Professional Documents
Culture Documents
Consilium: Fire Alarm System
Consilium: Fire Alarm System
Consilium: Fire Alarm System
Salwico CS3000
User’s guide
Ver. 6
çConsilium
The contents of this document are subject to revision without notice due to continued progress in
methodology, design and manufacturing. Consilium assumes no legal responsibility for any error
or damage resulting from the usage of this document.
Consilium Marine AB
P.O. Box 8763
SE-402 76 GÖTEBORG
SWEDEN
Tel: +46-31-710 77 00, Fax: +46-31-710 78 00
E-mail: cmab.got@consilium.se
Internet: www.consilium.se
User’s Guide Contents i
CS3000
Contents
About this manual .................................................................................................... iv
Chapter 4: Disconnections
Disconnect zones ....................................................................... 4-2
Disconnect a whole zone permanently ....................................... 4-2
Disconnect a whole zone for a specified time interval ................ 4-3
Disconnect detectors .................................................................. 4-4
Disconnect all detectors in a zone .............................................. 4-4
Disconnect a certain detector in a zone ...................................... 4-5
Disconnect a sequence of detectors in a zone ........................... 4-6
Disconnect all detectors in a zone for a certain time................... 4-7
Disconnect a certain detector in a zone for a certain time .......... 4-8
Disconnect a sequence of detectors in a zone for a cert. time .. . 4-9
Disconnect a manual call point ............................................. 4-11
Disconnect a certain manual call point in a zone ....................... 4-11
Disconnect a certain manual call point for a certain time........... 4-12
Disconnect external alarm devices...................................... 4-13
Disconnect all external alarm devices ....................................... 4-13
Disconnect a certain external alarm device .............................. 4-14
Disconnect external control devices ................................... 4-15
Disconnect all external control devices ..................................... 4-15
User’s Guide Contents ii
CS3000
All CS3000 systems are custom designed including different numbers of control
units, display units, loops, zones, loop units, etc. This manual describes the
function of the control unit and the display unit MN3000, the latter is
described in a separate chapter at the end of the manual.
To help you to learn and work with the system efficiently, this manual is
organised by tasks, starting with a short description of the control unit panel
and some limitations of the system in the first chapter. The next chapters
describe a fire alarm, when there is a fault and disconnections. A disconnected
unit should be disconnected for a minimum of time since a disconnected unit is
not supervised by the system. All reconnections are made by using the
different lists in the system, refer to chapters Reconnection and Listings
Printouts.
There might be some deviations between the text shown in your display and
the text presented in this manual. Always follow the instructions on your
display, if there are major deviations we would most grateful if you would
report them to Consilium Marine.
User’s Guide Chapter 1: CS3000 Fire alarm system 1-1
CS3000
Control unit
All communication between the operator and the system is performed via the
front panel on the control unit, that has been designed for ease of use. If the
CS3000 system detects a fire, fault, abnormal condition or change in the
system status, this is displayed on the control unit panel. The operator can
control and check a number of functions in the system. To make it easier for
the operator to handle the functions, they are divided in to three levels. Each
level is protected by an access code that can easily be changed by the operator.
The following functions are available in the system:
− Disconnection of loops, zones, detectors, manual call points, loop units,
alarm devices, external controls.
− Electric isolation of a loop.
− Reconnection of all disconnected units.
− Display of all events present in the different lists in the system.
User’s Guide Chapter 1: CS3000 Fire alarm system 1-2
CS3000
− Change of system status, such as date, time, and number of loops connected
to the system and connection/disconnection of PC.
− Change of smoke detector settings, such as sensitivity and time delay.
− Display of the status of all loop units connected to the system.
− Test buzzer, LED’s, indicators and display.
ÇConsilium
The control unit panel is designed for ease of use. Therefore the panel is
divided into two halves, the fire alarm panel and the operating panel. The fire
alarm panel is activated when a fire alarm is detected in the system. The
operator controls and supervises the system by using the four-line display, the
keyboard and a few dedicated keys.
ÇConsilium
The Fire alarm panel is activated when a fire alarm is detected in the system.
The FIRE indicator is flashing and, the alarming zone number and detector
address are displayed on the numeric display.
Keys
ALARM MUTE This key is used to acknowledge the fire alarm and
mute the buzzers.
ALARM RESET This key is used to reset the fire alarm.
ALARMS IN QUEUE LEDs indicating multiple alarms with a possibility
to list these on the numerical display and on the
alphanumerical display.
Indicators
EXTERNAL CONTROL LED indicating that an external control output is
ACTIVATED active.
User’s Guide Chapter 1: CS3000 Fire alarm system 1-3
CS3000
Operating panel
The Operating panel is used for controlling the system and to display
additional information in case of a fire alarm. The alphanumerical display is
used as a complement to the numerical display on the Fire Alarm panel, as a
communication medium when operating the system, and to display guiding
texts for the function keys. Under normal conditions, when the central unit is
in normal status, the text CS3000 CONTROL UNIT is displayed together with
the date and time.
Keys
F1, F2, F3, F4 Function keys, used for choosing functions from
the menus in the display and for entering certain
characters with no keys of their own.
0-9 Numerical keys
← Correction key, the last keystroke is erased.
↵ Return key, the system returns to normal status,
CS3000 CONTROL UNIT is displayed.
S, D, SD, EA, Command keys used to choose the unit to operate
EC, AD on.
MUTE Fault handling key used to acknowledge faults and
to mute the buzzers.
RESET Fault handling key used to reset the faults.
ON, OFF, TIMER Operation keys used to choose the operation to
perform.
LIST, ⇑, ⇓ List handling keys, the LIST key is used to open
the list function. The arrow keys are used to scroll
through the lists.
Indicators
POWER ON Is lit when the power is on.
DISCONNECTION Is a general disconnection indicator.
TEST Is lit when the central unit is in test mode.
ZONE/DETECTOR Is lit when a reset of a fire alarm has been
NOT RESET attempted but failed.
User’s Guide Chapter 1: CS3000 Fire alarm system 1-4
CS3000
Authorization
The functions of the system are divided into three different access levels, each
level protected by an access code. The system is in access level 1 when the
door to the control unit is closed. To go to access level 2 or 3 the appropriate
access code for each level is entered. Access level 2 can also be reached by
opening the door.
All functions are described one by one, but for clarity the functions have been
grouped according to their functionality into different chapters. The access
code for each function is specified first in each description.
