Professional Documents
Culture Documents
Fire Alarm System CS3000 Reference v4 E7 08 1 E
Fire Alarm System CS3000 Reference v4 E7 08 1 E
Salwico CS3000
Reference manual
Ver. 4
çConsilium
The contents of this document are subject to revision without notice due to continued progress in
methodology, design and manufacturing. Consilium assumes no legal responsibility for any error
or damage resulting from the usage of this document.
Consilium Marine AB
P.O. Box 8763
SE-402 76 GÖTEBORG
SWEDEN
Tel: +46-31-710 77 00, Fax: +46-31-710 78 00
E-mail: cmab.got@consilium.se
Internet: www.consilium.se
Reference Manual Contents i
Salwico CS3000
Contents
About this manual .................................................................................................... iv
Chapter 2: Definitions
General definitions ...................................................................... 2-1
Normal status ............................................................................... 2-1
Cold start ................................................................................... 2-1
Warm start ................................................................................... 2-1
Service status............................................................................... 2-1
Disconnected status..................................................................... 2-1
Control unit definitions ............................................................... 2-1
Normal status ............................................................................... 2-1
Active fire alarm ........................................................................... 2-1
Section related definitions ......................................................... 2-1
Section unit .................................................................................. 2-1
Detector ................................................................................... 2-2
Chapter 4: Functions
Access levels................................................................................ 4-1
Fire alarms ................................................................................... 4-1
Acknowledge fire alarm................................................................ 4-1
Reset fire alarm............................................................................ 4-1
List fire alarms.............................................................................. 4-1
Printouts ................................................................................... 4-1
Faults ................................................................................... 4-1
Acknowledge fault ........................................................................ 4-1
Reset fault ................................................................................... 4-1
List faults ................................................................................... 4-1
Printouts ................................................................................... 4-1
Disconnections............................................................................. 4-2
Section on /off .............................................................................. 4-2
Electrical isolation of a section ..................................................... 4-2
Detectors on/off............................................................................ 4-2
Manual call point on/off ................................................................ 4-2
Alarm devices on/off..................................................................... 4-2
External control devices on/off ..................................................... 4-2
Alarm delay on/off ........................................................................ 4-2
List disconnections....................................................................... 4-2
Printouts ................................................................................... 4-3
Test and service functions ........................................................ 4-3
Lamp test ................................................................................... 4-3
Buzzer test ................................................................................... 4-3
Read section unit data ................................................................. 4-3
Connect a PC............................................................................... 4-3
Polling section units ..................................................................... 4-3
Miscellaneous functions ............................................................ 4-3
LED intensity (Dimmer) ................................................................ 4-3
Display program version .............................................................. 4-3
Set alarm data for smoke detectors ............................................. 4-3
Change number of section units .................................................. 4-3
Real time clock............................................................................. 4-3
Choice of access level ................................................................. 4-4
Change access level code ........................................................... 4-4
Logging of fire alarms and faults .................................................. 4-4
Reference Manual Contents iii
Salwico CS3000
Chapter 5: Operation
General about operations ......................................................... 5-1
Keying in information.................................................................... 5-1
Erroneous operations................................................................... 5-1
Non-executable orders ................................................................. 5-1
Fire alarm ...................................................................................... 5-2
Multiple alarms ............................................................................. 5-2
Acknowledge and mute fire alarms .............................................. 5-2
List fire alarms.............................................................................. 5-3
Reset fire alarm............................................................................ 5-3
Faults .............................................................................................. 5-4
Acknowledge and mute faults ...................................................... 5-4
List faults ...................................................................................... 5-4
Reset faults .................................................................................. 5-5
Disconnections............................................................................. 5-5
Disconnection of sections ............................................................ 5-5
Disconnection of detectors........................................................... 5-5
Disconnection of manual call point .............................................. 5-6
Disconnection of alarm devices ................................................... 5-6
Disconnection of external control devices ................................... 5-6
Disconnection of alarm delay....................................................... 5-6
Reconnections ............................................................................. 5-7
Listings and Printouts ................................................................. 5-7
Display unit ................................................................................... 5-7
Menus ............................................................................................. 5-7
Main menu ................................................................................... 5-8
Section menu ............................................................................. 5-10
Control menu.............................................................................. 5-12
Smoke detector .......................................................................... 5-13
List menu.................................................................................... 5-14
Chapter 3, System description, describes more in detail the function of fire alarm
panel, operating panel, loops, inputs and outputs. Last in this chapter there is also a
short description of the definition program. This program is downloaded to the system
before start and includes the complete definition of the system, how the system should
react to different events.
Chapter four, Functions, describes all functions available in the system separately.
Chapter five, Operations, describes how you as an operator can handle the system by
using the fire alarm and operating panels, and it also includes a description of all the
menus available in the system.
For a more detailed description of each function, we refer to CS3000 User’s Guide.
Reference Manual Chapter 1: System definition 1-1
Salwico CS3000
The fire alarm system may consist of one or several central units and control
units, which are inter-connected into a larger system. Conventional detectors
and sensors of closing type can be connected to the CS3000 system, in
addition to the analogue detectors.
The operator supervises and operates the system from one or more control
units, which normally are placed at convenient locations, separated from the
central unit.
The different central and control units communicates with each other on two
RS-422 channels, the system loop.
The central unit and its detectors communicate on two-wire loops. The
communication method is based on frequency modulation (FSK). Each
detector is connected to the loop via a specially developed integrated circuit,
the IDA, for supervision and communication. The detectors are normally
power supplied from the loop. The loop can be either a single-ended branch
line, a two-way closed loop or a two-way closed loop with branch lines.
Block diagram
1 2
1
1
2 4
Central unit
3
Inputs/Outputs for
example:
Control unit • Fire extinguishing
control
1 • Closing of fire doors
5 • Ventilation
Power supply • External fault signal
6 unit • Alarm bells and sirens
• Digital inputs
• Relay outputs
7
9
Loops
8
2. Printer
A printer is used for logging and registration of important system information.
