Professional Documents
Culture Documents
Edfmt391732 Fxuq-A
Edfmt391732 Fxuq-A
Edfmt391732 Fxuq-A
201709
Engineering Data
FXUQ-AVEB
50 / 60 Hz
FXUQ-AVEB EDFMT391732
FXUQ-AVEB
4-Way Flow Ceiling Suspended Type
50 / 60 Hz
1. Lineup..........................................................................................................2
2. Specifications..............................................................................................3
3. Dimensions..................................................................................................4
4. Piping Diagrams..........................................................................................5
5. Wiring Diagrams..........................................................................................6
6. Electric Characteristics................................................................................7
7. Safety Devices Setting................................................................................8
8. Capacity Tables...........................................................................................9
8.1 Cooling Capacity for Te: Auto............................................................9
8.2 Cooling Capacity for Te: 6°C.............................................................9
8.3 Cooling Capacity for Te: 9°C.............................................................9
8.4 Heating Capacity..............................................................................10
9. Sound Levels.............................................................................................11
10. Accessories...............................................................................................12
10.1 Optional Accessories (for Unit)........................................................12
10.2 Optional Accessories (for Controls).................................................12
11. Installation Manual....................................................................................13
1
FXUQ-AVEB EDFMT391732
1. Lineup
8.0 kW 11.2 kW
Capacity range
3 HP 4 HP
Capacity index 71 100
2
FXUQ-AVEB EDFMT391732
2. Specifications
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During cfm=m³/min×35.3
actual operation, these values are normally somewhat higher as a result of ambient conditions. l/s=m³/min×1000/60
3
FXUQ-AVEB EDFMT391732
3. Dimensions
FXUQ71AVEB / FXUQ100AVEB
Unit: mm
3D080135
4
FXUQ-AVEB EDFMT391732
4. Piping Diagrams
FXUQ71AVEB / FXUQ100AVEB
4D034245P
Unit: mm
Model Gas Liquid
FXUQ71AVEB / FXUQ100AVEB φ15.9 φ9.5
5
FXUQ-AVEB EDFMT391732
5. Wiring Diagrams
FXUQ71AVEB / FXUQ100AVEB
3D079580
6
FXUQ-AVEB EDFMT391732
6. Electric Characteristics
FXUQ71AVEB / FXUQ100AVEB
4D080216A
7
FXUQ-AVEB EDFMT391732
8
FXUQ-AVEB EDFMT391732
8. Capacity Tables
8.1 Cooling Capacity for Te: Auto
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
For VRV indoor units only at Te: 9°C / mixed combination of VRV and residential indoor units
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXUQ71AVEB 71 3.7 3.7 4.8 4.4 6.0 5.2 6.5 5.3 7.0 5.4 7.4 5.4 7.8 5.3
FXUQ100AVEB 100 5.5 5.0 6.8 6.0 8.5 7.0 9.2 7.2 9.5 7.1 10.1 7.0 10.6 6.9
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
9
FXUQ-AVEB EDFMT391732
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
10
FXUQ-AVEB EDFMT391732
9. Sound Levels
FXUQ71AVEB
4D080130
FXUQ100AVEB
4D080131
11
FXUQ-AVEB EDFMT391732
10. Accessories
10.1 Optional Accessories (for Unit)
Model
Item
FXUQ71AVEB FXUQ100AVEB
Sealing member of air discharge outlet KDBHP49B140
Decoration panel for air discharge KDBTP49B140
Replacement long-life filter KAFP551K160
C: 3D080116A
Model
Item
FXUQ71AVEB FXUQ100AVEB
Cooling Only BRC7CB59
Wireless
Remote controller Heat Pump BRC7CB58
Wired BRC1C62
Navigation remote controller (Wired remote controller) BRC1E62 (Note 2)
Wiring adaptor for electrical appendices (2) H KRP4AA53
Remote sensor (for indoor temperature) KRCS01-4B
Installation box for adaptor printed circuit board KRP1BA97
C: 3D080116A
Notes:
1. Installation box is necessary for each adaptor marked H.
2. Individual airflow direction, auto airflow rate can be set only via wired remote controller BRC1E62. Cannot be set via other remote controllers.
12
FXUQ-AVEB EDFMT391732
11. Installation
01_EN_3P177351-7V.fm Manual
Page 1 Friday, August 21, 2015 9:25 AM
FXUQ71AVEB
FXUQ100AVEB VRV SYSTEM Air Conditioners Installation manual
1 English
3P177351-7V
13
FXUQ-AVEB EDFMT391732
2. BEFORE INSTALLATION
Used in
When unpacking the indoor unit or moving the unit after common with
unpacked, hold the hangers (4 places) and do not apply packing
Shape
force to other parts (particularly refrigerant piping, drain
piping and resin parts).