User's Guide Chapter 2: Fire Alarm 2-1
CS3000
ÇConsilium
A fire alarm is detected in the system. The zone number and detector address
in alarm is displayed on the fire alarm panel and in clear text on the
alphanumeric display on the operating panel. If dash signs are displayed in the
detector address field a fire alarm has been generated in a conventional loop,
see Fire alarm in a conventional loop. A special fire alarm, a central alarm, is
generated if dash signs are displayed in both the zone and detector fields, see
Central fire alarm.
All the information about the fire alarm is displayed on the first and second
line on the display. The zone number and the detector address are displayed on
the first line and additional information about the unit, if provided, is displayed
on the second line.
The fire alarms can be acknowledge and reset. All fire alarms are put in the All
list.
User's Guide Chapter 2: Fire Alarm 2-2
CS3000
ÇConsilium
A fire alarm is detected in a conventional loop. The system can only display
the zone numbers.
MENU
These fire alarms can be acknowledged, muted and reset in the same way as all
other fire alarms in the system.
ÇConsilium
The system has detected a fire alarm at the same time as it has detected a
hardware fault in the central unit. The system can not display the exact address
of the fire alarm it can only display the central unit number.
MENU
This fire alarm can be acknowledged, muted and reset in the same way as all
other fire alarms in the system.
User's Guide Chapter 2: Fire Alarm 2-3
CS3000
ÇConsilium
The address of the first fire alarm is displayed on the first line and additional
information about the alarming unit, if provided, is displayed on the second
line. The address of the latest fire alarm is displayed on the third line and
additional information about this unit, if provided, is displayed on the fourth
line. The text MENU on the fourth line disappears when there is more than one
fire alarm in the system, but the F4 key is still active.
Display next alarm
• Press ALARMS IN QUEUE.
The next fire alarm address is displayed both on the fire alarm panel and on the
alphanumerical display for a few seconds. The fire alarm is presented on the
two first lines on the display.
User's Guide Chapter 2: Fire Alarm 2-4
CS3000
ÇConsilium
Acknowledge and mute
• Press ALARM MUTE, to mute and acknowledge the fire alarms.
The FIRE indicator stops blinking and turns over to steady red. The function of the
audible fire alarm when the door is opened is defined at the initialisation of the
system. The internal buzzer is temporarily silenced. They are permanently silenced
when ALARM MUTE is pressed. The internal buzzer is sounding each time a new fire
alarm is generated.
The zone number and detector address of the first detected fire alarm is displayed on
the fire alarm panel and on the alphanumerical display on the operating panel.
The zone number and detector address is displayed on the first line and
additional information about the alarming unit is displayed on the second line.
If there are more than one unit in alarm the addresses of these alarms will not
be automatically displayed. You can display one at a time by pressing the
ALARMS IN QUEUE key repeatedly.
User's Guide Chapter 2: Fire Alarm 2-5
CS3000
ÇConsilium
You can only reset the displayed fire alarm one at a time.
Select fire alarm
• Press ALARMS IN QUEUE repeatedly to select the appropriate fire
alarm.
Reset fire alarm
• Press ALARM RESET to reset the fire alarm.
The system is trying to reset the fire alarm.
FIRE ZONE 6 DET 13 1(1)
CREW CABIN 754
EXECUTING ORDER...
MENU
The reason why the fire alarm is not reset is displayed on line three. The
indicator ZONE/DETECTOR NOT RESET on the fire alarm panel turns on.
The display returns to normal status and the text CS3000 CONTROL UNIT is
displayed. The fire alarm is now a not resettable fire alarm and it can be listed
in two different ways:
1. Use the ALARMS IN QUEUE key, if all fire alarms are muted and
reset, and all faults are muted.
2. Use the list function. Press the LIST key on the operating panel and
select the Fire Alarm - Not reset list.
Check the problem and deal with it. For more information see Fire alarms
that could not be reset.
User's Guide Chapter 2: Fire Alarm 2-6
CS3000
The fire alarm address is displayed both on the fire alarm panel and on the
alphanumerical display on the operating panel.
Reset fire alarm
• Press ALARM RESET.
The system is trying to reset the fire alarm.
The reason why the fire alarm is not reset is displayed on line three. Check the
problem and deal with it. The not resettable fire alarm is displayed again after
a few seconds.
User's Guide Chapter 2: Fire Alarm 2-7
CS3000
LIST KEY
• Press LIST.
• Press F1 (FIRE ALARM).
• Press F2, to select the not resettable list.
The first not resettable fire alarm is displayed.
When the FAULT indicator is flashing and the internal buzzer is sounding, this
means that one or more faults have been detected in the system. The first line
displays the word FAULT, followed by a fault code, a zone number, a detector
address and a fault message. Additional text, if provided, is displayed on line
two. The total number of faults is displayed on line 3.
However, if there is a fire alarm in the system the fault is not displayed. It is
then put in the Fault list instead.
The faults can, one at a time, be acknowledged/muted and reset by using the
MUTE and RESET keys situated in the Fault field. If there is a fire alarm in
the system the LIST key is used to display the fault in the display. The fault
codes are listed in Appendix A: Fault codes.
User's Guide Chapter 3: Fault indication 3-2
CS3000
Acknowledge faults
(Access level 2)
Reset faults
(Access level 2)
The faults can be reset from the Fault list or the automatic fault list displayed
when there are no fire alarms in the system. The fault is only reset if the cause
of the problem has disappeared.
• Press LIST to open the list function.
• Press F2 to select the Fault list.
FAULT (22) ZONE 2 DET 5 NO ANSWER
ENGINE WORKSHOP
FAULT 1 OF 1
PRINTOUT
The first fault is always displayed first. The list function can be interrupted at
any time by pressing the ↵ key.
• Select the appropriate fault by using the ↑ and ↓ keys. The LED on the
arrow keys respectively is lit if there are more faults to be listed.
• Press R in the FAULT field to reset the fault.
The system will then try to reset the fault.
The text in line three disappears after a few seconds. Check the problem and
deal with it. Then try to reset the fault again.
User's Guide Chapter 4: Disconnections 4-1
CS3000
Chapter 4: Disconnections
Different parts of the fire alarm system can be disconnected: loops, zones,
detectors, manual call points, loop units, alarm devices and external control
devices. All disconnections are put in the Disconnection list. The LED marked
DISCONNECTION on the control panel is lit when the first disconnection in
the system is made and it remains lit until all disconnections are reconnected.
A disconnection can be interrupted at any time, regardless of how it has been
defined.
WARNING! When a unit or a part of a loop is disconnected, the fire alarm
system can not supervise this area for any fire alarms. It is therefore very
important that as few loop units as possible are disconnected and for a
minimum of time.
User's Guide Chapter 4: Disconnect a whole zone 4-2
CS3000
Disconnect zones
A whole zone can either be disconnected permanently or for a defined time
interval.