A printer can be connected to the central unit and/or the control units.
Reference Manual Chapter 1: System definition 1-3
Salwico CS3000
3. Central unit
The central unit controls and supervises the CS3000 fire alarm system. The
central unit includes different PCB boards with specific tasks and a power
supply unit.
4. Inputs/Outputs
Various devices can be connected to the inputs and outputs:
• Fire extinguishing control. The CS3000 system can control the release of
fire extinguishing medium such as carbondioxide, water via a sprinkler
system, etc.
• Closing of fire doors. The fire door closing function can be programmed to
close doors only in the actual area of a fire.
• Ventilation. At a fire alarm the ventilation system can be totally or
partially stopped. The smoke may also be directed along a special smoke
evacuation route instead of the normal air way.
• External fault signal. When this signal is active the system acts in a pre-
programmed way.
• Alarm bells and sirens
• Digital inputs
• Relay outputs
5. External computer
All information in the fire alarm system can be transferred to an external
computer.
7. Optical mimic
An optical mimic is used to outline the different decks on a vessel. In the
mimic, LEDs indicate the fire alarm, thereby giving an immediate visual
location of the fire alarm.
8. Loops
Different types and numbers of fire detectors are connected to the loops. The
number of loops depends on the locations.
9. Interface
For connection of conventional digital fire alarm sections to the system.
Reference Manual Chapter 1: System definition 1-4
Salwico CS3000
Central unit
The central unit contains different types of PCBs, which are placed in one or
more 19" racks. The circuit boards of the system are designed in accordance
with the European Standard.
Each central unit contains one alarm processor board, a number of loop
processor boards and one relay board. The central unit may also, as an option,
include a communication board and one or more input/output boards.
Control unit
POWER ON....
DISCONNECTION..
FIRE (21) SEC 3 DETECTOR 43
FIRE 3 43 SEWING ROOM
1(1) TEST..........
ALARM TRANSFER.
SECTION DETECTOR EXTERNAL ALARM.
DELAY OFF...
SYSTEM FAULT..
F1 F2 F3 F4 ABNORMAL COND.
ALARM MUTE
ALARMS IN QUEUE 7 8 9 S SECTION EA
EXTERNAL
ALARM
FAULT
EXTERNAL
4 5 6 D DETECTOR EC CONTROL M MUTE
SECTION / DETECTOR
NOT RESET 0 ON OFF TIMER LIST
The CS3000 system is operated from a control unit that usually is placed at a
separate location from the central unit. The communication between the
control unit and the central unit is made via two RS-422 channels.
The control unit panel is the link between person and machine in the CS3000
system and it is designed for ease of use. The control unit panel is divided into
two halves, the fire alarm panel and the operating panel.
FIRE 3 43
SECTION DETECTOR
ALARM MUTE
ALARMS IN QUEUE
SECTION / DETECTOR
NOT RESET
The fire alarm panel is designed for greatest possible clarity. In addition to
keys to acknowledge and reset the fire alarm, it includes a numerical display
indicating alarming sections and detectors and LEDs to indicate multiple
alarms, with a possibility to list these on the numerical display. On the panel
there are also two indicators, one is lit if an external device is activated, for
instance fans are stopped, and the other is lit as long as their is a fire alarm in
the system that has not been reset.
Reference Manual Chapter 1: System definition 1-6
Salwico CS3000
Operating panel
POWER ON....
FIRE (21) SEC 3 DETECTOR 43 1(1) DISCONNECTION..
TEST..........
SEWING ROOM ALARM TRANSFER.
EXTERNAL ALARM.
DELAY OFF...
SYSTEM FAULT..
F1 F2 F3 F4 ABNORMAL COND.
7 8 9 S SECTION EA EXTERNAL
ALARM
FAULT
EXTERNAL
4 5 6 D DETECTOR EC CONTROL M MUTE
SMOKE ALARM
1 2 3 SD DETECTOR AD DELAY R RESET
The operating panel is used to supervise and operate the system and it includes
an alpha-numerical display, a key-pad, function keys, command keys, fault
keys, list keys and indicators. For security reasons and for quick function,
some important functions have been given separate keys. All other functions
are menu oriented. The alpha-numerical display is used as an interface
between the operator and the system, and it is used to inform and guide the
operator when using the different functions on the operating panel. The status
of the system is also displayed on the alphanumerical display.
The power unit is under continuous supervision and control by the central unit,
which controls voltages, currents and certain faults. Important status data are
indicated by LEDs on the power unit.
Reference Manual Chapter 1: System definition 1-7
Salwico CS3000
Each section unit is connected to the loop via a communication module, the
IDA, which also contains the main address of the unit. A total of 150 detectors
and manual call points can be connected per loop and a total of 190 loops can
be connected to the system.
Reference Manual Chapter 1: System definition 1-8
Salwico CS3000
Figure 1-3. Two different loops are shown in the example below.
CS3000
1
6
5
3
4
2 7
9 9 10
8
11 12 5
13 6
3 3
5
9 12
15
16
14
5. Combination detector
A smoke detector combined with a heat detector unit.
Reference Manual Chapter 1: System definition 1-9
Salwico CS3000
7. Branch line
A complete part of the loop, branching out from a point on the rest of the loop.
Detectors
The central unit automatically identifies which type of detector or other unit
that is connected to an address. The address is set, at the installation, with a
switch in each detector. The alarm levels are stored in each detector. When a
detector reaches alarm status, its IDA gives a priority signal to the central unit
and transfers actual alarm data. The central unit acknowledges the message.
Should the central unit not return an acknowledgement within a certain time,
the transmission will be repeated a certain number of times. If, however,
contact still is not established, which might depend on a fault in the loop
processor, the IDA of the detector will by itself start a procedure, which will
result in a general fire alarm in the central unit.
All detectors on the loops are supervised. Each detector is polled and checked
by a special test program to evaluate the status of each detector.
RS-232 communication
The CS3000 also includes two RS-232 channels. All the communication
parameters are set in a special program, the Definition program, before the
start of the system.
