Analog positioning module RE 30050/07.

12
Replaces: 03.04
1/12

Type VT-MACAS-...

Component series 1X

Table of contents Features


Contents Page – Suitable for controlling valves with installed electronics for
Features 1 position and velocity control
Ordering code 2 – Design: Module for snapping onto carrier rails
Front plate 3 – Enable input
Block diagram with pin assignment 4 – Cable break detection for actual value cable
Technical data 5 – Interfaces short-circuit-proof
Function 6 – Test points on front plate
Electrical connection 7 and 8 – Compensation step that can be switched off
Adjustment and commissioning 9 – Position: PT1 control
Error reactions 10 – Velocity control possible in connection with tachometer
(speed indicator): PI control
Velocity controller adjustment 11
– Area adjustment cylinder
Device dimensions 12
Project planning / maintenance instructions /
additional information 12
Notice:
The photo is an example configuration.
The delivered product differs from the figure.
2/12 Bosch Rexroth AG Hydraulics VT-MACAS-... RE 30050/07.12

Ordering code

VT- M A C A S 500 1X V0
Hydraulic component Option
Axis control =A without = Marking
Type Variant with voltage input
Controller =C I= Variant with current input

Control Customer version


Analog =A V0 = Catalog version

Function 1X = Component series 10 to 19


Position control =S (10 to 19: Unchanged technical data
and pin assignment)
Serial number for types
500 = Standard variant without valve amplifier function

Preferred types
Amplifier type Material number
VT-MACAS-500-10/V0 0811405139
VT-MACAS-500-10/V0/I 0811405140
Front plate

Enable TP Command value

TP Actual value
RE 30050/07.12 VT-MACAS-...

Error U
ON inp. act.
TP 0V
U IN pos.
0.5% 1%
Cable break actual value ⨍⨍ MACAS Message in position:
+ + Position window
Zero point calibration actual value zero 1 0V input off
– -0- Compensation step On/OFF
feedb. 2 +10 V/ +10 V signal –
Adjustment actual gain value gain 3 0V feedb. zero –
Zero point valve
4 +10 V/ +10 V signal valve +
A B
1 5 4...20 mA
15 3 valve S
Area adjustment cylinder 13 5 A/B 6 I Switch-over velocity position controller
11 7 signal
9 7 U +10 V V
off 8 0V
supply 24 V= KP
Ramp time ranges 0.1...1 s 9 +UB 7 9 11
1...10 s 10 enabling 5 13 P controller adjustment
ramp time 3
1
15
11 message
Accelerations 12 IN position
K I 7 9 11 I controller adjustment (velocity control)
13 – 5 13
Braking or
3 1 15 KT1 controller (position control)
K T1
Hydraulics Bosch Rexroth AG
3/12
4/12

v vor v zur.
or acceleration or braking
v ext. v retr.

off
Block controller

100 ms...1 s
1 s...10 s
Area adjustment

Position
U (5) 4...20 mA
Command PT 1 I
Ramp generator Valve signal
value
(1)
0...10 V – Actual value
acceptance S/V + + (7) 0...+
–10 V
and/or – +
0...+
–10 V PI + +
Bosch Rexroth AG Hydraulics

or + –
(2)
4...20 mA + Velocity
only with command
Block diagram with pin assignment

value 0...±10 V ON/OFF


Command value

Zero point (6)


Actual value (3) Gain Zero point

– 0.5%
– 1.0%
0V

+
+
0...10 V – valve Ground
and/or Compensation
– step
0...+
–10 V Actual value
or + +24 V
(4)
4...20 mA +
0V (12)
"IN POS"
in position (compare
+24 V
Position window technical data)
Cable break 0V (11)
>
–1
⨍⨍
Error

(10)
Enable
>
–1
ON Block valve signal

Supply U
(9)
UB 24 V +15 V
(8)
0V +
–15 V –15 V
VT-MACAS-... RE 30050/07.12
RE 30050/07.12 VT-MACAS-... Hydraulics Bosch Rexroth AG 5/12

Technical data (For applications outside these parameters, please consult us!)