• Make sure to check in advance that the refrigerant to be used
for installation work is R410A.
(The air conditioner will not properly operate if a wrong refrig-
erant is used.) (15) Non
Name (14) Screw
• For installation of the outdoor unit, refer to the installation woven fabric
manual attached to the outdoor unit. Quantity 5 pcs. 1 sheet (Miscellaneous)
• Do not throw away the accessories until the installation work
• Operation manual
is completed. • Installation manual
• After the indoor unit is carried into the room, to avoid the Shape • Declaration of conformity
indoor unit from getting damaged, take measures to protect
the indoor unit with packing materials.
(1) Determine the route to carry the unit into the room.
(2) Do not unpack the unit until it is carried to the installation
location.
Where unpacking is unavoidable, use a sling of soft
material or protective plates together with a rope when
lifting, to avoid damage or scratches to the indoor unit.
English 2
3P177351-7V
14
FXUQ-AVEB EDFMT391732
(It may lead to capacity drop Does not heat 2500 or more
more
3 English
3P177351-7V
15
FXUQ-AVEB EDFMT391732
CAUTION
(Discharge pattern) (Views from the ceiling)
• Install the indoor and outdoor units, power supply wiring,
4-way discharge 3-way discharge
remote controller wiring and transmission wiring at least 1
meter away from televisions or radios to prevent image inter- 2 2 2
ference or noise.
(Depending on the radio waves, a distance of 1 meter may
not be sufficient to eliminate the noise.) 3 1 1 3 1
• Install the indoor unit as far as possible from fluorescent
lamps.
If a wireless remote controller kit is installed, the transmis- 4 4
sion distance may be shorter in a room where an electronic 2-way discharge (optional blocking material kit 2-way
lighting type (inverter or rapid start type) fluorescent lamp discharge is required)
is installed. (NOTE 1) 2 2
NOTE
1. Restriction applies to the exposed type lighting but does not 1
apply to the recessed type.
2. When the air outlet is closed, the space shown with “ ”
must have a distance of 30mm or more. 4
3. For setting the airflow direction of horizontal blade, refer to
the operation manual attached to the indoor unit and The indication “ . ” shows the refrigerant piping outlet
remote controller. direction.
: Backward outlet piping : Rightward outlet piping
(2) Ceiling height (straight outlet) (piping needs to be bent)
• This indoor unit can be hung from the ceiling of which
height is up to 3.5m (models 100: up to 4.0m). For upward outlet piping, any outlet pattern can be selected.
• However, if the ceiling height exceeds 2.7m (models 100:
Fig. 3
3.2m), it is necessary to set on site from the remote con-
troller. Refer to the section “10. FIELD SETTING AND
TEST OPERATION”.
(3) Air discharge direction * : This indication shows the air discharge direction.
Select the air discharge pattern according to the installation For cross-reference of air outlet No. to indication on indoor
location. unit
In case of 2-way and 3-way, it is required to set on site from
the remote controller. Name of air outlet Indication on indoor unit
For details, see the section “10. FIELD SETTING AND Air outlet 1
TEST OPERATION”. Air outlet 2
(Caution) Since there are some restriction on the piping Air outlet 3
connection side, make sure to select the air dis-
Air outlet 4
charge pattern from the Fig. 3.
The names of air outlet are shown in inscription by the num-
No. of air outlet
ber of “ ” marks on the underside of the air outlet.
(Refer to the Fig. 4) Indication on
4 indoor unit
(4) Use hanging bolts for installation.
Investigate if the installation place can withstand the mass
of the indoor unit and, if necessary, hang the unit with bolts
after it is reinforced by beams etc.
(Refer to the installation pattern paper (11) for the mounting
pitch.) Indoor unit
Fig. 4
English 4
3P177351-7V
16
FXUQ-AVEB EDFMT391732
(2) Make holes for hanging bolts, piping outlet, drain pip-
ing outlet and electric wiring inlet.
950 (unit [mm])
• Use the installation pattern paper (11) which shows the
835 (hanging bolt pitch) above hole locations.
• Determine the locations of hanging bolts, piping outlet,
drain piping outlet and electric wiring inlet. And make the
hole.
