conductor of the line TABLE 5 Capacitive currents per active conductor of the line when it
rains
Critical surface
Surface electric Surface electric electric field Critical
Conductor field gradient field gradient gradient Current capacitive
number (kV Peak/cm) (kV RMS/cm) (kV RMS/cm) Conductor Module current
number Abscissa (m) Ordered (m) (A RMS/km) (A RMS/km)
1 14.979 10.592 24.832
1 –5.9 25.27 0.305 0.4
7 14.902 10.537 24.832
2 16.892 11.945 24.832 7 –5.5 25.27 0.303 0.4
2 –5.9 19.27 0.344 0.4
8 16.834 11.904 24.832
8 –5.5 19.27 0.343 0.4
3 15.495 10.957 24.832
3 –5.9 13.27 0.316 0.4
9 15.391 10.883 24.832
4 14.902 10.537 24.832 9 –5.5 13.27 0.313 0.4
4 5.5 25.27 0.303 0.4
10 14.979 10.592 24.832
10 5.9 25.27 0.305 0.4
5 16.834 11.904 24.832
5 5.5 19.27 0.343 0.4
11 16.892 11.945 24.832
6 15.391 10.833 24.832 11 5.9 19.27 0.344 0.4
6 5.5 13.27 0.313 0.4
12 15.495 10.957 24.832
12 5.9 13.27 0.316 0.4

TABLE 6 Surface gradient of the electric field per active conductor of the
line when it rains

Critical surface
Surface electric Surface electric electric field
Conductor field gradient field gradient gradient
number (kV Peak/cm) (kV RMS/cm) (kV RMS/cm)

1 14.979 10.592 19.754


7 14.902 10.537 19.754
2 16.892 11.945 19.754
FIGURE 4 Sectional section of the phase conductors of the transmission
8 16.834 11.904 19.754
line
3 15.495 10.957 19.754
9 15.391 10.883 19.754
The corona losses are distributed in each active conductor
4 14.902 10.537 19.754
and their average per bundle with good weather conditions is
10 14.979 10.592 19.754
different (see Figure 4.). For the tower structure, with mirror
symmetry (ABC-ABC), the main conductors (1, 2, 3, 4, 5 and 5 16.834 11.904 19.754
6) have different corona losses among them; the losses have a 11 16.892 11.945 19.754
certain symmetry per circuit and the central phase has the high- 6 15.391 10.833 19.754
est losses, 52.88% higher than those of the phase at the highest 12 15.495 10.957 19.754
elevation and 38.26% higher than the one at the lowest eleva-
tion. Finally, the total losses of the line under good weather
conditions are 6.047 kW.
Tables 5 and 6 show, respectively, the surface gradients of by the conductors is such that no water droplets are formed
the electric field and the critical capacitive current, both with on the conductors due to dew. In this case, the average corona
rainfall. Note that both the critical electric field and the critical losses over the year are 6177 kW.
capacitive current decrease the specified 20%. An important aspect of the algorithm is that it allows the cal-
The corona losses in each active conductor and the average culation of corona losses taking into account the line unbalance.
ones per bundle when it rains maintain the same distribution, Table 7 shows the annual average corona losses for different
only the values change, which are higher per phase and total, phase arrangements of circuit II in reference to circuit I. For
42.78% and 50.28% respectively. the calculation without taking into account the unbalance, the
The algorithm allows calculating the average corona losses in Peterson formula was used, assuming a symmetrical line.
a year. It was assumed that it will rain on one third of the line, All results are close to those of the symmetrically trans-
that is, on 8 km, while on the other 16 km, there will be good posed line with a maximum difference of 10.01% below and
weather conditions. It is assumed that the temperature reached a minimum of 2.75% above.
20513305, 2022, 7, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/tje2.12155 by CAPES, Wiley Online Library on [08/05/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
730 LLAMO-LABORÍ AND SANTOS-FUENTEFRIA

