12.7kV SWER 2

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

1 2 3 4 5 6 7 8

NOTES :
1. POLES SHALL BE DRILLED, SCARFED AND DRESSED ON SITE. DRILLING AND SCARFING
A A
TO BE TREATED WITH APPROVED PRESERVATIVES.
2. ALL BOLTS PASSING THROUGH TIMBER ARE TO BE COATED WITH GRAPHITE GREASE.
3. CROSSARM SPECIFIED IS TO BE CUT IN HALF AND DRILLED ON SITE TO DIMENSIONS SHOWN.
4. THE DOLF ARM IS TO BE INSTALLED A MINIMUM OF 400mm BELOW THE LOWEST CONDUCTOR
10 9 8 7
ATTACHMENT POINT OR THE M20 ATTACHMENT BOLT ON A POLE TOP BRACKET TO ALLOW FOR

1200

1350
150

610
READY ACCESS FOR THE CONDUCTOR ATTACHMENTS AND FUSE OPERATION.

c c c c
c

50
B B
c

3 4 5

C
CONSTRUCTION ISSUE C

19 CLOUTS - 30x2.8mm, IRON, GALVANISED 50971 4

c
18 PLATE - NUMBER, EQUIPMENT IDENTIFICATION 506676 1
200
6 17 LUG - COMPRESSION (TO SUIT CONDUCTOR) 514053 2
18 19
16 15 14 13 16 WASHER - CONICAL, M16, STAINLESS STEEL 518082 146308 1

15 WASHER - FLAT, M16, GALVANISED 518081 177984 1


c
c
c

c
14 WASHER - SQUARE, 50x50x6mm, GALVANISED (18mm HOLE) 518081 H39257 1
5 c 600
13 BOLT & NUT - M16x140mm, HEX., GALVANISED 515466 H37506 1
c (SEE NOTE 4) 12 FUSE - ELEMENT, 11kV DROPOUT (REFER TO TS4200) 1
11 12 c
D 11 FUSEHOLDER - BASE & CARRIER, 12/24kV, EXPULSION DROPOUT, 150MVA, 8kA H84350 1 D
1
c

c 10 WASHER - CONICAL, M20, STAINLESS STEEL 518082 146316 1

9 WASHER - FLAT, M20, GALVANISED 518081 177986 1


c

c
514 2 8 WASHER - SQUARE, 75x75x6mm, GALVANISED (22mm HOLE) 518081 H39231 2

7 BOLT & NUT - M20, HEX., GALVANISED (LENGTH TO SUIT POLE) 515466 1
17
6 CROSSARM - 2700x100x100mm, HARDWOOD OR LAMINATED VENEER 513989 H23656 1
(CUT IN HALF)(SEE NOTE 3)
5 WASHER - CONICAL, M12, STAINLESS STEEL 518082 179601 1

4 WASHER - FLAT, M12, GALVANISED 518081 177982 1

3 BOLT & NUT - M12x130mm, HEX., GALVANISED 515466 46805 1


E 2 SCREW - COACH, M12x100mm, GALVANISED H40484 1 E
1 BRACE - CROSSARM, ANGLE, 740mm, GALVANISED 514383 99119 1

ALL DIMENSIONS IN MILLIMETRES UNLESS NOTED OTHERWISE. DO NOT SCALE. STOCK


ITEM DESCRIPTION DRG. No CODE QTY
AUTH’D by: STEPHEN CONNOR
LOCATION CHANGED. ALTERNATIVE POLE TOP
DO NOT MANUALLY AMEND

SCALE 1:20
STOCK CODES REMOVED.
A M E N D M E N T S

STANDARD CONSTRUCTION
ITEMS 11.14,15 AND 16 ADDED. CROSSARM

DRG NUMBER UPDATED

SHEET SIZE CHANGED.


DWN: PATRICIA RIOS

DESIGNED -
CAD DRAWING

ITEMS 14 AND 15 ADDED. CROSSARM

P.SUMNER

P.SUMNER

22/06/2006
28/09/95

TO 500,000 SERIES.
14/09/95

12.7kV SWER
CHKED: PHIL JONES

DRAWN P.S
INITIAL ISSUE

CHKED:

CHKED:

LOCATION CHANGED TO 1400mm.


BRACKET LOCATION CHANGED.

CHECKED - DOLF ARRANGEMENT


DESIGN APPROVED R.BREMMELL
2-260
DWN: P.S

DWN: P.S

145 NEWCASTLE RD WALLSEND, NSW 2287


AUTH’D by:

AUTH’D by:

DATE 31/05/95
F F
DATE:

TEL: 4951 9388 FAX: 4951 9389


DATE:

DATE:

PRJTRK No. -

A Business of PROJECT
Enerserve STD DRAWING No
520296 SHEET
01 AMD
04 SIZE
A3
0

C
B

04

EnergyAustralia NUMBER

1 2 3 4 5 6 7 8 '