EUROPEAN STANDARD EN 1253-1

NORME EUROPÉENNE
EUROPÄISCHE NORM May 2003
DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

ICS 91.140.80 Supersedes EN 1253-1:1999

English version

Gullies for buildings - Part 1: Requirements

Avaloirs et siphons pour bâtiments - Partie 1: Abläufe für Gebäude - Teil 1: Anforderungen
Spécifications

A
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

This European Standard was approved by CEN on 20 February 2003.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national

versions. SIJ
standards may be obtained on application to the Management Centre or to any CEN member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the official

CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United
Kingdom.
MI
KO

EUROPEAN COMMITTEE FOR STANDARDIZATION


COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: rue de Stassart, 36 B-1050 Brussels

© 2003 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1253-1:2003 E
worldwide for CEN national Members.
EN 1253-1:2003 (E)

Contents
DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

page
Foreword......................................................................................................................................................................3
1 Scope ..............................................................................................................................................................3
2 Normative references ....................................................................................................................................3
3 Terms and definitions....................................................................................................................................4
4 Loading strength............................................................................................................................................7
5 Places of installation .....................................................................................................................................8

A
5.1 General............................................................................................................................................................8
5.2 Exceptions ......................................................................................................................................................8
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

6 Nominal sizes .................................................................................................................................................8


7 Materials..........................................................................................................................................................8
8
8.1
8.2
8.3
8.4
8.5
8.6
SIJ
Design and construction...............................................................................................................................9
General............................................................................................................................................................9
Appearance.....................................................................................................................................................9
Depth of water seal ........................................................................................................................................9
Resistance of water seal to pressure ..........................................................................................................9
Apertures in gratings.....................................................................................................................................9
Blockage prevention: trapped gullies........................................................................................................10
8.6.1 Access for cleaning .....................................................................................................................................10
8.6.2 Self-cleansing capacity ...............................................................................................................................10
MI
8.6.3 Anti-blockage ...............................................................................................................................................10
8.7 Side inlets .....................................................................................................................................................10
8.8 Thermal behaviour.......................................................................................................................................10
8.8.1 Temperature cycling for floor gullies ........................................................................................................10
8.8.2 Additional mounting conditions and test conditions for gullies for use with sheet floor
covering ........................................................................................................................................................10
8.8.3 Roof outlets ..................................................................................................................................................11
8.8.4 Behaviour when exposed to hot bitumen or asphalt ...............................................................................11
8.9 Tightness ......................................................................................................................................................11
KO

8.9.1 Odourtightness: trapped gullies ................................................................................................................11


8.9.2 Watertightness for gully bodies .................................................................................................................11
8.9.3 Gullies and roof outlets for use with a membrane ...................................................................................11
8.9.4 Gullies for use with a sheet floor covering ...............................................................................................11
8.9.5 Gullies with factory fixed skirt membrane ................................................................................................11
8.9.6 Watertightness for extensions ...................................................................................................................12
8.10 Mechanical strength ....................................................................................................................................12
8.10.1 Extensions for gullies for use with sheet floor covering.........................................................................12
8.10.2 Membrane clamping ring ............................................................................................................................12
8.10.3 Gullies with factory affixed skirt membrane .............................................................................................12
8.11 Flow rates .....................................................................................................................................................12
8.11.1 Water through the grating...........................................................................................................................12
8.11.2 Water through the grating and side inlets.................................................................................................13
8.11.3 Water through the side inlet .......................................................................................................................13
8.12 Roof outlets for siphonic drainage systems.............................................................................................13
8.12.1 Fitness for the purpose ...............................................................................................................................13
8.12.2 Coefficient of hydraulic loss.......................................................................................................................13
9 Marking .........................................................................................................................................................14
10 Quality control..............................................................................................................................................14
Annex A (informative) A-Deviation ..........................................................................................................................15

2
EN 1253-1:2003 (E)

Foreword
DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

This document (EN 1253-1:2003) has been prepared by the Technical Committee CEN/TC 165 "Wastewater
engineering", the secretariat of which is held by DIN.

