STRUCTURAL SPECIFICATION

PROJECT: PROPOSED TWO STOREY RESIDENCE


LOCATION: B27 LOT 11PHASE 6 STA. BARBARA VILLAS 1, SILANGAN, SAN
MATEO
STRUCTURAL DESIGN CRITERIA
a. Design stresses

Concrete @ 28 days
Foundation, RW f’c = 3,000 psi (21 MPa)
Columns &
Retaining walls f’c = 3,000 psi (21 MPa)
Beams & Slabs f’c = 3,000 psi (21 MPa)
Curbs & Slab on Grade f’c = 2,500 psi (17 MPa)

Reinforcing bar astm a615


Grade 40 (for ø12 & smaller) fy = 40,000 psi (276 MPa)
Grade 60 (for ø16 & larger) fy= 40,000 psi (276 MPa)

Structural steel ASTM A36 fy = 36,000 psi

Soil bearing capacity


1.5m from FGL q = 2000 psf* ( 95.76 KPa)

b. Design Live Loads

Floor Load:
Common Area / Residential 100 psf
Roof Load 12 psf

c. Load Combination
d. References
National Structural Code of the Phil., 2010
Uniform Building Code 1997
AISC steel manual 9th ed.
ACI 318-99