950
Foundation bolt
50~100mm
Gas piping
Hanging bolt
Liquid piping Ceiling surface
Fig. 7
57
88
120
105
132
140 Tape
88
120
89
88
14
198
Fig. 8
Fig. 6
5 English
3P177351-7V
17
FXUQ-AVEB EDFMT391732
Hanger 1.
Hanger
Bend the horizontal
blade and pull it out.
Hanger
Fig. 9
• When carrying the indoor unit, hold it by the hanging metal fit-
tings. (Refer to Fig. 9) 2.
Claw parts
How to block the air outlet for 2-way or 3-way air discharge
• For 2-way air discharge, in addition to the attached blocking Turn the horizontal Bearing
blade backward.
material, the optional blocking material kit for 2-way dis-
charge is required.
The attached blocking material and the optional blocking Lift the claw on
the bearing
material for 2-way discharge can be used in common for any
side.
air outlet.
• For 2-way air discharge, give caution to the inclination of the
indoor unit when installing. For details, follow the instruction Remove the
horizontal
mentioned in the section “5. INSTALLATION OF THE blade.
INDOOR UNIT”.
(1) Remove the horizontal blade of the air outlet to be
blocked. (Refer to Fig. 10 and Fig. 11)
1. Without applying force to the bearings, lift the horizontal
blade with both hands and remove it from the bearing at
the side of the motor not mounted.
Claw (Lift upward.)
2. After turning the horizontal blade backward, remove the
claw of the bearing on the motor side. Then, lift the hori-
zontal blade and remove it. Horizontal blade
*
Bearing
Fig. 11
English 6
3P177351-7V
18
FXUQ-AVEB EDFMT391732
2.
1.
Projected part
3.
Blocking material
2.
Projected part 1.
Upper decoration panel
Screw Screw
Fig. 12
< Screw location of piping >
Blocking material
Insert
Insert
Screw
Projected part
Insulation
Upper decoration
panel
Screw
2. Lift this part slightly. < Screw location other than piping part >
(Other side also.)
Fig.14
Lower decoration
panel
Fig.13
7 English
3P177351-7V
19
FXUQ-AVEB EDFMT391732
(3) Check the level of the unit from 2 directions (air outlet 1 • Install the indoor unit leveled.
If the unit is inclined and the drain piping side gets high, it
and 2 ). (Refer to Fig. 18) may cause malfunction of a float switch and results in
Nut Hanging bolt
water leakage.
(Field supply) However, for 2-way air discharge, install the unit inclined
1° downward to the drain piping.
• Attach nuts on the upper and lower side of hanger.
If there is no upper nut and the lower nut is over-tight-
Hanger ened, the hanging plate and the top plate will deform and
cause abnormal sound.
• Do not insert materials other than that specified into the
clearance between the hanger and the washer for hanger
Washer for hanger (3)
(accessory)
(3).
Unless the washers are properly attached, the hanging
Tighten
Nut (Field supply) bolts may come off from the hanger.
WARNING
To fix hanger
Fig.15 The indoor unit must be securely installed on a place
that can withstand the mass.
If the strength is insufficient, the unit may fall down and cause
injuries.
Washer clamp (5) Upper nut
(accessory)
2
1
Level
English 8
3P177351-7V
20
FXUQ-AVEB EDFMT391732
45°±2°
Electric wiring 9.5 36.3 ± 3.6 13.0 ± 0.2 R0.4-0.8
Piping penetration cover
90°±2°
12.7 54.9 ± 5.4 16.4 ± 0.2
A
15.9 68.6 ± 6.8 19.5 ± 0.2
Drain Gas
Liquid
CAUTION
Fig.19
Do not tighten flare nuts too tight.
If a flare nut cracks, the refrigerant may leak.
• The refrigerant is pre-charged in the outdoor unit.
• Use the flare nut attached to the air conditioner. • If there is no torque wrench, use Table 2 as a rule of
• When making a flare connection, coat the flared inner sur- thumb.
face only with either oil or ester oil. (Refer to Fig. 20) When tightening a flare nut with a spanner harder and
Then, turn the flare nut 3 to 4 times with your hand and harder, there is a point where the tightening torque sud-
screw in the nut. denly increases.
From that position, tighten the nut additionally the angle
Coat the flared inner surface only with shown in Table 2.
either oil or ester oil. After the work is finished, check securely that there is no
gas leak.
If the nut is not tightened as instructed, it may cause slow
refrigerant leak and result in malfunction (such as does
not cool or heat).