Reference Manual Chapter 2: Definitions 2-1
Salwico CS3000
Chapter 2: Definitions
General definitions
Normal status
At normal status the units have the same status as after an initialisation, except
that there are no alarms, faults or abnormal conditions for the units. The inputs
and the outputs have returned to normal conditions. The system is said to be in
normal status if it has not been put manually into any other status.
Cold start
At cold start the unit is initialised and it then returns to normal status, as is the
case for instance after power-on. The current status is thereafter collected and
all deviations from normal status are reported.
Warm start
At a warm start the software restarts, i.e. the units return to normal status but
fire alarms and faults still exist. All states different from normal status is
reported.
Service status
When the system is in service status access is given to additional service
functions.
Disconnected status
A disconnected unit is functionally disconnected from the system and it can
not generate any status changes.
Detector
Reference Manual Chapter 2: Definitions 2-2
Salwico CS3000
A section unit that is an automatic fire alarm detector. A manual call point is
not regarded as a detector.
Reference Manual Chapter 3: System description 3-1
Salwico CS3000
Each central unit contains an alarm processor board (LPK-2), that controls and
supervises all other PCBs in that central unit. The central unit also contains
control PCBs for the detector loops (SPK-2).
Basic functions
Cold start
A cold start is performed after the system definition is downloaded into the
system. Different actions will take place in different units in the system.
Unit Action
SPK A warm start is performed on all the section units on
the section(s) concerned. All information except fire
alarms and faults are erased. As a result all the
disconnections for the central unit disappear.
Central unit A warm start is performed on all the section(s) on the
actual central unit. A cold start is performed on the
sub-central and the main central. All information
except fire alarms and faults are erased. As a result all
disconnections for the cold starting central unit
disappear and the output status may temporarily return
to normal status.
Control unit A warm start is performed on all the central units. All
disconnections disappear in the whole system and the
output status may temporarily return to normal status.
Fire alarms and faults are displayed as new events in
the control unit.
Warm start
A warm start is performed for the unit and it passes the warm start on to its
sub-units.
Disconnections
Reference Manual Chapter 3: System description 3-2
Salwico CS3000
Functional disconnection
The functional disconnections are divided into three different levels and are
either manually/centrally initiated or locally initiated. Disconnections may
exist on all three levels simultaneously. A unit is regarded as disconnected if it
is disconnected on one level. Overlapping intervals of disconnected units on
the same level are not permitted. A disconnected unit will not generate fire
alarms, faults, abnormal conditions or any other status changes
Manual
A manual disconnected section unit will first get normal status and thereafter
disconnected status, i.e. all alarms and faults are cleared.
Local
A local disconnected section unit will get disconnected status immediately, the
fire alarms and faults are not cleared.
General on disconnections
A section unit can always be disconnected, regardless if it answers or not. If
the address(es) to be disconnected should not exist, a "missing unit" message is
shown on the display.
Fire alarm
Fire alarm always has the highest priority. A received fire alarm is
immediately shown on the display, all messages, faults and other activities on
the display are suppressed. The fire alarm is indicated both optically and
acoustically. The optical indication on the control unit keeps flashing until the
fire alarms have been acknowledged. The fire alarm shown in the display is
always the first received. The system is capable of handling up to 100 fire
alarms. A fire alarm can be both acknowledged and reset from any control
unit.
If there are to many fire alarms at the same time the indication on the detectors
may not be lit but all the fire alarms are always indicated on the central unit.
For each fire alarm the outputs of the central unit are activated according to the
programmed definitions. The outputs remain activated until all causes for
activation have been reset. Up to 15 fire alarms per section can be stored in the
LPK-2. If a section generates more than 15 fire alarms, all outputs with
conditions depending on that section are activated. One address may have
several fire alarms at the same time since each address and type may generate a
fire alarm.
Basic alarm
If an LPK-2 in a central unit should cease to function, a normal fire alarm
cannot be transmitted to the control units. Instead the system initiates a basic
alarm by activating alarm outputs no 1 - 3 on the ARK-2. The alarm outputs
must be manually reset with a switch on the ARK-2.
A basic alarm is as a central alarm if the section that has generated the alarm is
unknown or as a section alarm if the alarming unit is unknown.
Reference Manual Chapter 3: System description 3-4
Salwico CS3000
Fault indications
Faults are displayed if there are no active fire alarms in the system. When the
faults can not be displayed a manual listing is necessary, all faults can always
be acknowledged, reset and listed. The faults are stored in a cyclic list with
room for 400 fault messages.
Acknowledge fault
When the fault messages have been acknowledged one by one and the internal
buzzer is silenced, the fault output of the central unit is deactivated.
Reset fault
A fault indication can only be reset if the cause of the fault has disappeared,
the fault is acknowledged and the section unit responds. If the cause remains or
if the section unit does not respond, a message is displayed.
The fault indication has the second highest priority and a just received fault
message is immediately shown in the alpha-numerical displayed, if there are
no active fire alarms. Up to 400 faults can be stored in a fault list. The list is
cyclic.
Failure on loop processor board SPK-2 and control units ME will have the
same effects as described under “system with one central” previous in this
chapter.
Abnormal conditions
An abnormal condition is generated if something is not quite normal, but the
function is still retained. Abnormal conditions are automatically reset by the
unit that generated the indication. Up to 100 abnormal conditions can be stored
in an abnormal conditions list.
System definition
In the system definition three groups of parameters can be defined: physical
configuration, adjustment of certain functions and the functions of output and
input.
Physical configuration
By defining the number of control units, central units and sections the system
is able to give fault messages when something deviates from this definition.
Several parameters have to be define for the central units and the control units,
including a definition of which central units the control unit can operate on. A
control unit can also be defined to function as a passive display unit.
Adjusting functions
For the whole system the following adjusting functions can be defined:
The control unit is polled by the alarm processor board (LPK-2) in the main
central unit. The control unit is also updated with status changes in the system.
