Non Factored Reaction For Sun Shade

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Inroduction:

This Report include the anchor reaction from the Steel structure supporting the sun screen.
all the profile size is considered for reaction estimation, with some additional weight for safety,
additional sizing and correct will be provided in final structural calculation
Loading:
Dead Load:

Self weight of steel and considering 25 kg/m2 for the aluminium sheet
kN kN
DL  0.25  1.47m  0.367
2 m
m

Wind Load:
The sunshade is open from top, wind load will not be critical, conservatively 1.0 kPa is considered

wind load considered is 1.0 kPa


kN
WL  1.47m 1 kPa  0.15m  0.221 m
m

Combination:

Service (SLS) check

1.0DL  1.0WL

live load is less than 1.0 kPa (as per BS 6399 live load is 0.6 kPa)
SERVICE REACTION (NON FACTORED)

The non factored reaction on the bracket is 1.5x33 kN = 49.5 kN acting downward.
(50% additional redunduncy)