Fig. 20 Table 2
Piping size Recommended arm length of
(mm) Tightening angle tool used
CAUTION 6.4 60° – 90° Approximately 150mm
Do not have oil adhere to the screw fixing part of resin 9.5 60° – 90° Approximately 200mm
parts. 12.7 30° – 60° Approximately 250mm
If oil adheres, it may weaken the strength of screwed part. 15.9 30° – 60° Approximately 300mm
Spanner
Flare nut
9 English
3P177351-7V
21
FXUQ-AVEB EDFMT391732
• After leak test, referring to Fig. 22, insulate both the gas • When carrying out upward and rightward piping, use the
and liquid piping connection with the attached joint insu- attached L-shaped piping, and insulate the 2 places of
lating material (6) and (7) to prevent the piping from get- connection. (Refer to Fig. 23)
ting exposed. In addition, bend the liquid side field piping using a bender
Then, tighten the both ends of insulating material with the with radius is 40 mm or less.
clamp (4). If the attached L-shaped piping is not used or the piping is
bent with a bender with radius more than 40 mm, it may
interfere with other piping or drain hose.
Liquid side piping insulating method
Piping insulating
Clamp (4) (accessory)
material
(field supply) Tighten the section where
the piping insulating
For prevention of material and the joint Insulate the piping in the same manner as
sweating, do not insulating material (7) shown in Fig. 22 using the attached joint
expose the piping overlap. insulating material (6).
Sealing material
Wrap the sealing For upward and rightward piping
(Small) (9)
material from the root L-shaped piping insulating method
(accessory)
of the unit to the part
of flare nut connection Piping insulating material
(field supply)
To prevent sweating, do not
Liquid piping expose the piping to the
atmosphere. Flare nut
connection
Joint insulating material (6)
(accessory) L-shaped
piping (13)
Clamp (4) (accessory)
Gas piping Tighten the section where the piping insulating material and the
joint insulating material (6) overlap.
English 10
3P177351-7V
22
FXUQ-AVEB EDFMT391732
NOTE
1. The proper pressure for having nitrogen flow through the
piping is approximately 0.02MPa, a pressure that makes
one feel like breeze and can be obtained through a pressure
reducing valve. Metal clamp (2)
(accessory)
2. Do not use flux when brazing refrigerant piping.
Use phosphor copper brazing filler metal (BCuP-2: JIS Z
3264/B-Cu93P-710/795: ISO 3677) that does not require
flux. Elbow (10)
(If chlorinated flux is used, the piping will be corroded and, (accessory)
Longer side
in addition if fluorine is contained, the refrigerant oil will be
deteriorated and the refrigerant circuit will be affected
badly.) Fig. 26 Sealing material (Large) (8)
(Backward piping) (accessory)
3. When carrying out leakage test of refrigerant piping and the
indoor unit after the installation of indoor unit is finished,
confirm the connecting outdoor unit installation manual for
test pressure.
Refer to also the outdoor unit installation manual or techni-
cal document for refrigerant piping.
Metal clamp (2)
4. In case of refrigerant shortage due to forgetting additional (accessory)
refrigerant charge etc., it will result in malfunction such as
does not cool or does not heat.
Refer to the outdoor unit installation manual or technical
Drain hose (1)
document for refrigerant piping.
(accessory)
CAUTION
Sealing material (Large) (8)
Do not use antioxidant when brazing piping.
(accessory)
It may result in malfunction of components and clogging of
piping due to residue. Fig. 27
(Rightward piping)
• Select the piping diameter equal to or larger than (except
for riser) that of the connection piping (polyvinyl chloride
7. DRAIN PIPING WORK piping, nominal diameter 20mm, outside diameter
(1) Carry out drain piping. 26mm).
Carry out drain piping so that drainage can ensured. • Install the drain piping as short as possible with down-
• Drain piping can be connected from 3 directions. ward inclination of 1/100 or more and without where air
(Refer to Fig. 25, 26, and 27) may stagnate. (Refer to Fig. 28)
(It may cause abnormal sound such as bubbling noise)
Sealing material (Large) (8)
(accessory) Downward inclination of 1/100 or more
OK
Metal clamp (2)
(accessory)
Not acceptable
Fig. 25
Fig. 28
(Upward piping) Shorter side
11 English
3P177351-7V
23
FXUQ-AVEB EDFMT391732
If drain stagnates in the drain piping, the piping may be If the drain riser is installed inclined, the float switch may
clogged. malfunction and cause water leakage.