When a fire alarm exists in the system only the Fire alarm panel needs to be
used. There are only three keys on this panel ALARMS IN QUEUE, ALARM
MUTE and ALARM RESET. All other functions are controlled from the
operating panel where the most frequently used functions have separate keys.
All other functions are menu controlled.
Reference Manual Chapter 3: System description 3-7
Salwico CS3000
FIRE 6 13
SECTION DETECTOR
ALARM MUTE
ALARMS IN QUEUE
SECTION / DETECTOR
NOT RESET
The fire alarm panel is designed for greatest possible clarity. It includes a
numerical display indicating the section number and the detector address of the
alarming unit. There are three keys on the fire alarm panel, an
acknowledge/mute key, a reset key and a key to scroll through the fire alarms.
The LED’s indicate if there are more than one fire alarm in the system, if a fire
alarm could not be reset and if any external control is activated.
The fire alarm panel is activated when a fire alarm is detected in the system.
The optical fire alarm indicator FIRE starts flashing, and both the section
number and the detector address in alarm are shown on the numeric display. If
there is more than one fire alarm in the system the optical fire alarm indicator
ALARMS IN QUEUE is lit. All keys on the fire alarm panel are used for
handling fire alarms.
Numeric display
The numeric display shows the section number and detector address in alarm
(3 + 3 red digits).
Reference Manual Chapter 3: System description 3-8
Salwico CS3000
KEY FUNCTION
Other indicators
Operating panel
POWER ON....
Salwico CS3004 1993-11-13 DISCONNECTION..
TEST..........
10:11:23
ALARM TRANSFER.
EXTERNAL ALARM.
DELAY OFF...
SYSTEM FAULT..
F1 F2 F3 F4 ABNORMAL COND.
7 8 9 S SECTION EA EXTERNAL
ALARM
FAULT
EXTERNAL
4 5 6 D DETECTOR EC CONTROL M MUTE
SMOKE ALARM
1 2 3 SD DETECTOR AD DELAY R RESET
The control panel is used to supervise and operate the system. The most
frequent functions have keys of their own. All other functions are reached
through menus. The display is used to show general information to the
operator when operating the system, function keys lead texts, menus,
additional information about the section units, error messages and additional
information at fire alarm.
Reference Manual Chapter 3: System description 3-9
Salwico CS3000
Keyboard
The keyboard is divided into six areas: numerical keys, command keys,
operation keys, fault handling keys, list handling keys and function keys. The
corresponding text or error message is displayed on the alpha-numerical
display at a key touch.
Numerical keys
The numerical part of the keyboard contains the digits 0 - 9 and the keys ←
and ↵ . When a numerical key is pressed the corresponding digit is displayed if
it is allowed, otherwise an error code is displayed.
↵ Return key. The system returns to normal status, CS3000 CONTROL UNIT
is displayed.
← A correction key. Each time this key is pressed the last numeric input is
erased or the system returns to the previous menu.
Command keys
The command keys S, D, SD, EA, EC and AD are used to choose the units to
operate on.
Key Function
S Chooses a section to operate on. After the S-key is
pressed enter a section number.
D Chooses detectors to operate on. Before the D-key
is pressed enter a section number. The different
choices of detectors are single address, address
interval or no address at all, meaning all detectors
on the section.
SD Chooses smoke detectors to operate on. Otherwise
identical to D-key above.
EA Chooses an external alarm device to operate on.
EC Chooses an external control device to operate on.
AD Chooses the alarm delay function.
Key Function
M Acknowledges the fault shown in the display. Mutes
the fault buzzer. (Access level 2)
R Resets the fault shown on the alpha-numerical display.
(Access level 2)
Reference Manual Chapter 3: System description 3 - 10
Salwico CS3000
Operation keys
The operation keys are used to choose the operations to perform.
Key Function
ON Reconnects the displayed unit from the Disconnection
list.
OFF Disconnects units.
TIMER Disconnects units during a time interval.
The lists are scrolled up and down by using the two arrow keys ↑ and ↓ .
↑ Displays previous item in the list. The key LED is lit when there is a
previous item in the list.
↓ Displays next item in the list. The key LED is lit when there is a next
item in the list.
Function keys
The function keys, F1, F2, F3 and F4 below the alpha-numerical display are
used to choose functions from the menus and moreover to enter certain
characters with no keys of their own. Explanatory texts for the function keys
are shown on the display above each key.
Reference Manual Chapter 3: System description 3 - 11
Salwico CS3000
Alpha-numerical display
The alpha-numerical display has 4 x 40 characters and is equipped with
background light. The display is used as a complement to the fire alarm panel
at fire alarm, it displays fault and abnormal conditions and lead texts for the
function keys. It is also a general interface to the operator when operating the
system.
Optical indicators
Name Colour Function
POWER ON Green Is lit when the power is set on.
DISCONNECTION Yellow General disconnection
indicator.
TEST Yellow Is lit when the central unit is in
test mode.
ALARM TRANSFER Yellow Is lit when the dedicated fire
output is activated (steady
light) and is flashing when the
door is open, the fire output is
deactivated.
EXTERNAL ALARM Yellow Is lit when an external alarm is
disconnected (steady light) or
faulty (flashing).
DELAY OFF Yellow Is lit when the time delay is
deactivated.
SYSTEM FAULT Yellow Is lit when an error occurs in
the system program.
ABNORMAL COND Yellow Is lit when an abnormal
condition occurs.
Reference Manual Chapter 3: System description 3 - 12
Salwico CS3000
Buzzer
A buzzer starts sounding when a fire alarm or a fault is detected in the central
unit. It keep buzzing until the fire alarm or fault is muted. The buzzer will
resound each time the system detects a new fire alarm or fault.
Supplementary texts
A supplementary text can be attached to each section number and detector
address. The text is displayed whenever a fire alarm is detected. The text is
shown on line two for the first fire alarm and if there are more than one fire
alarm present in the system, on line four for the latest fire alarm. The text may
be up to 40 characters long.