ZONE 2 OFF
EXECUTING ORDER...
MENU
ZONE 2 TIMER
ENTER DISCONNECTION LENGTH
• Enter how long time the detectors should be disconnected. Enter the time as
HH:MM. Allowed time interval is 00:00 – 23:59. Please note the colon (:)
as separator between each item, present on the F1 key.
Disconnect the zone
• Press OFF.
Disconnect detectors
(Access level 2)
A detector, a group of detectors or all detectors in a zone can be disconnected.
The detectors can be specified by address or by address and category, such as
smoke or heat detectors. Manual call points are not affected. The disconnected
units can be permanently disconnected or for a certain time. You can manually
reconnect a detector that has been disconnected for a certain time by using the
Disconnection list.
ZONE 2 SD OFF
EXECUTING ORDER...
ZONE 2 SD 4 OFF
PUMP ROOM 1, SB
EXECUTING ORDER...
ZONE 2 SD 2 - 4 OFF
EXECUTING ORDER...
• Enter how long time the detectors should be disconnected. Enter the time as
HH:MM. Allowed time interval is 00:00 – 23:59. Please note the colon (:)
as separator between each item, present on the F1 key.
Disconnect the detectors
• Press OFF.
• Enter how long time the detector should be disconnected. Enter the time as
HH:MM. Allowed time interval is 00:00 – 23:59. Please note the colon (:)
as separator between each item, present on the F1 key.
Disconnect the detector
• Press OFF.
ZONE 2 DET 3 TIMER 02:15 OFF
EXECUTING ORDER ...
• Enter how long time the detectors should be disconnected. Enter the time as
HH:MM. Allowed time interval is 00:00 – 23:59. Please note the colon (:)
as separator between each item, present on the F1 key.
Disconnect the detectors
• Press OFF.
A message is displayed on line three for a few seconds if the system can not
disconnect the detectors. The system thereafter returns to the previous menu.
ENTER ADDRESS
ENTER ADDRESS
• Enter how long time the manual call point should be disconnected. Enter
the time as HH:MM. Allowed time interval is 00:00 – 23:59. Please note
the colon (:) as separator between each item, present on the F1 key.
Disconnect the manual call point
• Press OFF.
ZONE 3 MAN. CALL POINT 4 TIMER 02:15 OFF
EXECUTING ORDER...
EXT.ALARM
ENTER CENTRAL NUMBER
• Press F1 (READY).
Disconnect all external alarm devices
• Press OFF.
EXECUTING ORDER...
CENTRAL NUMBER
CENTRAL NUMBER 5
• Press F1 (READY).
EXT.ALARM
EXT.ALARM 3.52
EXECUTING ORDER...
• Press F1 (READY).
EXT. CONTROL
EXECUTING ORDER...
• Press F1 (READY).
EXT. CONTROL
ENTER EXT. CONTROL NO.OR SELECT FUNCTION
MENU
• Press OFF.
• Press F1 (READY).
EXT. CONTROL
Select a category
• Press F4 (MENU).
EXT. CONTROL
ENTER EXT. CONTROL NO.OR SELECT FUNCTION
SPRINKLER DOOR DAMPER MORE
The categories Sprinklers, Doors and Dampers can be selected in this menu.
Smoke hatches and Fans are selected in the next menu.
EXECUTING ORDER...
User's Guide Chapter 4: Disconnect one external control ... 4-18
CS3000
• Press F1 (READY).
EXTERNAL CONTROL
• Press F4 (MENU).
EXTERNAL CONTROL
ENTER EXT. CONTROL NO.OR SELECT FUNCTION
SPRINKLER DOOR DAMPER MORE
The categories Sprinklers, Doors and Dampers can be selected in this menu.
Smoke hatches and Fans are selected in the next menu.
Select a category
• Press the appropriate function key F1 – F3.
EXTERNAL CONTROL SPRINKLER
User's Guide Chapter 4: Disconnect one external control ... 4-19
CS3000
• Press OFF.
The external control devices are disconnected
When the external control is disconnected the text on line three is changed to
ORDER DONE. The LED marked DISCONNECTION is lit, if this is the first
active disconnection in the system. After a few seconds the display returns to
the previous menu.
The external control is not disconnected
A message is displayed on line three for a few seconds if the system can not
disconnect the external control. The system thereafter returns to the previous
menu.
• Press F2 (EL.ISOL.).
ELECTRIC ISOLATION LOOP NO:
ENTER LOOP NUMBER
Select a loop
• Enter a loop number, 1 – 200.
Disconnect a loop
• Press F1 (YES).
ELECTRIC ISOLATION LOOP NO.: 5
DISCONNECTION LOOP
Chapter 5: Reconnection
There is only one way to reconnect disconnected units, and that is to list the
units and thereafter change the status of the unit. A unit that is disconnected
for a certain time interval is automatically reconnected when that time interval
has elapsed, but it can also be manually reconnected from the Disconnections
list at any time. For more information see Chapter 7 Listings and Printouts,
List disconnections.
All disconnected units should be reconnected as soon as possible since the
CS3000 fire alarm system can not supervise a disconnected unit.
User's Guide Chapter 6: Deactivation/activation of alarm delay 6-1
CS3000
CENTRAL NUMBER
CENTRAL NUMBER 5
• Press F1 (READY).
Deactivate the alarm delay
• Press OFF.
ALARM DELAY
DEACTIVATING ALARM DELAY
The alarm delay is deactivated and the LED marked DELAY OFF is lit. If
there are no previous disconnections in the system the LED marked
DISCONNECTION is lit. After about five seconds the display returns to the
previous menu.
User's Guide Chapter 6: Deactivation/activation of alarm delay 6-2
CS3000
LIST
SELECT LIST
FIRE ALARM FAULT DISCONN. MORE
• Press F3 (DISCONN.).
Scroll the list up and down
• Use the arrow keys ( ↑ ↓ ) to scroll the list up and down. The LED on an
arrow key is lit if there are more disconnections to be listed.
DISCONNECTION 5 OF 10
PRINTOUT
• Press ON.
The alarm delay is activated and the LED marked DELAY OFF goes out.
After a few seconds the display returns to the previous menu.
User's Guide Chapter 7: Listings and Printouts 7-1
CS3000
• All fire alarms (not acknowledged, acknowledged, not reset, not resettable)
• Not resettable fire alarms
• Fire alarm history (reset)
• Faults
• Abnormal conditions
• Disconnections (all disconnected loop units)
• Loop units
• Inputs
• Outputs
Fire alarms
There are three different fire alarm lists in the system: the All list, the Not reset
list and the Fire hist. list. A fire alarm can be in four different states: Not
acknowledged/reset. acknowledged, reset and not resettable. The All list
includes all these fire alarms. The Not reset list includes all the fire alarms that
could not be reset. The Fire hist. list includes a history of all the reset fire
alarms.