• Install supports at a distance of 1 to 1.5m so that the pip- • Make sure to use the drain hose (1), the elbow (10) and
ing may not deflect. (Refer to Fig. 29) the sealing material (Large) (8) attached to the indoor unit
as accessories.
Drain hose (1) 1. To prevent the elbow from getting damaged by the
(for connection to VP20)
metal clamp (2) for upward and backward piping,
(accessory)
Drain piping Support wrap the vinyl tape around the elbow 2 to 3 times so
(field supply) that the tape covers more than the width of metal
Ceiling slab
Distance 1~1.5m
clamp (2) leaving 10 - 15 mm from the tip of the elbow
(10) without wrapping as shown in Fig. 30.
600mm
Drain piping
Riser
Vinyl tape
Wrap with the width (approx. 20mm) larger
Elbow Fig. 30 than metal clamp (2).
Not acceptable 2. Insert the drain hose (1) and the elbow (10) to the root
of the drain socket. Tighten the metal clamp (2) within
Fig. 29 the taped range of hose inserted tip with the torque
(Caution for upward drain piping) 1.35±0.15N·m (135±15N·cm).
(Refer to Fig. 25, 26, 27, and 31)
Make sure to use the attached drain hose (1) (for rightward
piping), the elbow (10) (for upward and backward piping) Insert without leaving any clearance
and metal clamp (2).
Indoor unit (Drain socket)
If an old drain hose or an elbow or a clamp is used, it may Taped part
cause water leakage.
• Insulate the piping that goes through indoors. Drain hose (1) (accessory)
CAUTION
• To avoid the attached drain hose (1) getting excessive
force, do not bend nor twist it.
(It may cause water leakage.)
• Do not connect the drain piping directly to the sewage that Metal clamp (2) (accessory)
gives off ammonia odor.
The ammonia in the sewage may go through the drain pip-
Fix the metal clamp (2) so that the screw
ing and corrode the heat exchanger of the indoor unit. head faces downward. Fig. 31
< Caution to be taken when carrying out upward drain
piping > • Do not tighten the metal clamp (2) with the torque more
• The maximum height of the drain riser is 600mm. than the specified value.
• Install the drain riser vertically. (Refer to Fig. 29) The socket, the drain hose (1), the elbow (10) or the metal
clamp (2) may be damaged.
Fix the metal clamp (2) so that the tightened part may be
in the range shown by Fig. 32.
3. Wrap the vinyl tape around the end of the metal clamp
(2) so that the sealing material (large) (8) to be used
at the next process may not be damaged with the
clamp end or bend the tip of the metal clamp (2)
inward as shown. (Refer to Fig. 32)
English 12
3P177351-7V
24
FXUQ-AVEB EDFMT391732
Bend the tip without tearing If the air outlet 3 is closed, pour water from the air outlet
the sealing material (Large) (8). 2.
Fig. 32-1 Drain outlet for service (with rubber plug)
(Section A - A of Fig. 31) (Use it when draining water in the drain pan)
1
2 Location of drain pump
Vinyl
and float switch
tape
Fig. 33
L N
Earth terminal
Power supply
220 - 240V/220·230V
~
50Hz/60Hz Fig. 35
13 English
3P177351-7V
25
FXUQ-AVEB EDFMT391732
3. Gradually pour 1 liter of water from the air outlet 3 8-3 SPECIFICATION FOR FIELD SUPPLIED FUSES
into the drain pan (Fig. 34) giving caution to avoid AND WIRING
splashing water on the electric components such as Remote controller
drain pump. Power supply wiring wiring
Transmission wiring
If the air outlet 3 is closed, pour water from the air Model
Field
outlet 2. fuses Wiring Size Wiring Size
4. When the power supply is turned on, the drain pump
will operate. Check drainage. Wiring
FXUQ71AVEB Vinyl
size and cord with
(The drain pump will automatically stop after 10 min- H05VV- length
sheath or 0.75 -
utes.) 16A U3G must
cable 1.25mm
2
NOTE 1) comply (2 core)
5. Turn off the power supply after checking drainage, FXUQ100AVEB with local
NOTE 2)
and remove the power supply wiring. codes.
6. Attach the control box lid as before. The lengths of remote controller wiring and transmission wiring
are as follows:
(1) Remote controller wiring (indoor unit - remote controller)....