Reference Manual Chapter 4: Functions 4-1
Salwico CS3000
Chapter 4: Functions
Access levels
The functions of the system are divided into three access levels, to prevent
unauthorised operation of the system. All functions are available up to and
including the current access level of the operator. To change to a higher access
level an access code is needed. The access codes can be changed at will.
Fire alarms
Acknowledge fire alarm
Press the key ALARM MUTE on the control unit to mute all general alarm
devices and the internal buzzer.
Printouts
The printouts of the lists active fire alarms and not resettable fire alarms is
activated from a menu in the list function.
Faults
Acknowledge fault
Press the fault key FM to acknowledge the fault and to mute the buzzer.
Reset fault
Press the fault key FR to reset the fault. The fault is not reset if the fault
conditions remain.
List faults
Press the LIST key to list the acknowledged faults.
Printouts
The faults/abnormal condition list can be printed out on a printer. Select
PRINTOUT from the LIST menu.
Abnormal conditions
Reference Manual Chapter 4: Functions 4-2
Salwico CS3000
Disconnections
Normal status of the system is with all functions "ON".
Section on/off
One or more whole sections can be logically disconnected, i.e. all the
connected detectors and manual call points are set off. A section can also be
disconnected for a certain time interval after which the detectors are
automatically reconnected again.
Detectors on/off
A single detector, a section of detectors and a sequence of detectors can be
disconnected and reconnected. A detector can also be disconnected for a
certain time interval, after which it is automatically reconnected again.
List disconnections
All the disconnections in the system can be listed.
Printouts
Reference Manual Chapter 4: Functions 4-3
Salwico CS3000
All lists can be printed out on a printer. Select PRINTOUT from the LIST
menu.
Buzzer test
Test of buzzer. It will sound for about 5 seconds.
Connect a PC
Supplementary text and definition data is downloaded to the control unit via a
connected PC.
Miscellaneous functions
LED intensity (Dimmer)
The intensity of the LEDs on the control unit can be adjusted, dimmed.
Choice of access level to check that the operator has access to the desired
function.
Chapter 5: Operation
To perform an operation the first choice is to select the unit to operate on.
Then the actual command is chosen. When selecting the unit the choice is
gradually narrowed, i.e. the choice goes from larger to smaller units.
Address
The numerical keys are used to key in a section unit address. There are three
valid intervals for section units but only one can be used at a time. The address
type is defined at the installation of the system.
A) 1 - 150
B) 1 - 99.x, x is equal to 0 or 1 (Note the point before the letter x.)
C) 1-99x, x is equal to 0 or 1
Number
The numerical keys are used to key in a section number, central unit or control
unit. The valid intervals are:
Time
The numerical keys are used to key in the time. A colon (:) is used as a
separator between hours, minutes and seconds. The colon is available on the
function key F1 when needed.
Date
The numerical keys are also used to key in the date. The day is specified by six
digits, two digits each for hour, minutes and seconds.
Erroneous operations
Each key touch is checked and if it is not valid an error message is displayed.
The cause or an explanation is given, when possible ,why that particular key
was not allowed.
Non-executable orders
If an order can not be executed a message about this is displayed together with
an explanation why the execution was interrupted.
Reference Manual Chapter 5: Operation 5-2
Salwico CS3000
Fire alarm
When a fire alarm is activated from a conventional loop the system will
display a section number in the section field and dash signs ‘---’ in the detector
field. The section numbers are in the interval 200-600.
A central alarm is generated by the system if two dash signs ‘---’, one in each
field, are displayed. The word FIRE CENTRAL and the central unit number
are at the same time shown in the display. The system has activated a fire
alarm at the same time as a hardware fault has occurred in a central unit.
All received alarms are stored in chronological order in the Fire alarm list All.
A total of 100 fire alarms can be stored in this list. All functions in the system
are available at a fire alarm.
Multiple alarms
If more fire alarms are received the LEDs ALARMS IN QUEUE are lit. The
first received fire alarm is shown on both the numerical indicators and on the
first and second line of the alpha-numerical display. The latest fire alarm is
displayed on the third and fourth line of the alpha-numeric display.
The alarms can be listed one by one in the alpha-numeric display. The total
number of fire alarms and the fire alarm in order are shown to the right on line
one. If no key is pressed for about 5 seconds the display returns to show the
first received fire alarm. The list is cyclic, i.e. when the last received fire alarm
has been listed, the next key touch will list the first fire alarm again.
Reference Manual Chapter 5: Operation 5-3
Salwico CS3000
By using the LIST key three different lists can be selected from the menu: All
Fire alarms, All not resettable fire alarms and Fire alarm history, i.e. all fire
alarms that have been reset. All lists can be printed out on a local printer.
If the reset was successful a message is displayed for about 5 seconds. After
this the next active fire alarm is displayed, if existing. Otherwise the system
returns to normal status, CS3000 CONTROL UNIT is displayed. If the alarm
could not be reset a message is displayed and the fire alarm is moved to the list
of not resettable fire alarms and the indication SECTION/DETECTOR NOT
RESET is lit.
The fire alarm reset can either be executed instantly when the ALARM
RESET key is pressed or the key must be pressed for two seconds before the
execution starts. The function of the ALARM RESET key is defined at the
installation in a special program, the Definition program.
The not-resettable fire alarms can be listed in two different ways, either by
using the ALARMS IN QUEUE key on the fire alarm panel or by using the
LIST key on the operating panel. The ALARMS IN QUEUE key can only list
the not resettable fire alarms if there are no active fire alarms present in the
system and if all faults are acknowledged. The LIST key can always be used
regardless of the system status. The fire alarms are shown on the first line of
the alpha-numeric display, one by one. They are then reset in the normal
manner.
Reference Manual Chapter 5: Operation 5-4
Salwico CS3000
Faults
POWER ON....
Salwico CS3004 1993-11-13 DISCONNECTION..
TEST..........
10:11:23
ALARM TRANSFER.
EXTERNAL ALARM.
DELAY OFF...
SYSTEM FAULT..
F1 F2 F3 F4 ABNORMAL COND.