LIST
SELECT LIST
FIRE ALARM FAULT DISCONN. MORE
• Press F1 (ALL).
User's Guide Chapter 7: Listings and Printouts 7-2
CS3000
The first detected fire alarm in the system is listed. All information about the
fire is displayed on the first line, additional text is displayed on the second
line. The total number of alarms and the number in order for the fire alarm is
displayed on line three.
The > sign is displayed above function key F3 if the first line is too long to be
displayed. Press F3 to display the remaining part of the line. The < sign
appears above function key F3 if the beginning of the line disappears, use this
key to display the beginning of the line again.
Scroll the list up and down
• Use the arrow keys ( ↑ ↓ ) to scroll the list up and down. The LED on an
arrow key is lit if there are more fire alarms to be listed.
TO MAKE A PRINTOUT
• Press F1 (PRINTOUT).
The list is printed out on the local printer and the system returns to normal
status and the text CS3000 CONTROL UNIT is displayed.
User's Guide Chapter 7: List not-resettable fire alarms 7-3
CS3000
LIST
SELECT LIST
FIRE ALARM FAULT DISCONN. MORE
SELECT LIST
ALL NOT RESET
The first not resettable fire alarm is listed. All information about the fire is
displayed on line one, additional text is displayed on line two. The total
number of alarms and the number in order for the fire alarm is displayed on
line three.
The > sign is displayed above function key F3 if the first line is too long to be
displayed. Press F3 to display the remaining part of the line. The < sign
appears above function key F3 if the beginning of the line disappears, use this
key to display the beginning of the line again.
Scroll the list up and down
• Use the arrow keys ( ↑ ↓ ) to scroll the list up and down. The LED on an
arrow key is lit if there are more not-resettable fire alarms to be listed.
TO MAKE A PRINTOUT
• Press F1 (PRINTOUT).
The list is printed out on the local printer. The system returns to normal status
and the text CS3000 CONTROL UNIT is displayed.
User's Guide Chapter 7: List fire alarm history 7-4
CS3000
LIST
SELECT LIST
FIRE ALARM FAULT DISCONN. MORE
• Press F4 (MORE).
LIST
SELECT LIST
ABNORMAL FIRE HIST. ZONE UNIT MORE
The first reset fire alarm is displayed first. All information about the fire is
displayed on line one and additional text is displayed on line two. The total
number of alarms and the number in order for the fire alarm is displayed on
line three.
The > sign is displayed above function key F3 if the first line is too long to be
displayed. Press F3 to display the remaining part of the line. The < sign
appears above function key F3 if the beginning of the line disappears, use this
key to display the beginning of the line again.
Scroll the list up and down
• Use the arrow keys ( ↑ ↓ ) to scroll the list up and down. The LED on an
arrow key is lit if there are more old fire alarms to be listed.
TO MAKE A PRINTOUT
• Press F1 (PRINTOUT).
The list is printed out on the local printer. The system returns to normal status
and the text CS3000 CONTROL UNIT is displayed.
User's Guide Chapter 7: List faults 7-5
CS3000
Faults
(Access level 1)
The Fault list includes all faults in the system and it can used both to list and
to reset the faults. The text (NOT MUTED) is displayed on line three to the
right if the fault is not acknowledged. A maximum of 400 faults can be
included in the list. When the list is full the faults are put on a waiting list until
a fault is reset. The complete list can also be printed out on a printer
The system is trying to reset the fault on the display when the Fault reset key
(R) is depressed.
Select the Fault list
• Press LIST.
LIST
SELECT LIST
FIRE ALARM FAULT DISCONN. MORE
• Press F2 (FAULT).
FAULT (22) ZONE 1 SD 10 NO ANSWER
CREW CABIN 762
FAULT 1 OF 3
PRINTOUT
The first fault is displayed first. All information about the fault is displayed on
line one and the additional text is displayed on line two. The total number of
faults and the number in order for the fault is displayed on line three. The text
(NOT MUTED) is displayed on line three to the right if the fault has not been
acknowledged.
The > sign is displayed above function key F3 if the first line is too long to be
displayed. Press F3 to display the remaining part of the line. The < sign
appears above function key F3 if the beginning of the line disappears, use this
key to display the beginning of the line again.
Scroll the list up and down
• Use the arrow keys ( ↑ ↓ ) to scroll the list up and down. The LED on an
arrow key is lit if there are more faults to be listed.
User's Guide Chapter 7: List faults 7-6
CS3000
TO RESET A FAULT
• Select the fault by using the arrow keys.
• Press R, in the FAULT field.
FAULT (22) ZONE 1 SD 10 NO ANSWER
CREW CABIN 762
EXECUTING ORDER...
After about five seconds the information about the total number of faults and
which fault in order that is displayed replace the text on line three. Check the
problem and deal with it, thereafter try to reset the fault again.
TO MAKE A PRINTOUT
• Press F1 (PRINTOUT).
The list is printed out on the local printer. The system returns to normal status
and the text CS3000 CONTROL UNIT is displayed.
User's Guide Chapter7: List abnormal conditions 7-7
CS3000
Abnormal conditions
(Access level 2)
The Abnormal list includes all abnormal conditions in the system. A maximum
of 100 abnormal conditions can be included in the list. If the list is full when a
new abnormal condition occurs this event will be rejected by the list. The
complete list can be printed out on a printer.
Select abnormal conditions
• Press LIST.
LIST
SELECT LIST
FIRE ALARM FAULT DISCONN. MORE
• Press F4 (MORE).
LIST
SELECT LIST
ABNORMAL FIRE HIST. ZONE UNIT MORE
• Press F2 (ABNORMAL).
ABNORMAL (21) ZONE 1 SD 1 BAD ANSWER
PANTRY AND MESS
ABNORMAL 1 OF 2
PRINTOUT
The latest abnormal condition is listed first. All the information about the
abnormal condition is displayed on line one and the additional text is displayed
on line two. The total number of registered abnormal conditions and the
number in order are displayed on line three.
The > sign is displayed above function key F3 if the first line is too long to be
displayed. Press F3 to display the remaining part of the line. The < sign
appears above function key F3 if the beginning of the line disappears, use this
key to display the beginning of the line again.
Scroll the list up and down
• Use the arrow keys ( ↑ ↓ ) to scroll the list up and down. The LED on an
arrow key is lit if there are more abnormal conditions to be listed.