Supply voltage Nominal 24 V =


(8), (9) Battery voltage 21...40 V,
Rectified alternating voltage Ueff = 21...28 V
(one-phase, full-wave rectifier)
Current consumption, max. mA 200
Signal input VT-MACAS-500-10/V0 Ucommand: ±10 V, differential amplifier
(1), (2) Ri = 100 kΩ
VT-MACAS-500-10/V0/I Icommand: 4...20 mA Rsh = 200 Ω
Actual value signal VT-MACAS-500-10/V0 Uactual: ±10 V, differential amplifier
(3), (4) Ri = 100 kΩ
VT-MACAS-500-10/V0/I Iactual: 4...20 mA Rsh = 200 Ω
Valve signal UV = ±10 V (max. 10 mA) or
(5), (6, (7)) IV = 4...20 mA (middle 12 mA)
Compensation step Can be switched off;
effective in a range of ± 4 %
Enable signal (10) V= 8.5...40
Error message (11) No error: 24 Vnom (UB) max. 50 mA
Error: < 2 V
IN POS message (12) IN POS: 24 Vnom (UB) max. 50 mA
Not IN POS: < 2 V
Ramp ranges I: 0.1 ... 1 s
II: 1 ... 10 s
Area adjustment Min. 1:1; max. 1:4
A K : AR
Actual value adjustment Zero point: –5...10 %
Gain: 50...110 %
Controller type Position: PT1
Velocity: PI
Zero point valve % ±5
Special features – Switchable from position to velocity control
– Switchable position window
– Test points on front plate
– Interfaces short-circuit-proof
Format/design mm (86 x 110 x 95.5) / module
Mounting Top hat rail TH35-7,5 or G rail G32 according to EN 60715
Connection Connectors + terminals
Ambient temperature °C 0...+70
Storage temperature range °C –20...+70
Weight m 0.38 kg
6/12 Bosch Rexroth AG Hydraulics VT-MACAS-... RE 30050/07.12

Function

Applications Position control


By means of this controller module, simple position or ve- Command and actual value of the position are compared
locity controls can be represented in connection with Bosch and the deviation is forwarded to the valve amplifier. In case
Rexroth servo cylinders with analog position measurement of an abrupt change of the input signal, the system will react
systems (potentiometer). As the entire signal processing is with maximum dynamics. The times for accelerating or brak-
analog and the module is only equipped with the necessary ing a load are either limited by the available power or the
features for the set-up of controls, the costs for the drive system gain. With a ramp function as input value, the load is
can be kept low. There is moreover the particularity that the moved with a constant velocity.
module can be internally switched to velocity control (front
plate) and one version is in each case offered for voltage in-
terface and current interface, referring to the command and
actual values.

0...10 V/ +
– 10 V
4...20 mA

Velocity
G Σ 0...10 V/ +
– 10 V
Position 4...20 mA

Command value
in position

0 V Error
UB = +24 V DC

Enable
+24 V

+24 V

+24 V
0V

0V

Velocity control*
Command and actual value of the velocity are compared With a ramp function as input signal, there is a gradual acce-
and the deviation is forwarded to the valve amplifier. The si- leration and/or deceleration with a constant value.
gnal is amplified by integration so that even smallest errors * Only possible with tachometer (speed indicator).
are compensated.

0...10 V/ +
– 10 V
+ 4...20 mA


Velocity

G Σ 0...10 V/ +
– 10 V
Position 4...20 mA

Command value
0 V Error
in position
UB = +24 V DC

Enable
+24 V

+24 V

+24 V
0V

0V
RE 30050/07.12 VT-MACAS-... Hydraulics Bosch Rexroth AG 7/12

Electrical connection

Wiring diagram
AVPC-V

ON inp. act.
U IN pos.
0.5% 1%
⨍⨍
+
+ zero 1 0V input off
– -0-
feedb. 2 +10 V/ +10 V signal –
gain 3 0V feedb. –
zero
4 +10 V/ +10 V signal valve +
A B
1 3 5
15 4...20 mA valve S
13 5 A/B 6 I
signal
11 7 7 U +10 V
9 V
off 8 0V
supply 24 V= KP
0.1...1 s 9 +UB 7 9 11
1...10 s 5 13
10 enabling
ramp time 3 1 15
11 message
12 IN position
K I 7 9 11
13 –
5 13
3 1 15
K T1

1 2 3 4 5 6 7 8 9 10 11 12 13

+10 V
free
0V
10 V/+ 10 V

24 V
Usoll 24 V DC 0V
0V

24 V DC 24 V
–10 V 0V
v
or 8,5...40 V DC 24 V
0V x
0V
Actual
value 0V nom.
24 V DC

D* D*
E
D
*
C
B
0V
A
24 V

D* valve signal for valve with voltage or current interface


8/12 Bosch Rexroth AG Hydraulics VT-MACAS-... RE 30050/07.12

Electrical connection

Wiring diagram
AVPC-mA

ON inp. act.
U IN pos.
0.5% 1%
⨍⨍
+
+ zero 1 input off
– 4...20 mA -0-
feedb. 2 signal –
gain 3 feedb. –
4...20 mA zero
4 signal valve +
A B
1 3 5
15 4...20 mA valve S
13 5 A/B 6 I
signal
11 7 7 U +10 V
9 V
off 8 0V
supply 24 V= KP
0.1...1 s 9 +UB 7 9 11
1...10 s 5 13
10 enabling
ramp time 3 1 15
11 message
12 IN position
K I 7 9 11
13 –
5 13
3 1 15
K T1

1 2 3 4 5 6 7 8 9 10 11 12 13

free
I soll 24 V
4...20 mA 24 V DC 0V
I set
I const. 24 V DC 24 V
0V
8,5...40 V DC 24 V
mA
4...20 mA 0V
x
0V nom.
Actual value 24 V DC

D* D*
E
D
*
C
B
0V
A
24 V

D* valve signal for valve with voltage or current interface


RE 30050/07.12 VT-MACAS-... Hydraulics Bosch Rexroth AG 9/12

Adjustment and commissioning

The entire adjustment of the module is carried out at the


front plate with operating pressure.