7 8 9 S SECTION EA EXTERNAL
ALARM
FAULT
EXTERNAL
4 5 6 D DETECTOR EC CONTROL M MUTE
SMOKE ALARM
1 2 3 SD DETECTOR AD DELAY R RESET
The FAULT indicator is flashing and the internal buzzer is sounding. One or
more faults are detected in the system and the latest fault is displayed on the
alpha-numerical display. The first line displays the word FAULT and a fault
code followed by the section number, the detector address, and a fault
message. Supplementary text is displayed on line two, if provided. The fault is
not displayed if there is an active fire alarm in the system. The fault codes are
listed in Appendix A: Fault codes.
The faults are stored in a list in chronological order, the first received fault is
displayed first. A total of 400 faults can be stored in the list.
A new fault is put in a waiting list until an old fault is reset if the fault list is
full. The fault list can be printed out on a local printer.
Reference Manual Chapter 5: Operation 5-5
Salwico CS3000
Reset faults
(Access level 2)
A fault can only be reset if the cause has disappeared, the fault is
acknowledged and the unit is responding. The selected fault is shown on the
first and second line on the alphanumeric display. The system tries to reset the
fault when the R key is pressed and a message is shown. If the reset is
successful a message is shown and the next fault is displayed, if existing.
Otherwise the system returns to normal status, CS3000 CONTROL UNIT is
displayed. If the fault could not be reset a NOT RESET message is shown and
the fault remains displayed.
Disconnections
A disconnection can either be performed on a section or on a specific unit or
sequence of units. A disconnection can be permanent or temporarily, the
disconnetion will automatically be reconnected after the specified time interval
has elapsed. All the disconnections are to be found in the Disconnections list.
The DISCONNECTION LED is lit when the first disconnection is defined and
it remains lit until the last disconnection is reconnected.
Disconnection of sections
(Access level 1)
A whole section can be disconnected either permanently or for a certain time
interval. A permanent disconnection sets all the detectors and manual call
points off on the specified section, it remains disconnected until it is
reconnected from the Disconnections list. A disconnection for a certain time
interval reconnects the detectors automatically when the time interval has
elapsed.
Permanent disconnection
The procedure for a permanent disconnection is: press the S key first to select
a section and then enter a section number, thereafter press the OFF key to
disconnect the section.
Disconnection of detectors
(Access level 1)
When disconnecting detectors there is a free choice of a single address, a
sequence of addresses or all addresses. The disconnections can either affect all
types of detectors or only a specific type of detectors such as smoke detectors
or heat detectors. The disconnection can either be a permanent disconnection
or a disconnection for a certain time interval. A disconnection for a certain
time interval reconnects the detectors automatically when the time interval has
Reference Manual Chapter 5: Operation 5-6
Salwico CS3000
Reconnection
(Access level 1 or 2)
The permanently disconnected units can only be reconnected from the
Disconnections list. Select the appropriate disconnection and thereafter change
the status of the specified unit by pressing the ON key.
Press the LIST key to select the list function and thereafter select the
appropriate list from the List menu. All lists provided by the system can be
printed on a local printer from a sub-menu.
Menus
Functions that do not have separate keys can be reached via menus on the
alphanumeric display. The menus are presented on the fourth line, one line of
text at a time. The explanatory text is displayed above each key in each menu.
To choose a certain function, press the corresponding function key.
A menu is present when the text MENU is displayed above the F4 key. You
activate the menu by pressing the F4 key. Some menus consist of more than
one line that is indicated by the text MORE above the F4 key. To display the
first line of the menu again, press F4.
The menus differ depending on the chosen unit and the access level. The
menus are the Main menu, the Section menu, the Control menu, the Smoke
detector menu, and the List menu.
The different menus are listed below together with their access levels.
Reference Manual Chapter 5: Operation 5-8
Salwico CS3000
Main menu
The main menu is accessible when the system is in normal status.
Menu A
ACC. LEV. - Access level (F1)
This function changes the access level. You can only change the access level if
you enter the correct access code.
ACC.CODE:
CURRENT ACCESS LEVEL:3
The system displays the present access level and asks you to enter the four-
digit access level code for the desired level. Each keystroke is echoed in the
display with an asterisk (*). The system displays the new access level if the
access code is correct. If an invalid code should be keyed in the system
changes to access level 1.
ACC.LEVEL:
CURRENT ACCESS LEVEL:3
ENTER ACCESS LEVEL
The system displays the present access level and asks you to enter the access
level. Thereafter the system asks you to enter the new access code twice.
ACC.LEVEL: 2 ACC.CODE:
CURRENT ACC.LEVEL:3
ENTER THE NEW ACCESS CODE
Each keystroke is echoed on the display with an asterisk (*) and a successful
change confirmed on line three. If the code is not accepted the code is not
changed and a message is displayed.
Menu B
LAMP TEST - Test the LEDs (F1)
All indications and each segment on the display on the central unit are tested.
The indications will be lit for about 5 seconds.
LAMP INTENS. - Change LED intensity (F2)
Reference Manual Chapter 5: Operation 5-9
Salwico CS3000
This function sets the LEDs intensity for all indicators on the central unit. The
intensity level can be set to five different levels, represented by the numbers 1
- 5 where 5 is the strongest intensity. The intensity level is displayed to the
right on the first line on the alphanumerical display.
LAMP INTENS.
SELECT INTENSITY 1 - 5
Enter a digit between 1 and 5. The intensity is changed immediately after the
READY (F1) key is pressed.
BUZZER TEST.
Menu C
SET TIME - Change the time (F1)
This function sets the system clock.
SET TIME
CURR.DATE 1993-08-22 CURR.TIME 10:27:01
ENTER TIME HH:MM:SS
The system displays the present time and asks you to enter the new time. The
time should be given as hours:minutes:seconds on a 24-hour clock. The colon
(:) used as separator is provided on the function key F1 when needed. The time
is changed after the new setting is confirmed, press READY (F1).