TABLE 7 Influence of the unbalance of the double circuit line with two to now the effect of rain, the dew, the height of the line trace
conductors per phase at 220 kV, on the value of corona losses above sea level, its operating voltage, the frequency, the annual
Arrangement of average ambient temperature and the roughness of the sur-
the phases of face of the conductors. It was shown that the formulas used
circuit II with Corona effect to calculate corona losses give results generally higher than the
respect to circuit losses in kilo Differences in
real ones because they assume that the line has a symmetrical
I, Unbalance. Watt. percentage.
transposition of its conductors.
0.000% 6.720 ——
ABC-ABC 12.435% 6.047 –10.01
ACKNOWLEDGEMENTS
ABC-ACB 8.482 6.431 –4.30 The authors wish to thank the Technological University of
ABC-CBA 5.452 6.975 3.79 Havana Jose Antonio Echeverría (CUJAE), the Unión Electrica
ABC-CAB 1.955 6.905 2.75 (UNE) for funding the project. Also, the authors wish to thank
the professor Juan Almirall Mesa for its important criteria as
specialist and María Magdalena La Serna Gómez for helping us
with the English language revision of the final version of the
The largest difference with the symmetrically transposed article.
line (10.01%) occurred for the mirror symmetry, ABC ABC,
which gave the largest imbalance to the negative sequence CONFLICT OF INTEREST
with 12.431%. It can be stated that the value of the losses The authors declare that there is no conflict of interest that
due to corona effect, when the symmetrical line is assumed, is could be perceived as prejudicing the impartiality of the research
conservative. reported.
The variation trend is not uniform, because a double circuit
line, with two conductors per phase, has a matrix of potential DATA AVAILABILITY STATEMENT
coefficients of order twelve by twelve in which there are one The data presented in this study are available on request from
hundred and thirty-two mutual elements (132) that change their the corresponding author. The data are not publicly available
value in each case. due to privacy and sensitive nature of the data.
Corroborating the non-uniformity of the variation trend,
Table 1 shows that the phase arrangement giving the lowest ORCID
unbalance u, which gives an unbalance to the negative sequence, Héctor Silvio Llamo-Laborí https://orcid.org/0000-0002-4675-
1.955%, gives corona losses 2.75% higher than those of the 8189
assumed symmetrical line with zero unbalance. Ariel Santos-Fuentefria https://orcid.org/0000-0002-9131-
The advantage of this result is that it is possible to know the 5539
value of the average corona losses per phase and per circuit, the
line balance and the best direction of the changes that should REFERENCES
be made, for example, in the configuration of the conductor 1. IEEE Transmission and Distribution Committee: IEEE guide for con-
bundles to reduce the value of the losses or the asymmetry of ducting corona tests on hardware for overhead transmission lines and
the line. substations (IEEE Std. 1829–2017) (2017)
The differences in corona losses calculated with the algo- 2. Committee, D.: IEEE standard definitions of terms relating to corona and
field effects of overhead power lines. Vol. 1990 (1991)
rithm keep the same units, 6 kW, as the Peterson formula that
3. List, V., Pochop K.: Mechanical Design of Overhead Transmission Lines.
disregards the unbalance of the lines. Publishers of technical Literature, Prague (1963)
In the double circuit line, with more than one conductor 4. Sharma, S., Goel, K., Gupta, A., Kumar, H.: Corona effects on EHV AC
per phase, the tendency of variation of corona losses is not to transmission lines. Int. J. Sci. Res. Eng. Technol. 1(5), 160–164 (2012)
decrease when the unbalance decreases, but there is an arrange- 5. Yunpeng, L., Feng, H., Chen, L., Yongshuang, L., Jian, T., Shaoshuai, C.,
Daran, L., Sijia, C., Shilong, H.: Corona loss of the bundle conductors on
ment of the phases of circuit II in reference to circuit I, that
EHV/UHV AC power lines under sandy and dusty conditions in high-
gives higher losses than with zero unbalance. altitude areas. J. Electrostat. 107(619), 103476–103487 (2020)
6. Megala, V., Karpagam, R., Sathishkumar, G.K., Gopinath, B., Marish
Kumar, P., Deva Brindha, M.: Investigation on corona performance of
4 CONCLUSION conductors using fabricated indoor corona cage. Mater. Today: Proceed-
ings 44(2), 3652–3656 (2020). https://doi.org/10.1016/j.matpr.2020.10.
682
With the developed algorithm it is possible to calculating the 7. Chee, FP., Zainuddin, NS., Ha, HL., Dayou, J.: Analysis and characteri-
transmission lines’ corona losses. This calculation can made for zation of enhanced kinetic reaction on ozone generation using negative
each of their active conductors, considering their real unbalance corona discharge. J. Phys. Commun. 4(7), 1–12 (2020)
with any configuration, with single or bundled conductors and 8. He, W., Wan, B., Lan, L., Pei, C., Zhang, J., Chen, Y., Chen, X., Wen, X.:
Effect of altitude on the audible noise level of AC power lines. Energies
up to four circuits. It is possible to analyse the line unbalance
10(7), 1055–1064 (2017)
imposed by the type of tower, the number and disposition of 9. Abdulkareem, A., Oguntosin, V., Dare, O., Mutalub, AL.: The electricity
conductors in each bundle, the sag and the type of conduc- security in nigeria: Design and analysis of 750-kV mega grid. Int. J. Eng.
tors installed in the phases and the shield wires. It is capable Res. Technol. 13(9), 2219–29 (2020)
20513305, 2022, 7, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/tje2.12155 by CAPES, Wiley Online Library on [08/05/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
LLAMO-LABORÍ AND SANTOS-FUENTEFRIA 731