Checking the
wiring (page 6)

– Velocity controller/position controller


Mode settings – Compensation step ON / OFF
– Position window 0.5 % / 1 %
– Ramp ON / OFF

– KP = 1 with position control


Controller default setting – KI = 2 / KTI = 1 with velocity control (KI = 1 forbidden)

– Hex switch "A / B"; according to the area ratio of the cylinder
Area ratio default setting

– LED "ON" is illuminated


Supply voltage ON
– LED " U" and LED " ʃʃ" are not illuminated
Enable ON (cl. 10)
→ otherwise, see error reactions, page 10

– Specification of the command value minimum


Adjustment of the
→ by means of "zero feedb." potentiometer actual value adjustment to 0 V
actual value transducer
(TP "act." against TP "⊥")
– Specification of the command value maximum (e. g. + 10 V; 20 mA)
→ by means of "gain" potentiometer actual value adjustment to 10 V
(TP "act." against TP "⊥")
Notice
At the 13-pin connection terminal of the module, no measuring devices must be con-
nected in order to perform voltage measurements of the actual or command value.

– Enable OFF
Adjustment of the
– Specification of the command value for valve zero position
valve signal
→ By means of "zero valve" potentiometer adjustment of the valve signal
(e. g. cylinder standstill; 0 V at the valve)

– Gradual increase in the KP share, then


Controller adjustment – Gradual increase in the KTI /KI share
– Adjustment aid, page 10

– If ramp function required:


Ramp adjustment Ramp ON → time range pre-selection
– Specification of the command value step (e. g. 20 %...60 %)
Setting of the velocity ramps (position) and/or acceleration ramps (velocity) by
means of the potentiometer

– Comparison of the chronological sequence s(t) and/or v(t)


Fine adjustment
of both directions of movement by means of an oscilloscope
area adjustment
→ by means of hexcode switch "A / B"
compensation of differences
10/12 Bosch Rexroth AG Hydraulics VT-MACAS-... RE 30050/07.12

Error reactions

U: Tripping if the value falls below the minimum inter- The error is stored.
nal supply voltage Deletion of the error by switching the enable signal or the
⇒ Valve signal 0 V and/or 12 mA; supply voltage off and on again.
⇒ Message LED " U" and (11)
Possible causes: External supply voltage too low (< 16 V) or
internal error (→ repair).
ʃʃ: Tripping if the actual value or command value
lines break
⇒ Valve signal 0 V and/or 12 mA;
⇒ Message LED "ʃʃ" and (9)

Ideal development (without command value ramps)


Position sactual scommand

"Overshooting", P gain too high, → rotate switch KP against 1


Position sactual scommand

"Creeping into the position", P gain too low,


Position sactual scommand → rotate switch KP against 16

"Vibrations", time constant too small, → rotate switch KT1 against 16


Position sactual scommand

"Area ratio wrong"; set symmetric motion sequence by means of switch A/B
Position sactual scommand

t
RE 30050/07.12 VT-MACAS-... Hydraulics Bosch Rexroth AG 11/12

Velocity controller adjustment

Ideal development (without command value ramps)


vactual

V Minimum
vcommand
following error

P gain too small, → rotate switch KP against 16

vactual

vcommand

P gain too large, → rotate switch KP against 1

vactual

vcommand

P gain correct, however following error too large,


minimization of the following error by means of the I controller → ro-
tate switch KI until the min. following error is reached
vactual
Following error
vcommand
12/12 Bosch Rexroth AG Hydraulics VT-MACAS-... RE 30050/07.12

Device dimensions (dimensions in mm)

86 74

ON 7,5
UB

5,5
110

1 2 3 4 5 6 7 8 9 10 11 12 13 38
36
98 21,5

110

Wall mounting (86 x 110 x 95.5) mm Carrier rail assembly (snap-in)

Project planning / maintenance instructions / additional information


– The distance to aerial lines, radios and radar systems must be sufficient (> 1 m).
– Do not lay solenoid and signal lines near power cables.
– For signal lines and solenoid conductors, we recommend using shielded cables.
The cable shield must be connected to the control cabinet extensively and as short as possible.
– The valve solenoid must not be connected to free-wheeling diodes or other protection circuits.

Bosch Rexroth AG © This document, as well as the data, specifications and other informa-
Hydraulics tion set forth in it, are the exclusive property of Bosch Rexroth AG. It
Zum Eisengießer 1 may not be reproduced or given to third parties without its consent.
97816 Lohr am Main, Germany The data specified above only serve to describe the product. No state-
Phone +49 (0) 93 52 / 18-0 ments concerning a certain condition or suitability for a certain applica-