SET DATE
CURR.DATE 1993-08-22 CURR.TIME 10:29:53
ENTER NEW DATE YYMMDD
The system displays the present date and asks you to enter the new date. The
date should be specified with six digits, two digits each for year, month and
day, in this order. Thereafter specify the day of week. The date is changed
after the new date is confirmed, press READY (F1).
Menu D
PROG. VER. - Display program information (F1)
This function displays for about 5 seconds the program name and the program
version number for the control unit, central unit (LPK) and sections (SPK).
LPP-F/S v.4.00
Enter the section number and thereafter press OFF. The section is electrically
isolated and all the sections defined on the section are also electrically isolated.
The section is reconnected from the Disconnections list.
Section menu
The section menu is accessible after a section is selected and a section number
is given.
Menu A
MAN. CALL PT. - Manual call point (F1)
Selection to operate on a manual call point (alarm push button). The system
responds by displaying MAN. CALL PT.
MENU F1 F2 F3 F4
Sub-menu A READ VALUE TEXT
The analogue values of a selected section unit are read and shown on the
display. The analogue values are displayed in decimal form on line three,
beginning with channel 0.
The analogue values depend on the type of section unit and the status of the
detector.
Menu B
FLASH ON - Activation of poll flash (F1)
This function tests the communication with the section units. The LEDs of
each section unit will flash at each poll. Poll flash remains on until it is set off.
The system asks you to enter the new number of section units, thereafter to
confirm the setting by pressing READY (F1). The new setting is confirmed by
ORDER DONE.
Reference Manual Chapter 5: Operation 5-12
Salwico CS3000
Menu C
POWER DATA - Power unit (F2)
The following sub-menu is accessible when a power unit has been selected.
MENU F1 F2 F3 F4
Sub-menu A EARTH + EARTH - DATA R.CHARGE
Control menu
The control menu is accessible when the external control device (EC) key is
pressed.
Menu A
SPRINKLER (F1)
This function operates on external controls defined as sprinklers. The system
responds by displaying SPRINKLER and asks you to define an external
control number or to select a function (OFF). When the sprinklers are
disconnected the system displays ORDER DONE.
DOOR (F2)
This function operates on external controls defined as fire door controls. The
system responds by displaying DOOR and asks you to define an external
control number or to select a function (OFF). When the doors are disconnected
the system displays ORDER DONE.
DAMPER (F3)
This function operates on external controls defined as fire damper controls.
The system responds by displaying DAMPER and asks you to define an
external control number or to select a function (OFF). When the dampers are
disconnected the system displays ORDER DONE.
Reference Manual Chapter 5: Operation 5-13
Salwico CS3000
Menu B
SMOKE HATCH (F1)
This function operates on external controls defined as smoke hatch controls.
The system responds by displaying SMK.HATCH and asks you to define an
external control number or to select a function (OFF). When the smoke
hatches are disconnected the system displays ORDER DONE.
FAN (F2)
This function operates on external controls defined as fan controls. The system
responds by displaying FAN and asks you to define an external control
number or to select a function (OFF). When the fans are disconnected the
system displays ORDER DONE.
Menu A
NORMAL SENS. - Change to normal sensitivity (F1)
Setting of normal sensitivity for the selected smoke detector. When the
sensitivity is set the system displays the text ORDER DONE on line three for
about 5 seconds. The sensitivity of the smoke detectors is normally set too
normal at start-up.
Menu B
DELAY OFF - Set the time delay to off (F1)
Setting of no time delay for the selected smoke detector. With this setting an
alarm is generated immediately when it is detected. When the time delay is
erased the system displays the text ORDER DONE for about 5 seconds.
List menu
The list menu can always be activated with the LIST key, regardless of the
status of the system.
Menu A
FIRE ALARM - Selection of fire alarm lists (F1)
The fire alarm function has a sub menu consisting of one line.
The ALL list includes all fire alarms: not acknowledged, not reset and not
resettable fire alarms.
FIRE SEC 1 SD 1
JOINERS WORKSHOP 4 STORE
ALARM 1 OF 6
PRINTOUT
The different fire alarms are distinguished with the following text to the right
on line three:
The Not Reset list only includes the not resettable fire alarms. The first fire
alarm is displayed first and the maximum number of fire alarms in both lists is
100. The lists can be printed out on a local printer, select PRINTOUT (F1)
from the sub-menu.
The list can be printed out on a local printer, select PRINTOUT (F1) from the
sub-menu.
This function lists all disconnected sections, detectors, section units, alarm
devices, external controls, and electrically isolated loops.
SEC 2 SD 2 - 4 OFF
PUMP ROOM 1, SB
DISCONNECTION 1 OF 10
PRINTOUT
Menu B
FIRE HISTORY (F1) - Fire history list
This function displays a list of all fire alarms that have been reset.
The maximum number of fire alarms is 100, if the list is full the oldest fire
alarm disappears. The list can be printed out on a local printer, select
PRINTOUT (F1) from the sub-menu.
The list can be printed out on a local printer, select PRINTOUT (F1) from the
sub-menu.
Menu C
SEC.UNIT - Section unit (F1)
The section unit list includes all status information about each section, section
unit and communication between the units.
The system displays for each section how many section units it expected to
find and how many it found. It also displays the number of disconnected units,
the SPK status byte and the estimated current consumption.
STATUS SECTION: 8
EXPECTED UNITS: 7 FOUND: 7
DISABLED: 0
SPK STATUS BYTE: 4 CURR. (M AMP): 0
INPUTS (F2)
The status information for each central unit and control unit input is displayed
one by one. The list can be printed out on local printer.
OUTPUTS(F3)
The status information for each central unit and control unit output is
displayed one by one. The list can be printed out on local printer.
Reference Manual Appendix A 1
Fault codes
Major computer failure Program execution has stopped. Contact our service department.
8 Additional section unit(s) * Wrong definition of number of Compare the installation with
section units. the drawings. Contact our
service department.
Section unit connections faulty. Connect the unit correctly.
21 Bad answer (Abnormal Bad communication with one or Exchange the section unit if the
condition) several section units, could be condition remains or returns. If
temporary. this fault is not temporary
contact our service department.