10. Furby, L., Slovic, P., Fischhoff, B., Gregory, R.: Public perceptions of 31. Momani, M.A.: Factors affecting corona power losses in Jordan power
electric power transmission lines. J. Environ. Psychol. 8(1), 19–43 (1988) grid. In: Proceedings In 3rd International Conference on Technological
11. Zhao, Z.B., Gan, Z.Y., Zhang, X.W., Cui, X., Wu, X.: Passive interfer- Advances in Electrical, Electronics and Computer Engineering, Beirut,
ence to radio station caused by UHV AC transmission line in shortwave Lebanon, pp. 283–288 (2015)
frequency. High Voltage Eng. 35(8), 1818–1823 (2009) 32. Kitta, I., Manjang, S., Rachmaniar, I., Maricar, F.: Tropical climate effects
12. Shu, Y., Chen, W.: Research and application of UHV power transmission on corona power losses on 275 kV transmission lines in the south sulawesi
in China. IET High Voltage 3(1), 1–13 (2018) system. Przeglad Elektrotechniczny 95(1), 197–201 (2019)
13. Gonen, T.: Electrical Power Transmission System Engineering: Analysis 33. Diachenko, A., Sidorov, K., Hussein, A., Kononov, Y.: Investigation of
and Design, 2nd edn., Wiley-Inter Science, Hoboken, NJ (2015) online corona losses as a function of operating voltage based on PMU
14. Al-Hamouz, Z.: Corona power loss versus ohm power loss in HVDC data. In: Proceedings In 16th Conference on Electrical Machines, Drives
transmission lines. In: Proceedings of the 1999 6th Annual IEEE Technical and Power Systems, Varna, Bulgaria, pp. 1–5 (2019)
Exchange Meeting, pp. 1–3. Dhahran, Saudi Arabia (1999) 34. Balametov, A.B., Halilov, E.D., Isayeva, T.M.: An adequate mathematical
15. He, G., Hu, Q., Shu, L., Jiang, X., Liu, Y., Wu, W., Li, Y., Peng, H.: Impact model of an ultrahigh-voltage overhead transmission line using synchro-
of icing severity on corona performance of glaze ice-covered conductor. nized phasor measurements. Iran. J. Sci. Technol.: Trans. Electr. Eng. 44(1),
IEEE Trans. Dielectr. Electr. Insul. 24(5), 2952–2959 (2017) 175–183 (2020)
16. Huang, S., Liu, Y., Chen, S., Zhou, G., Zhuang, W.: Corona onset charac- 35. Peterson, W. S.: Development of a corona loss formula. Trans. Am. Inst.
teristics of bundle conductors in UHV AC power lines at 2200 m altitude. Electr. Eng. 52, 62 (1933)
Energies 11(5), 1047–1060 (2018) 36. Ryan, H.J., Henline, H.H.: The hysteresis character of corona formation.
17. Omeje, C.O.: Corona loss minimization on high voltage transmission line Trans. Am. Inst. Electr. Eng. 43, 1118–1124 (1924)
network using bundled conductors. Int. J. Eng. Adv. Technol. 9 (3), 887– 37. Carroll, J.S, Rockwell, M.M.: Empirical method of calculating corona loss
891 (2020) from high-voltage transmission lines. Trans. Am. Inst. Electr. Eng. 56(5),
18. Cozzens, B.: Corona loss measurements for the design of transmission 558–65 (1937)
lines to operate at voltages between 220 kV and 330 kV. Trans. Am. Inst. 38. Carroll, J.S., Cozzens, B., Blakeslee, T.M.: Corona losses from conduc-
Electr. Eng. 52(1), 55–62 (1933) tors of 1.4-inch diameter. Trans. Am. Inst. Electr. Eng. 53(12), 1727–1733
19. Diachenko, A.D., Kononov, Y.G., Rybasova, O.S., Petrov, A.V.: Online (1934)
corona losses investigation during overcast in real 500 KV TLS based 39. Huang, S.L, Liu, Y.P.: The optimum method for determining the corona
on PMU data. In: 2nd International Youth Scientific and Technical onset voltage gradient of bundle conductors on UHV AC power line.
Conference on Relay Protection and Automation, Moscow, Russia (2019) J. Electr. Eng. Technol. 14, 1777–1780 (2019)
20. Yin, F., Farzaneh, M., Jiang, X.: Corona investigation of an energized con- 40. Rawlinson, E., King, P.H., Richardson, P.K.: Automatic corona-loss