This European Standard shall be given the status of a national standard, either by publication of an identical text or
by endorsement, at the latest by November 2003, and conflicting national standards shall be withdrawn at the latest
by November 2003.

This document supersedes EN 1253-1:1999.

A
Annex A is informative.
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Czech Republic, Denmark, Finland,

1 Scope
SIJ
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands, Norway, Portugal,
Slovakia, Spain, Sweden, Switzerland and the United Kingdom.

This standard classifies gullies, gives guidance for places of installation and specifies requirements for the con-
struction, design, performance and marking of factory made gullies for buildings, irrespective of material, for use in
drainage systems operating under gravity including siphonic systems.
MI
NOTE Although normally used to convey domestic wastewater, industrial wastewater and rainwater, gullies can convey
other wastewater provided there is no risk of damage to components or of injury to health.

This standard does not apply to gully tops and manhole tops which are specified in EN 124.

2 Normative references
KO

This European Standard incorporates by dated or undated reference, provisions from other publications. These
normative references are cited at the appropriate places in the text, and the publications are listed hereafter. For
dated references, subsequent amendments to or revisions of any of these publications apply to this European
Standard only when incorporated in it by amendment or revision. For undated references the latest edition of the
publication referred to applies (including amendments).

EN 124, Gully tops and manhole tops for vehicular and pedestrian areas - Design requirements, type testing,
marking, quality control

EN 476, General requirements for components used in discharge pipes, drains and sewers for gravity systems.

prEN 1253-2:2002, Gullies for buildings — Part 2: Test methods.

EN 1253-3, Gullies for buildings — Part 3: Quality control.

3
EN 1253-1:2003 (E)

3 Terms and definitions


For the purposes of this European Standard, the following terms and definitions apply.

3.1
gully
DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

discharge fitting the top of which is a grating or cover capable of installation at ground, floor or roof level, intended
to receive wastewater either through apertures in the grating and/or from pipes connected to the body of the gully
(see figure 1)

NOTE A gully can include an integral trap and a sediment bucket (see figure 2).

3.2
side inlet gully
gully with one or more integral inlets for underfloor or underground connections (see figure 2)

3.3

A
roof outlet
non-trapped gully, used in a roof (see figure 3)
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

NOTE A roof outlet can include an anti-vortex device.

SIJ
MI

Key
2 Membrane clamping ring
4 Grating/cover and frame
KO

5 Spigot
6 Body
8 Membrane
10 Extension
12 Sheet floor covering
Figure 1 — Gully, non-trapped (typical example)

4
EN 1253-1:2003 (E)
DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

A
Key
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

1 Finished floor
3 Sediment bucket
4
5
6
7
8
9
11
14
Grating/cover and frame
Spigot
Body
Side inlet
Membrane
Access for cleaning
Connecting flange
Depth of water seal
SIJ
Figure 2 — Side inlet gully, trapped (typical example)
MI
KO

Key
4 Grating/cover and frame
6 Body
8 Membrane
11 Connecting flange
13 Roof layer

Figure 3 — Roof outlet (typical example)

5
EN 1253-1:2003 (E)

3.4
grating
removable component with apertures which permit the discharge of wastewater

3.5
frame
DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

support for a grating or cover which is connected to a body either directly or by means of a membrane clamping
collar or an extension

3.6
cover
removable part of an access cover which covers the opening

3.7
body
part of a gully below or in the floor, ground or roof on which the grating/frame/extension is mounted, and to which
pipework is connected

A
3.8
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

extension
component used to adjust the height of a grating or cover above a body

3.9
membrane clamping ring

SIJ
component used to clamp a membrane or a sheet floor covering to a body or extension

3.10
joint
connection between the adjacent ends of two components including the means of sealing