.......................................................Max. 500m
8. ELECTRIC WIRING WORK (2) Transmission wiring ........... Total wiring length 2000m
• Outdoor unit - Indoor unit ...........Max. 1000m
8-1 GENERAL INSTRUCTIONS • Outdoor unit - BS unit.................Max. 1000m
• Make certain that all electric wiring work is carried out by • BS unit - Indoor unit....................Max. 1000m
qualified personnel according to the applicable legislation • Indoor unit - Indoor unit ..............Max. 1000m
and this installation manual, using a separate dedicated cir- NOTE
cuit. 1. Shows only in case of protected piping. Use H07RN-F in
Insufficient capacity of the power supply circuit or improper case of no protection.
electrical construction may lead to electric shocks or a fire. 2. Vinyl cord with sheath or cable (Insulated thickness : 1mm or more)
• Make sure to install an earth leakage breaker.
Failure to do so may cause electrical shocks and a fire. 8-4 WIRING CONNECTION METHOD
• Do not turn on the power supply (branch switch, branch over- (Refer to Fig. 38)
current breaker) until all the works are finished.
• Multiple number of indoor unit are connected to one outdoor CAUTION FOR WIRING
unit. Name each indoor unit as A-unit, B-unit ….. and the like. • The indoor units in the same system can be connected to the
When these indoor units are wired to the outdoor unit and the power supply from one branch switch.
BS unit, always wiring the indoor unit to the terminal indi- However, selection of branch switch, branch over current breaker
cated with the same symbol on the terminal block. If the wir- and wiring size must be according to applicable legislation.
ing and the piping are connected to the different indoor units • For connection to the terminal block, use ring type crimp
and operated, it will result in malfunction. style terminals with insulation sleeve or treat the wiring
• Make sure to earth the air conditioner. Earthing resistance with insulation. (Refer to Fig. 36)
should be according to applicable legislation. Insulation sleeve
• Do not connect the earth wiring to gas or water piping, light- Wiring
ning conductor or telephone earth wiring. Ring type crimp style terminal
• Gas piping ............ Ignition or explosion may occur if the
gas leaks.
• Water piping ......... Hard vinyl tubes are not effective
Fig. 36
earths.
• Lightning conductor or telephone earth wiring ................. • Connect the terminal as shown in Fig. 37.
• Do not carry out soldering finish when stranded wires are
............................. Electric potential may rise abnormally
if struck by a lightning bolt. used. (Otherwise, the loosening of wires may result in
• For electric wiring work, refer to also the “WIRING DIA- abnormal heat radiation.)
GRAM” attached to the control box lid.
• Carry out wiring between the outdoor units, indoor units and
the remote controllers according to the wiring diagram.
• Carry out installation and wiring of the remote controller
according to the “installation manual” attached to the remote
controller.
• Do not touch the Printed Circuit Board assembly. It may
cause malfunction.
Model Hz Volts
Voltage
MCA MFA kW FLA (Abnormal heating may occur if the wirings are not tightened securely.)
range
• Use the required wiring, connect them securely and fix these
FXUQ71AVEB 50 220-240 Max. 264 0.6 16 0.046 0.5
wiring so that external force may not apply to the terminals.
FXUQ100AVEB 60 220·230 Min. 198 1.4 16 0.106 1.1 • Use a proper screw driver for tightening the terminal screws.
MCA: Min. Circuit Amps (A) ; MFA: Max. Fuse Amps (A) If an improper screw driver is used, it may damage the
kW: Fan Motor Rated Output (kW) ; FLA: Full Load Amps (A) screw head and a proper tightening cannot be carried out.
English 14
3P177351-7V
26
FXUQ-AVEB EDFMT391732
• If a terminal is over tightened, it may be damaged. • Remote controller wiring, transmission wiring.
Refer to the table shown below for tightening torque of terminals. Connect the remote controller wiring to [P1 · P2] and the trans-
mission wiring to [F1 · F2] of the terminal block (X1M) for
Tightening
torque (N · m) remote controller and transmission wiring. Bind the remote
Terminal block for remote controller and
controller wiring and the transmission wiring with the clamp (4).
0.88 ± 0.08 • Sticking non woven fabric (15).
transmission wiring
Terminal for power supply 1.47 ± 0.14 To prevent wiring from floating, stick non woven fabric (15).
Earth terminal 1.47 ± 0.14
CAUTION
• Do not carry out soldering finish when stranded wiring are used. • Never connect the power supply wiring to the terminal
block for remote controller/transmission wiring (X1M).
• Power supply wiring, earth wiring It may damage the total system.
Remove the control box lid, match the symbol to that of the • Do not connect the remote controller/transmission wiring
power supply terminal block (X2M) and connect the wiring. to the wrong terminal block.