TO MAKE A PRINTOUT
• Press F1 (PRINTOUT).
The list is printed out on the local printer. The system returns to normal status
and the text CS3000 CONTROL UNIT.
User’s Guide Chapter 7: List Disconnections 7-8
CS3000
Disconnections
(Access level 2)
The Disconnections list includes all disconnected units, such as loops, zones,
detectors, loop units, external alarm devices, external control, etc. This list is
used to display the disconnected units and to reconnect them.
A maximum of 250 disconnections can be included in this list. If the list is full
a new disconnection is put in a queue until an old disconnection disappears
from the list. The complete list can be printed out on a printer.
Select Disconnection list
• Press LIST.
LIST
SELECT A LIST
FIRE ALARM FAULT DISCONN. MORE
• Press F3 (DISCONN.).
ZONE 2 SD 2 - 4 OFF
PUMP ROOM 1, SB
DISCONNECTION 1 OF 10
PRINTOUT
The first disconnection is listed first. All the information about the
disconnection is displayed on line one and the additional text is displayed on
line two. The total number of disconnections and the number in order is
displayed on line three.
Scroll the list up and down
• Use the arrow keys ( ↑ ↓ ) to scroll the list up and down. The LED on an
arrow key is lit if there are more disconnections to be listed.
RECONNECTION
• Select the appropriate disconnection by using the arrow keys.
• Press ON.
ZONE 2 SD 2 - 4
EXECUTING ORDER...
SELECT A LIST
FIRE ALARM FAULT DISCONN. MORE
SELECT A LIST
LOOP UNIT INPUT OUTPUT MORE
Enter loop
• Enter a loop number.
LIST UNIT DATA IN LOOP 8
ENTER VALUE OR READY
READY
• Press F1 (READY).
LIST UNIT DATA IN LOOP 8
ENTER VALUE OR READY
DATA SCI STATUS
NOTE. Do not touch any key on the panel, except F1 (PRINTOUT) if you
want to have a printout. The system is not able to make this printout if you
have touched another key. If you have, return to the previous key and open this
menu again.
User’s Guide Chapter 7: List loop unit status 7-10
CS3000
• Press F1 (PRINTOUT).
The following information is printed out for each address: loop number, zone
number, address and type of loop unit, analogue values for the four channels
and, if appropriate, pollution in percent, sensitivity and time delay.
The analogue values depend on the type of loop unit and the status of the
detector. Use the table below to determine the status of each unit. The
sensitivity is either NORMAL or HIGH, and a clean detector is equal to 0%
and a dirty detector is equal to 100%, a fault is generated.
Display next unit
• Scroll the lists up and down with the arrow keys ( ↑ ↓ ).
*
The normal value depends on the environment. The system indicates on the display when there is a fault
on a detector.
User’s Guide Chapter 7: List loop unit status 7-11
CS3000
2 Sub.L >15
OA-130 16 0 Smoke 20-100 170 6
1 Heat 90 ± 5% 178 6
at 25°C
2 Sub.L
>15
RDJ-2 8 0 Smoke 21 - 45 96 4
RDJ-2T 10 0 Smoke 21 - 45 96 4
1 Heat 90 ± 5% 178 6
at 25°C
RDO-2 14 0 Smoke 40 ± 10 102 6
SID-38 4 0 Smoke 10 - 41 85 6
SID-38T 6 0 Smoke 10 - 41 85 6
1 Heat 90 ± 5% 178 6
at 25°C
TDT-2 18 1 Heat 90 ± 5% 178 6
at 25°C
TDT-2/RoR 19 1 Heat 90 ± 5% (223) 6
at 25°C
TDT-2K 20 1 Heat 90 ± 5% 178 6
at 25°C
TDT-2K/RoR 21 1 Heat 90 ± 5% (223) 6
at 25°C
If you want to connect a unit that you can not find in this table, please contact
our service department.
NB! The value within brackets indicates the maximum alarm level for rate of
rise detectors. The detector may generate a fire alarm before it reaches the
maximum alarm level if the temperature rise is to fast. The fire alarm
condition is generated by signal processed data.
User’s Guide Chapter 7: List loop unit status 7-12
CS3000
Address units
Address units make conventional digital detectors and other digital signals
addressable and compatible with the CS3000 system. The type of connected
device is set with the ID switch, see table below.
Analogue values for address units
The loop number is displayed on line one. The second line displays the
expected numbers of loop units in the selected loop, including built-in short
circuit isolators, and how many units the system found. The third line displays
how many units that are disconnected in the selected loop. The fourth line
displays the status of the SPK in decimal value and the estimated current
consumption for the loop.
The different status values of the SPK are listed below with their binary
values. You have to convert the decimal value to a binary value, where bit 0 is
the least significant bit (LSB) and thereafter use the list below to determine the
SPK status.
SPK status:
Bit
User’s Guide Chapter 7: List loop unit status 7-14
CS3000
0: 0 Double-fed loop
1 Single-fed loop (side 1)
1: 0 No time delay for smoke detectors
1 Time delay for smoke detectors
2: 0 Differential detectors are not allowed
1 Differential detectors allowed
3: 0 Normal sensitivity for smoke detectors
1 High sensitivity for smoke detectors
4: 0 Marine application
1 Industrial application
5: 0 Prim alarm allowed
1 Prim alarm not allowed
6: 0 Abnormal condition caused by dirty detector
1 Fault caused by dirty detector
7: 0 No pre-alarm
1 Pre-alarm
User's Guide Chapter 7: List input status 7 - 15
CS3000
Input status
(Access level 2)
This list includes the status of all inputs. The list can also be printed out on a
printer.
Select Input list
• Press LIST.
LIST
SELECT LIST
FIRE ALARM FAULT DISCONN. MORE
• Press F2 (INPUT).
INPUT 2 ACTIVE
INPUT 2 OF 5
PRINTOUT
The first input is listed. The status of the input is displayed on line one and the
additional text is displayed on line two. The total number of inputs and the
number in order are displayed on line three.
Scroll the list up and down
• Use the arrow keys ( ↑ ↓ ) to scroll the list up and down. The LED on an
arrow key is lit if there are more inputs to be listed.
TO MAKE A PRINTOUT
• Press F1 (PRINTOUT).
The list is printed out on the local printer. The system returns to normal status
and the text CS3000 CONTROL UNIT is displayed.
User's Guide Chapter 7: List output status 7-16
CS3000
Output status
(Access level 2)
This list includes the status of all outputs. The list can also be printed out on a
printer.
Select Output list
• Press LIST.
LIST
SELECT LIST
FIRE ALARM FAULT DISCONN. MORE
• Press F3 (OUTPUT).