ductor under various weather conditions. IEEE Trans. Dielectr. Electr. measuring equipment. Proc. Inst. Electr. Eng. 113(4), 705–709 (1966)
Insul. 24(1), 462–470 (2017) 41. Kudyan, H.M., Shih, C.H.: A nonlinear circuit model for transmission lines
21. Baran, I., Costea, M., Leonida, T.: Power losses on overhead lines in corona. IEEE Trans. Power Apparatus Syst. PAS-100(3), 1420–1430
under various loading regimes and weather conditions. In: Proceedings in (1981)
5th International Symposium on Electrical and Electronics Engineering, 42. Ghosh, S., Ahmed, N., Banerjee, S.: Impact of weather (Fog) on corona
Galati, Romania, pp. 1–6 (2017) loss and its geographical variation within eastern region. In: Proceedings In
22. Pan, W., Li, Y., Chen, X.: Calculation method of corona loss in EHV/UHV 20th National Power Systems Conference, Tiruchirappalli, India, pp. 1–6
system based on distributed parameter characteristic. IEEJ Trans. Electr. (2018)
Electron. Eng. 14(5), 730–734 (2019) 43. Gutman I., Solovyev Y., Ágústsson H., Mc Innes H.: Identification of hoar-
23. Youwei, L., Jihong, L., Bin, L.: Influence of air density and humidity on frost corona losses events based on advanced operational data analysis and
the corona performance of conductor. Power Syst. Technol. 14(4), 46–50 weather modelling. In: Németh, B. (eds) Proceedings of the 21st Interna-
(1990) tional Symposium on High Voltage Engineering. pp. 598, Springer, Berlin
24. Sollerkvist, F.J., Maxwell, A., Roudén, K., Ohnstad, T.M.: Evaluation, ver- (2020)
ification and operational supervision of corona losses in Sweden. IEEE 44. Balametov, A.B., Khalilov, E.D., Isaeva, T.M.: Modelling the EHV
Trans. Power Delivery 22(2), 1210–1217 (2007) transmission-line mode in light of actual corona losses. Russ. Electr. Eng.
25. Kolev, V.G., Sulakov, S.I.: The weather impact on the overhead line losses. 89 (2), 127–132 (2018)
In: Proceedings In 15th International Conference on Electrical Machines, 45. Cladé, J.J., Gary, C.H.: Predetermination of corona losses under rain: influ-
Drives and Power Systems, Sofia, Bulgaria, pp. 119–23 (2017) ence of rain intensity and utilization of a universal chart. IEEE Trans.
26. Abdel-Salam, M., Abdel-Aziz, E.Z.: A charge simulation based method for Power Apparatus Syst. PAS-89(6), 1179–1185 (1970)
calculating corona loss on AC power transmission lines. J. Phys. D: Appl. 46. Lü, F.C, You, S.H., Liu, Y.P., Wan, Q.F.: Analysis on corona loss measure-
Phys. 27(12), 2570–2579 (1994) ment of ultra high voltage AC single circuit test line in rain and snow
27. Cristina, S.: Influence analysis of the shielding grid parameters on right- weather conditions. High Voltage Eng. 37(9), 2089–2095 (2011)
of-way and on corona effects of an EHV 3-phase transmission line. Proc.
Inst. Electr. Eng. 131(7), 333–339 (1984)
28. Liu, Y., Huang, S., Liu, S., Liu, D., Huang, Z.: A helical charge simulation
based 3-D method for calculating AC stranded conductors corona loss in
the corona cage. (2017). https://doi.org/10.20944/preprints201711.0014. How to cite this article: Llamo-Laborí, H.S.,
v1. Accessed 10 May 2021 Santos-Fuentefria, A.: A new method to calculate
29. Peek, F.W.: The law of corona and the dielectric strength of air. In: Pro- corona losses for active conductors considering real
ceedings of the American Institute of Electrical Engineers, Chicago, USA
transmission line unbalance. J. Eng. 2022, 725–731
(1911)
30. Ogar, V.N., Bendor, S.A., James, A.E.: Analysis of corona effect on (2022). https://doi.org/10.1049/tje2.12155
transmission line. American J. Eng. Res. 6(7), 75–88 (2017)

You might also like