Connect the earth wiring also to the power supply terminal
block (X2M). Then, lead the wiring into the indoor unit
through the hole bored on the cover for penetrating piping
according to the section “6. REFRIGERANT PIPING WORK”
and bind the wiring with the clamp (4).
15 English
3P177351-7V
27
FXUQ-AVEB EDFMT391732
WARNING
• When wiring, form the wiring orderly so that the control box
lid can be securely fastened.
If the control box lid is not in place, the wiring may float up
or be sandwiched by the box and the lid and cause electric L N P1P2F1 F2 T1 T2
shocks or a fire.
Indoor unit A
8-5 WIRING EXAMPLES
< No.1 system: When 1 remote controller is used for 1 indoor unit > P1P2
Power supply
220-240V/
Remote controller
220·230V (option)
~ Fig. 42
50Hz/60Hz
L N
IN/D OUT/D NOTE
F1 F2 F1 F2
• Remote controller wiring and transmission wiring do not have
Outdoor unit
polarity.
Most WARNING
Indoor downstream
Be sure to install an earth leakage circuit breaker.
unit B Indoor unit
Failure to do so may cause electric shocks and a fire.
L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2
Indoor
unit A
P1 P2 P1 P2 P1 P2
English 16
3P177351-7V
28
FXUQ-AVEB EDFMT391732
8-6 FOR CONTROL WITH 2 REMOTE CONTROL- 8-8 FOR REMOTE CONTROL (FORCED OFF OR ON/
LERS (TO CONTROL 1 INDOOR UNIT WITH 2 OFF OPERATION)
REMOTE CONTROLLERS) (1) Wiring method and specification
• For control with 2 remote controllers, set one remote control- • Remote control is available by connecting the external
ler as main and the other remote controller as sub. input to the terminals T1 and T2 on the terminal block for
< Changeover method from main to sub and vice versa > remote controller and transmission wiring.
Refer to the installation manual attached to the remote con-
troller.
< Wiring method > F2 T1 T2
(1) Remove the control box lid according to the “8-4 WIRING FORCED
CONNECTION METHOD”. OFF
(2) Carry out additional wiring from the remote controller 2
(Sub) to the terminals (P1·P2) for remote controller wir-
Input A
ing on the terminal block (X1M) in the control box.
Terminal block (X1M) for Wiring specification Sheathed vinyl cord or 2 core cable
remote controller wiring (P1, P2)
Wiring size 0.75-1.25mm
2
No polarity
Wiring length Max. 100m
External contact Contact that can make and break the
specification min. load DC15V · 1mA
(2) Actuation
• Input A of FORCED OFF and ON/OFF OPERATION will
be as the table shown below.
In case of FORCED OFF by input Remote controller per-
FORCED A of “ON” (Remote mitted by input A of
OFF controller prohibited) “OFF”
In case of
Remote controller 1 Remote controller 2 ON/OFF Operation by input A of Stop by input A of
(Main) (Sub) OPERA- “OFF” “ON” “ON” “OFF”
Fig. 43 TION
< Caution > (3) How to choose FORCED OFF or ON/OFF OPERATION
When using the group control and the 2 remote controllers • For choosing FORCED OFF or ON/OFF OPERATION, set-
control at the same time, connect the remote controller 2 ting by remote controller is required.
(Sub) to the indoor unit at the end of the crossover wiring (the (Refer to “10. FIELD SETTING AND TEST OPERATION”)
largest No.). (Refer to Fig. 44)
17 English
3P177351-7V
29
FXUQ-AVEB EDFMT391732
9. MOUNTING CORNER COVER · SUC- • After attaching the suction grille in opposite order mentioned
in the clause “4. PREPARATION BEFORE INSTALLATION -
TION GRILLE
(3)” (Refer to Fig. 47-(1)), hook the strap (a) for preventing
For test operation without the corner cover, first refer to the suction grille from falling. (Refer to Fig. 47-(2))
“10. FIELD SETTING AND TEST OPERATION” • Hook the strap (b) for preventing the suction grille from fall-
• For backward and rightward piping outlet, cut the corner ing. (Refer to Fig. 47-(3))
cover as shown in Fig. 45 and remove it.
(When cutting, give caution and mount on the indoor unit so
that the parts for the corner cover may not fall off.) Hook the strap on the nearer one
Corner cover
(2)
(1)
(2)
For rightward piping outlet
Strap (a) for
Piping penetrating place preventing
Cut with a saw blade. the suction grille
Give caution so from falling
that it may not fall Hook the strap
off.