The first output is listed. The status of the output is displayed on line one and
the additional text is displayed on line two. The total number of outputs and
the number in order are displayed on line three.
• Press F1 (ACC.LEV.).
ACC.CODE:
CURRENT ACCESS LEVEL: 1
• Press F2 (CHA.CODE).
ACC.LEVEL::
CURRENT ACCESS LEVEL: 1
ENTER ACCESS LEVEL
ACC.LEVEL:2 ACC.CODE:
CURRENT ACCESS LEVEL: 1
ENTER THE NEW ACCESS CODE
ACC.LEVEL:2 ACC.CODE:****
CURRENT ACCESS LEVEL: 1
ENTER THE NEW ACCESS CODE AGAIN
Set date
(Access level 2)
The system date can be changed with this function. The date must be entered
on the form YYMMDD.
Select date function
• Press F4 (MENU) repeatedly until SET DATE is displayed on line four.
Set time
(Access level 2)
The system clock is set with this function. The time must be entered as hours:
minutes:seconds on a 24-hour clock. The colon is used as a separator between
each item. The colon is present on function key F1 when needed.
Select time function
• Press F4 (MENU) repeatedly until SET TIME is displayed on line four.
Set time
• Press F1 (SET TIME).
SET TIME
CURR.DATE: 2002-08-02 CURR.TIME 15:10:50
ENTER NEW TIME HH:MM:SS
• Press F3 (RESOUND).
RESOUND
SOUNDING DEVICE ACTIVATED
The FIRE indicator starts flashing and the external alarm device is sounding
until it is muted. After about 5 seconds the display returns to normal status and
the text CS3000 CONTROL UNIT is displayed.
User's Guide Chapter 8: Set lamp intensity (Dimmer) 8-6
CS3000
LAMP INTENS
SELECT INTENSITY 1 - 5
READY
Change intensity
• Enter a number between 1 and 5.
• Press F1 (READY).
The intensity of the LEDs is immediately changed and the text SENSITIVITY
SET is displayed on the third line.
If the intensity level still is not satisfactory enter a new digit.
After a few seconds the system returns to normal status and the text CS3000
CONTROL UNIT is displayed.
User's Guide Chapter 8: Change number of loop units 8-7
CS3000
ZONE
ENTER ZONE NUMBER
ZONE 13
ENTER ZONE NUMBER OR SELECT FUNCTION
FLASH ON FLASH OFF NO.OF UNITS MORE
Connect a PC
(Access level 3)
Definition data and supplementary texts are downloaded via a connected PC to
the system. The system is ready to receive data after the Connect PC function
is activated.
Note. The system is ready to receive data when the Connect PC function is
active but it can not detect if the PC is connected or not.
Select connect PC
• Press F4 (MENU) repeatedly until CONN. PC is displayed on line four.
CENTRAL NUMBER
ENTER CENTRAL NUMBER
CENTRAL NUMBER 5
ENTER CENTRAL NUMBER
READY
• Press F1 (READY).
EXECUTING DATA...
The system is now ready to receive data from the connected PC. A few
seconds after the last key is pressed or data sent, the system returns to normal
status.
User's Guide Chapter 9: Adjustments of detectors 9-1
CS3000
ZONE 9 FLASH ON
EXECUTING ORDER...
ZONE
Select an address...
• Enter an address.
or specify a smoke detector interval.
• Enter a start address.
• Press F3 (–).
• Enter the last address in the sequence.
Select function
• Press MENU.
SET HIGH SENSITIVITY
• Press F2 (HIGH SENS.).
The > sign is displayed above function key F3 if the first line is too long to be
displayed. Press F3 to display the remaining part of the line. The < sign
appears above function key F3 if the beginning of the line disappears, use this
key to display the beginning of the line again.
The sensitivity is set to high
When the sensitivity is set to high the system displays the text ORDER DONE
on line three. After a few seconds the system returns to the zone menu.
The sensitivity remains set to normal
The system displays a fault message if the system can not set the sensitivity
too high. After a few seconds the system returns to the zone menu.
User's Guide Chapter 9: Adjustments of detectors 9-3
CS3000
EXECUTING ORDER...
ZONE
Select an address...
• Enter a zone number in the interval 1 – 999.
...or specify a smoke detector...
• Press SD.
ZONE 4 SD
ENTER ADDRESS OR SELECT FUNCTION
MENU
• Enter an address.
...or specify an interval of smoke detectors
• Enter a start address.
• Press F3 ( - ).
• Enter an end address.
TIME DELAY
• Press F4 (MORE) repeatedly until DELAY ON is displayed on line four.
• Press F2 (DELAY ON).
ZONE 4 SD 6 DELAY ON
EXECUTING ORDER...
The > sign is displayed above function key F3 if the first line is too long to be
displayed. Press F3 to display the remaining part of the line. The < sign
appears above function key F3 if the beginning of the line disappears, use this
key to display the beginning of the line again.
The time delay is set on
When the time delay is to on the text ORDER DONE is displayed on line
three. After a few seconds the system returns to the zone menu.
The time delay is still off
If the system can not set the time delay to on, the system displays a fault
message. After a few seconds the system returns to the zone menu.
User's Guide Chapter 9: Adjustments of detectors 9-5
CS3000
NO TIME DELAY
• Press F4 (MORE), repeatedly until DELAY OFF is displayed on line four.
• Press F1 (DELAY OFF).
ZONE 4 SD 6 DELAY OFF
EXECUTING ORDER...
• Press F1 (PROG.VER.).
PROG.VER.
MEP FG/S 6.00
CENTRAL LOOP
The system displays the program version for the control unit program. After
about five seconds the system returns to normal status, the text CS3000
CONTROL UNIT is displayed.
SELECT CENTRAL
• Press F1 (CENTRAL).
CENTRAL NUMBER
ENTER CENTRAL NUMBER
READY
The system displays the program version for the central unit (LPK) program.
After about five seconds the system returns to normal status, the text CS3000
CONTROL UNIT is displayed.
User's Guide Chapter 10: System information 10-2
CS3000
SELECT LOOP
• Press F1 (LOOP).
LOOP
The system displays the program version for the SPK program. After about
five seconds the system returns to normal status, the text CS3000 CONTROL
UNIT is displayed.
A fault message is displayed if the system can not present the required
information and after about five seconds the system returns to normal status.
User's Guide Chapter 10: System information 10-3
CS3000
ZONE
ZONE 9
The analogue values depend on the type of loop unit and the status of the
detector. Use the table below to determine the status of each unit.
User's Guide Chapter 10: System information 10-4
CS3000
*
The normal value depends on the environment. The system indicates on the display when there is a fault
on a detector.
