GENERAL NOTES

3
1. ALL MECHANICAL EQUIPMENT (INTERNAL & EXTERNAL) TO BE CORROSION TREATED
WITH BLYGOLD OR EQUIVALENT. TO SUIT COASTAL LOCATION.

2. EXHAUST FANS TO OPERATE WITH LOCAL LIGHTING SWITCHING - WITH 10MIN RUN-ON.

3. REED SWITCHES TO BE INSTALLED TO EXTERNAL OPENINGS WERE IS SERVED


SIDE DISCHARGE AC CONDENSER. FANS TO OPERATE WITH HIGH LEVEL SECURE VIA & AC SYSTEM. WITH THE HIGH LEVEL WINDOWS IN THE MULTI PURPOSE ROOM TO
WALL MOUNTED & STACKED. LIGHTING CIRCUIT - WITH RELIEF GRILLE WITH BE THE EXCEPTION.
SCREEN TO HAVE MIN 50% FREE 10MIN RUN-ON RODENT MESH.
AREA TO ENSURE AIRFLOW FOR CONFIRM COLOUR 4. DUCTWORK TO BE INTERNALLY LINED WITH NOT LESS THAN 1.5m OF 50mm
HEAT DISSIPATION NOTE 4 WITH ARCHITECT PERFORATED FOIL FACE INSULATION - PER ACOUSTIC REQUIREMENTS.

A B C D E 5. ACOUSTIC RATED FLEX DUCT SHALL BE USED THROUGHOUT.

1
CU.03 E2
E2 E2 E2
3 CU.02 CU.01
- -
-
- E2
2 -
RH
RANGEHOOD TO DISCHARGE ON
ROOF OVER. FLUE TO BE PAINTED
EF.4
TO MATCH ROOF. 150Ø
E1
EF.3
EF.2
E1
50
TD 3 2
50 E1

400x150
E1
E1 50 3
50
50 E1 UD
E1 50
50
E1 E1 UD
50

400x150

400x150
50
E1
50
E1
E1 3
50
50
AC.G.3
E1
3 50
E1
50 E1 E1
50 50
REFRIGERANT PIPEWORK TO LEVEL 1 AC
TD

UD UD 4
E1 E1 E1 E2
50 50 50 -

T AC.G.3
C AC.G.4
T
C T
C
T AC.G.4
C REFRIGERANT TO RISE WITHIN FRAMED
OUT CAVITY SECTION TO AVOID HIGH
EF.1 AC.G.1
AC.G.2
LEVEL GLAZING. CO-ORDINATE WITH
ARCHITECTURAL LAYOUTS
200x200

5
HIGH LEVEL SECURE RELIEF GRILLE
900x150 WITH RODENT MESH.
POWDER COATED BLACK AND
FIXED BEHIND TIMBER BATTENS
CEILING CASSETTE - 600x600
3 3
NATURAL VENTILATION VIA
3 OPERABLE LOUVRES AT HIGH LEVEL.
LOUVRES TO BE FITTED WITH REED SWITCH
TO TURN OFF AC UNIT WHEN OPEN >5MIN

REED SWITCHES TO EXTERNAL


OPENINGS TO SWITCH OFF AC
AFTER 5MINS OPEN

0 2 4 6 8 10 m

1:100
ISSUE DATE AMENDMENT ARCHITECT CLIENT BUILDING SERVICES ENGINEER DESIGNED PROJECT DRAWING TITLE
0 23.04.21 TENDER ISSUE KM MECHANICAL SERVICES
1 27.04.21 TENDER ISSUE ASPENDALE LIFE SAVING CLUB
1230 NEPEAN HWY CHELTENHAM CHECKED GROUND LEVEL - MECHANICAL LAYOUT
2 04.06.21 TENDER ISSUE
3192
GROVES STREET ASPENDALE , VIC
3 09.06.21 TENDER ISSUE Sydney DO
Ph. 1300 653 356
61 2 9922 2344 nbrsarchitecture.com
PO BOX 1000 MENTONE VICTORIA
Any form of replication of this drawing in full or in part without the written NORTH POINT SCALE at A1 PROJECT No. DRAWING No. ISSUE
3194
permission of NBRS+PARTNERS Pty Ltd consistitutes an infringement of the Sydney Melbourne Manila 1 : 100
copyright.
L3, 116 Hardware St, Melbourne, VIC 3000 DATE
MEL18297-M100 3
THE DESIGN AND DETAILS SHOWN ON THESE DRAWINGS ARE APPLICABLE TO THIS PROJECT ONLY AND
MAY NOT BE REPRODUCED IN WHOLE OR IN PART OR BE USED FOR ANY OTHER PROJECT OR PURPOSE Nominated Architects:
WITHOUT THE WRITTEN PERMISSION OF ERBAS & ASSOCIATES WITH WHOM COPYRIGHT RESIDES.
ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE SHOWN. WORK TO FIGURED DIMENSIONS, DO NOT
Andrew Duffin NSW 5602 ©2019 Ph: (03) 8648 6538 general@erbas.com.au APR2020
SCALE FROM DRAWINGS. NBRS & Partners Pty Ltd VIC 51197 ABN 16 002 247 565 www.erbas.com.au DRAWN
CHECK ALL DIMENSIONS ON SITE PRIOR TO CONSTRUCTION. THIS DRAWING TO BE READ IN
CONJUNCTION WITH ALL CONTRACT DOCUMENTS. SH