(3)
Corner cover
(3)
Fig. 45
Fig. 46
English 18
3P177351-7V
30
FXUQ-AVEB EDFMT391732
< FIELD SETTING > 10-4 SETTING FAN SPEED DURING THERMOSTAT
After turn on the power supply, carry out field setting from OFF
the remote controller according to the installation state. • Set the fan speed according to the using environment after
• Carry out setting at 3 places, “Mode No.”, “FIRST CODE No.” consultation with your customer.
and “SECOND CODE No.”. • When the fan speed is changed, explain the fan speed rate to
The settings shown by “ ” in the table indicate those your customer.
when shipped from the factory.
Table 4
• The method of setting procedure and operation is shown in
the installation manual attached to the remote controller. FIRST SECOND
(Note) Though setting of “Mode No.” is carried out as a Setting Mode No.
CODE No. CODE No.
group, if you intend to carry out individual setting by LL (Extra
Fan speed during 01
each indoor unit or confirmation after setting, carry cooling thermo- low) 12 (22) 6
out setting with the Mode No. shown in the parenthe- stat OFF Setting 02
sis ( ).
Fan speed during LL (Extra
• In case of remote control, for changeover of input to 01
heating thermo- low) 12 (22) 3
FORCED OFF or to ON/OFF OPERATION. stat OFF Setting 02
[1] Enter into the field setting mode with the remote controller.
[2] Select Mode No. “12”.
[3] Set the FIRST CODE No. to “1”. 10-5 SETTING FILTER SIGN
[4-1] For FORCE OFF, set the SECOND CODE No. to “01”. • A message to inform the air filter cleaning time will be indi-
[4-2] For ON/OFF OPERATION, set the SECOND CODE cated on the remote controller.
No. to “02”. • Set the SECOND CODE No. shown in the Table 5 according
(It is set to FORCED OFF when shipped from the factory.) to the amount of dust or pollution in the room.
• Ask your customer to keep the instruction attached to the • Though the indoor unit is equipped with the long life filter, it is
remote controller together with the operation manual. necessary to periodically clean the filter to avoid clogging of
• Do not carry out setting other than those shown in the table. the filter. Please also explain the set time to the customer.
• The periodical filter cleaning time can be shortened depend-
10-1 SETTING OF CEILING HEIGHT ing on the environment.
• Set the SECOND CODE No. according to the ceiling height Table 5
as shown in the Table 3.
Table 3 SEC-
FIRST
Filter hours OND
Contamination Mode No. CODE
Ceiling height (m) FIRST (long life type) CODE
Mode SECOND No.
Setting CODE No.
FXUQ71AVEB FXUQ100AVEB No. CODE No.
No. Approx.
Normal 01
Standard 2.7 or less 3.2 or less 01 2500 hrs
0
High More contami- Approx.
2.7 - 3.0 3.2 - 3.6 02 10 (20) 02
ceiling 1 13 (23) 0 nated 1250 hrs
High With indication 01
3.0 - 3.5 3.6 - 4.0 03 3
ceiling 2 No indication* 02
* Use “No indication” setting when cleaning indication is not
10-2 SETTING WHEN AN OPTIONAL ACCESSORY IS necessary such as the case of periodical cleaning being car-
ried out.
ATTACHED
• For setting when attaching an optional accessory, refer to the 10-6 SETTING AIR DISCHARGE DIRECTION
installation manual attached to the optional accessory. • When changing air discharge setting (2-way or 3-way dis-
charge), set the SECOND CODE No. as shown in the Table
10-3 WHEN USING WIRELESS REMOTE CONTROL-
6.
LER
• When using a wireless remote controller, it is necessary to Table 6
set the wireless remote controller address. FIRST CODE SECOND
Refer to the installation manual attached to the wireless Setting Mode No.
No. CODE No.
remote controller. 4-way air
01
discharge
3-way air
13 (23) 1 02
discharge
2-way air
03
discharge
19 English
3P177351-7V
31
FXUQ-AVEB EDFMT391732
CAUTION
After test operation is completed, check the items men-
tioned in the clause 2 “2. Items to be checked at delivery”
on page 3.
If the interior finish work is not completed when the test
operation is finished, for protection of the air conditioner,
ask the customer not operate the air conditioner until the
interior finish work is completed.
If the air conditioner is operated, the inside of the indoor
units may be polluted by substances generated from the
coating and adhesives used for the interior finish work and
cause water splash and leakage.
English 20
3P177351-7V
32
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
●Specifications, designs and other content appearing in this brochure are current as of September 2017 but subject to change without notice.