User's Guide Chapter 10: System information 10-5
CS3000
SID-38 4 0 Smoke 10 - 41 85 6
SID-38T 6 0 Smoke 10 - 41 85 6
1 Heat 90 ± 5% 178 6
at 25°C
TDT-2 18 1 Heat 90 ± 5% 178 6
at 25°C
TDT-2/RoR 19 1 Heat 90 ± 5% (223) 6
at 25°C
TDT-2K 20 1 Heat 90 ± 5% 178 6
at 25°C
TDT-2K/RoR 21 1 Heat 90 ± 5% (223) 6
at 25°C
If you want to connect a unit that you can not find in this table, please contact
our service department.
NB! The value within brackets indicates the maximum alarm level for rate of
rise detectors. The detector may generate a fire alarm before it reaches the
maximum alarm level if the temperature rise is to fast. The fire alarm
condition is generated by signal processed data.
User's Guide Chapter 10: System information 10-6
CS3000
Address units
Address units make conventional digital detectors and other digital signals
addressable and compatible with the CS3000 system. The type of connected
device is set with the ID switch, see table below.
Analogue values for address units
ZONE
ENTER ZONE NUMBER
MENU
ENTER ADDRESS
MENU
• Press F4 (MENU).
ZONE 9 POWER UNIT 1
Buzzer test
(Access level 1)
This function is used to test the buzzer. The buzzer will sound for about 5
seconds.
• Press F4 (MENU) repeatedly until BUZZER is displayed on line four.
• Press F3 (BUZZER).
BUZZER TEST
BUZZER TEST ACTIVATED
The buzzer beeps a few times. Thereafter the system returns to normal status,
the text CS3000 CONTROL UNIT is displayed.
User's Guide Chapter 11: Test 11-3
CS3000
ZONE
ENTER ZONE NUMBER
MENU
ENTER ADDRESS
MENU
• Press F4 (MENU).
FIRE ALARM
On line List
More alarms CONSILIUM MARINE List
SALWICO CS3004
1993-11-13
15:10:32
10:11:23
Local mute
Lamp test
ÇConsilium
When the MN3000 panel is activated by a fire alarm the first fire alarm is
shown in the display and the local buzzer is sounding. The first two lines in the
display are equal to the first line in the display on the operating panel, and the
third and fourth lines are equal to the second line on the display on the
operating panel. The text on the MN3000 display changes at the same time that
the text on the first two lines on the operating panel display changes. The
MORE ALARMS indicator is lit when more than one fire alarm is detected in
the fire alarm system. The user may at any time display the other fire alarms in
the system by using the two LIST keys.
The user may mute the local buzzer by activating the LOCAL MUTE key all
the other audible devices are not effected.
Keys
Δ LIST The previous fire alarm is shown in the display.
∇ LIST The next fire alarm is shown in the display.
LOCAL MUTE The local buzzer is muted but no other audible
device is effected.
LAMP TEST All indicators and all segments in the display are lit
for a few seconds.
Indicators
ON LINE Is lit when the power is on.
MORE ALARMS LED indicating multiple fire alarms.
User's Guide Chapter 13: Maintenance 13-1
CS3000
Maintenance
It is however recommended to test the loops units such as smoke, heat or flame
detectors and manual call points once every 9-12 months.
The different outputs should also be tested at the same time if possible but in
order not to disturb the crew or passenger too much we recommend to choose
the time for the tests wisely. After having tested the outputs once they may be
turned off during the remaining test of the detectors.
Only persons with adequate knowledge of the fire alarm system should
perform this test.
How to mute and reset the alarms can be found in this manual
chapter: 2-4, 2-5.
Heat detectors
Heat detectors are preferably tested with test equipment available from
Consilium.
Apply heat to the sensing element until alarm is indicated by a red indication
on the detector and on the Control unit.
When the sensing element is cold again the alarm should be reset on the
control unit.
Important:
If other test equipments are used, for example cigarette lighter or heating gun,
make sure not to over-heat the detector by holding the heat-source to close to
the detector. This will damage the detectors, for example causing the plastic to
melt.
Smoke detectors
Smoke detectors are preferably tested with test gas equipment available from
Consilium.
User's Guide Chapter 13: Maintenance 13-2
CS3000
Spray test gas on to the detector during 1 second. Wait 10 seconds until new
gas is sprayed during 1 second. Repeat this procedure until the detector
indicates alarm with a red indication and the alarm is indicated on the control
unit.
After a while when the test gas has disappeared from the detector the alarm
should be reset on the control unit.
If other test methods are used, make sure not to damage the detector.
Flame detectors
Flame detectors may be tested with an ordinary cigarette lighter.
Turn up the flame to a height of approximately 5 cm.
Hold it in front of the detector at a distance of about 2-5 meters. Move the
lighter slowly during the test to obtain a flickering flame until alarm is
indicated with a red indication on the detector or on the address unit and on the
control unit.
After closing the lighter the alarm should be reset on the control panel.
Additional information
There are some other easy tests that concerned owners/ crews may perform at
the same time
Major computer failure Program execution has stopped. Contact our service department.
8 Additional section unit(s) * Wrong definition of number of Compare the installation with
section units. the drawings. Contact our
service department.
Section unit connections faulty. Connect the unit correctly.
21 Bad answer (Abnormal Bad communication with one or Exchange the section unit if the
condition) several section units, could be condition remains or returns. If
temporary. this fault is not temporary
contact our service department.
22 No answer Wrong type of section unit. Exchange to the correct section
unit.
The section unit has two Check the units.
addresses.
Hardware fault. Exchange the unit.
A fuse is blown. A secondary Exchange the fuse.
fault appears, code (83).
Cable break in loop or system Mend the cable. See Cable at
loop. A secondary fault appears, the end of this appendix.
code (121).
23 Wrong loop unit mark Section unit faulty. Exchange the section unit.
24 Wrong unit status Section unit faulty. Exchange the section unit.
Wrong software in CS3000. Change the software.
Wrong type of detector Install correct type of detector.
installed. Restart the system.
25 Unknown ID Communication error Reboot and retry. If this does
not solve the problem, contact
our service dept.
Software too old Update software
26 Bad loop comm. * The loop communication is bad. Test the loop. Measure the cable
(Abnormal condition) resistance. See Cable at the end
of this appendix.
27 Loop comm. stopped The loop communication is Contact our service department.
stopped by a section unit.
28 Loop trans. stopped Communication error on central Contact our service department.
unit level.
29 Communication error
Two section units with the same Check the section units.
address.
Faulty section unit. Exchange the section unit.