22 No answer Wrong type of section unit. Exchange to the correct section
unit.
The section unit has two Check the units.
addresses.
Hardware fault. Exchange the unit.
A fuse is blown. A secondary Exchange the fuse.
fault appears, code (83).
Cable break in loop or system Mend the cable. See Cable at
loop. A secondary fault appears, the end of this appendix.
code (121).
23 Wrong loop unit mark Section unit faulty. Exchange the section unit.
24 Wrong unit status Section unit faulty. Exchange the section unit.
Wrong software in CS3000. Change the software.
Wrong type of detector Install correct type of detector.
installed. Restart the system.
25 Unknown ID Communication error Reboot and retry. If this does
not solve the problem, contact
our service dept.
Software too old Update software
26 Bad loop comm. * The loop communication is bad. Test the loop. Measure the cable
(Abnormal condition) resistance. See Cable at the end
of this appendix.
27 Loop comm. stopped The loop communication is Contact our service department.
stopped by a section unit.
28 Loop trans. stopped Communication error on central Contact our service department.
unit level.
29 Communication error
Two section units with the same Check the section units.
address.
Faulty section unit. Exchange the section unit.
41 Booted The system is booting. Contact our service department.
42 Boot disabled Section unit is faulty. Exchange the section unit.
Address unit on a sub-loop is Test the sub-loop.
faulty.
Reference Manual Appendix A 3
Fault codes
43 Wrong address interval Overlapping address intervals. Set a valid address interval.
End-address of the interval is Set a valid address interval.
lower then the start-address.
44 Illegal address
Faulty section unit. Exchange the section unit.
Replace unit
89 No autoalarm Unable to use autoalarm
Optical smoke detector: Clean
90 Polluted detector Detector head is polluted.
the detector head according to
(Abnormal condition)
recommendations.
126 Short circuit on prim. Short circuit between the Attend to the problem.
Side positive and the negative
connector on the primary side.
127 Short circuit on sec. Short circuit between the Attend to the problem.
Side positive and the negative
connector on the secondary side.
141 Earth fault + Earth fault between the positive See Earth fault at the end of this
connector and earth. appendix.
142 Earth fault - Earth fault between the negative See Earth fault at the end of this
connector and earth. appendix.
143 High current Normal current exceeded Check power consumers
144 Earth fault Earth fault (either positive or Locate and fix the cause
negative)
145 Low voltage Too low system voltage from Test the rectifier and measure
the power unit the voltage. Contact our service
department.
147 Fire Prewarning The system has detected a Check the unit.
smoke value approaching the
alarm level.
148 Fault alarm transmitted Obsolete Obsolete
149 Fire brigade disconnection Industrial application only. Reconnect the connection.
Transfer to fire brigade
disconnected.
150 Timer Stuck The timer does not work Check the unit.
properly.
153 Emergency power failure The emergency power is Check the emergency power
missing
154 Secondary power failure All 115/230VAC power supplies Check the power supplies
are faulty
161 Door Open A door is still open one minute Check the door.
after the instruction to close it
was sent.
162 Door closed A door intended to be open is Open the door
closed
163 Open Door Subloop Cable break between module Mend the cable.
Break and open door sensor.
164 Door Closed Subloop Cable break between module Mend the cable.
Break and closed door sensor.
Reference Manual Appendix A 6
Fault codes
166 Damper /Door should Damper/door in wrong position. Check for obstruction.
have been opened
167 Damper /Door should Damper/door in wrong position. Check for obstruction.
have been closed
170 Sensor Fault The detector has a faulty sensor Replace the detector.
element.
NB This fault could be the result Check the location of the
of air blowing at the unit. detector and if need be, move it
to a less windy location.
171 Cable break from input 1 There is a cable break on input Check the cable.
1.
172 Cable break from input 1 There is a cable break on input Check the cable.
2.
173 Door Feedback There is no response from the Check the door-holder relay and
door-holding relay. its cable.
174 No power supply for loop No power feed from the pcb. DC/DC converter faulty.
175 Door in wrong position Door in wrong position. Check for obstruction.
176 Cable break positive side Check for a cable break on Mend the cable break.
positive lead.
A tripped short circuit isolator Check the short circuit isolators.
can cause this fault.
177 Cable break negative side Check for a cable break on Mend the cable break.
negative lead.
A tripped short circuit isolator Check the short circuit isolators.
can cause this fault.
178 Wrong type of loop unit Check the ID setting of the Set a correct value on the DIP-
found faulty unit. switch of the unit.
179 Unable to detect short Unable to detect short circuit. Exchange loop-PCB.
circuit
180 Valve Closed Valve closed. Check why it is closed.
181 Loop cable short circuit Short circuit on subloop. Check cable.
182 Cable break A cable break has been detected. Check corresponding cables.
183 Cable overload, current There is an overload in the Check if too many units are
limit reached cable. connected to the cable. Compare
with cable data.
184 Power fault The power supply is lost. Check power generation.
Reference Manual Appendix A 7
Fault codes
185 Loss of capacity to charge The battery charger is unable to Check the battery charger and
battery charge the battery. the battery.
186 External Fault Fault from input. Check cable and/or external
unit.
187 Double address on loop Check the offending units Set correct addresses for the
against drawings. units, with the DIP-switches.
Cable break
No section units are answering.
- The cable is broken before the first section unit if no answer is received on a
single fed loop.
- The cable is broken before the first section unit and after the last section unit
the if the loop is a double fed loop.
The easiest way to find a short circuit is to divide the cable in two halves,
locate the short-circuit on one of the halves. Divide this half of the cable again
into two halves. Continue to divide the cable into halves until you have found
the short-circuit.
Fuses
Check the fuses on the boards included in the system. The fuses are mounted
on the front panels on the following boards: ARK-2, GSK-2, INK-2, KPK-4,
LPK-2, RS232K-2, SPK-2 and UTK-2. The fuses to the IKK-4 are mounted on
the board itself.
* The central unit is not working properly. Indicator No. 1 (green) is not lit.