41 Booted The system is booting. Contact our service department.
42 Boot disabled Section unit is faulty. Exchange the section unit.
Address unit on a sub-loop is Test the sub-loop.
faulty.
User’s Guide Appendix A: Fault codes A-3
CS3000
43 Wrong address interval Overlapping address intervals. Set a valid address interval.
End-address of the interval is Set a valid address interval.
lower then the start-address.
44 Illegal address
Faulty section unit. Exchange the section unit.
Replace unit
89 No autoalarm Unable to use autoalarm
Optical smoke detector: Clean
90 Polluted detector Detector head is polluted.
the detector head according to
(Abnormal condition)
recommendations.
126 Short circuit on prim. Short circuit between the Attend to the problem.
Side positive and the negative
connector on the primary side.
127 Short circuit on sec. Short circuit between the Attend to the problem.
Side positive and the negative
connector on the secondary side.
141 Earth fault + Earth fault between the positive See Earth fault at the end of this
connector and earth. appendix.
142 Earth fault - Earth fault between the negative See Earth fault at the end of this
connector and earth. appendix.
143 High current Normal current exceeded Check power consumers
144 Earth fault Earth fault (either positive or Locate and fix the cause
negative)
145 Low voltage Too low system voltage from Test the rectifier and measure
the power unit the voltage. Contact our service
department.
147 Fire Prewarning The system has detected a Check the unit.
smoke value approaching the
alarm level.
148 Fault alarm transmitted Obsolete Obsolete
149 Fire brigade disconnection Industrial application only. Reconnect the connection.
Transfer to fire brigade
disconnected.
150 Timer Stuck The timer does not work Check the unit.
properly.
153 Emergency power failure The emergency power is Check the emergency power
missing
154 Secondary power failure All 115/230VAC power supplies Check the power supplies
are faulty
161 Door Open A door is still open one minute Check the door.
after the instruction to close it
was sent.
162 Door closed A door intended to be open is Open the door
closed
163 Open Door Subloop Cable break between module Mend the cable.
Break and open door sensor.
164 Door Closed Subloop Cable break between module Mend the cable.
Break and closed door sensor.
User’s Guide Appendix A: Fault codes A-6
CS3000
166 Damper /Door should Damper/door in wrong position. Check for obstruction.
have been opened
167 Damper /Door should Damper/door in wrong position. Check for obstruction.
have been closed
170 Sensor Fault The detector has a faulty sensor Replace the detector.
element.
NB This fault could be the result Check the location of the
of air blowing at the unit. detector and if need be, move it
to a less windy location.
171 Cable break from input 1 There is a cable break on input Check the cable.
1.
172 Cable break from input 1 There is a cable break on input Check the cable.
2.
173 Door Feedback There is no response from the Check the door-holder relay and
door-holding relay. its cable.
174 No power supply for loop No power feed from the pcb. DC/DC converter faulty.
175 Door in wrong position Door in wrong position. Check for obstruction.
176 Cable break positive side Check for a cable break on Mend the cable break.
positive lead.
A tripped short circuit isolator Check the short circuit isolators.
can cause this fault.
177 Cable break negative side Check for a cable break on Mend the cable break.
negative lead.
A tripped short circuit isolator Check the short circuit isolators.
can cause this fault.
178 Wrong type of loop unit Check the ID setting of the Set a correct value on the DIP-
found faulty unit. switch of the unit.
179 Unable to detect short Unable to detect short circuit. Exchange loop-PCB.
circuit
180 Valve Closed Valve closed. Check why it is closed.
181 Loop cable short circuit Short circuit on subloop. Check cable.
182 Cable break A cable break has been detected. Check corresponding cables.
183 Cable overload, current There is an overload in the Check if too many units are
limit reached cable. connected to the cable. Compare
with cable data.
184 Power fault The power supply is lost. Check power generation.
User’s Guide Appendix A: Fault codes A-7
CS3000
185 Loss of capacity to charge The battery charger is unable to Check the battery charger and
battery charge the battery. the battery.
186 External Fault Fault from input. Check cable and/or external
unit.
187 Double address on loop Check the offending units Set correct addresses for the
against drawings. units, with the DIP-switches.
Cable break
No section units are answering.
- The cable is broken before the first section unit if no answer is received on a
single fed loop.
- The cable is broken before the first section unit and after the last section unit
the if the loop is a double fed loop.
The easiest way to find a short circuit is to divide the cable in two halves,
locate the short-circuit on one of the halves. Divide this half of the cable again
into two halves. Continue to divide the cable into halves until you have found
the short-circuit.
Fuses
Check the fuses on the boards included in the system. The fuses are mounted
on the front panels on the following boards: ARK-2, GSK-2, INK-2, KPK-4,
LPK-2, RS232K-2, KPK-2, SPK-2 and UTK-2. The fuses to the IKK-4 are
mounted on the board itself.
* The central unit is not working properly. Indicator No. 1 (green) is not lit.
** Default value. Can be any value.
User’s Guide Appendix B: Technical Documentation File B-1
CS3000
Fuses
F5
F4
F3
I/O-board
F2 (IKK-4)
F1
MN3000
Fuse
Appendix C:
Installation and operation addendum
The fire detection system must be installed and configured in accordance with Subpart 161.002 and
Subchapter J of Title 46 of the U.S. Code of Federal Regulations, and with the 1993 or later version of
NFPA 72. This is in addition to any other requirements specific to the vessel and its route. Only those
components listed on the approved component list may be used.
The approved component list identifies those components that may be used in locations requiring an
exceptional degree of protection. Location requiring an exceptional degree of protection means a
location exposed to weather, seas, splashing, pressure-directed liquids, or similar moisture conditions.
These locations include--
(1) On deck;
(2) A machinery space;
(3) A cargo space;
(4) A location within a galley or pantry area, laundry, or water closet which contains a shower or
bath; and
(5) Other spaces with similar environmental conditions.
The fire detection system shall be installed as a fully addressable system. Any non-addressable
initiating device must be used with an addressing unit to provide an address for that device. Each
addressing unit shall be used to support only one device. Examples of non-addressable initiating
devices are the manual call point NS-CPWP and the UV-flame detector NS-DUV.
A trouble signal must be annunciated by the activation of the Models UR-2K and UR-2KN timers.
Timer UR-2K must be installed in a locker.
The fire control panels (CS3000 and CS3004) must be installed with two sources of external power.
The internal battery cannot be used to satisfy the requirement for a secondary source of power.
User's guide USCG Appendix D D-1
CS3000
Appendix D:
Component list for USCG approved systems
Approved Component List for Salwico CS3000 or CS3004 systems as an U.S. Coast Guard approved system.