3.11
connecting flange
MI
separate or an integral part of a body or of an extension which receives a membrane or sheet floor covering

3.12
nominal size (DN)
numerical indication of size which is a convenient integer approximately equal to the internal diameter (DN/ID) or
the external diameter (DN/OD) in millimetres

3.13
KO

external diameter
mean external diameter of the pipe barrel at any cross section

3.14
internal diameter
mean internal diameter of the pipe barrel at any cross section

3.15
gravity drainage system
system where flow is caused by gravity and where the pipe normally operates partially full

3.16
trap
removable or integral part of the body which prevents, by means of water seal the passage of foul air from the
outlet to the inlet

3.17
depth of water seal
effective height of water in the trap (h) which prevents the passage of foul air (see figure 2)

3.18
domestic wastewater
non-faecal wastewater discharged from appliances in kitchens, laundry rooms, lavatories, bathrooms and similar
facilities

6
EN 1253-1:2003 (E)

3.19
industrial wastewater
wastewater resulting wholly or partially from any industrial or commercial activity

3.20
sheet floor covering
DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

flexible watertight finished layer for floors affixed to the flange by bonding and/or by means of a clamping ring

3.21
membrane
watertight and/or damp proof layer attached to the gully either in the floor or on the floor or roof

3.22
head of water
distance a of a water line over the spill edge of the gully as shown in figure 4

A
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

SIJ
Figure 4 — Head of water

3.23
MI
siphonic drainage system
system for drainage of rainwater in which the outlets and pipework enable the system to flow completely full under
design conditions and make use of the total height available between the outlets and the point of change to
partially filled flow

4 Loading strength
KO

Gullies are classified by loading strength, when tested in accordance with prEN 1253-2:2002, clause 4 into
following classes: H 1,5, K 3, L 15, M 125.

Gullies not accessible to either vehicular or foot traffic or not required to withstand external loads are not classified.

7
EN 1253-1:2003 (E)

5 Places of installation

5.1 General

A guide for selecting the class of gully appropriate to the place of installation is given below. The selection of the
DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

appropriate class is the responsibility of the specifier.

Class H 1,5
Unused flat roofs such as felt-and-gravel roofs, gravel fill roofs and similar.

Class K 3
Areas without vehicular traffic, such as bathrooms in dwellings, old peoples' homes, hotels, schools, swimming
baths, public wash and shower facilities, balconies, loggias, terraces and roofs with greenery.
Non-load bearing gullies in bathrooms shall fulfill the requirements of class H 1,5.

A
Class L 15
Areas with light vehicular traffic, excluding fork-lift trucks, in commercially used premises.
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

Class M 125
Areas with vehicular traffic, such as car parks, factories and workshops.

5.2 Exceptions
SIJ
Class C 250 to F 900 gullies and tops conforming to EN 124 shall be used for all areas subject to special stresses,
such as exhibition halls, market halls, factory sheds and aircraft hangars.

Non-load bearing gratings for places of installation, which are not accessible to vehicles and pedestrians (protected
by suitable masonry surroundings) and which are not covered by the places of installation listed above nor by
EN 124, shall at least conform to the test requirements given in prEN 1253-2:2002, clause 4, Class H 1,5.
MI
6 Nominal sizes
Recommended nominal sizes are defined by internal diameter of outlet (DN/ID) and by external diameter of outlet
(DN/OD) as follows.

Nominal sizes DN/ID:


30; 40; 50; 70; 75; 100; 125; 150; 200
KO

Nominal sizes DN/OD:


32; 40; 50; 63; 75; 90; 100; 110; 125; 160; 200

NOTE Other nominal sizes which are at present in use are permissable, but they may be reconsidered in the future.

7 Materials
Materials shall withstand domestic wastewater up to a temperature of 95 °C and industrial wastewater as specified
by the specifier.

Materials for roof outlets shall be resistant to rainwater, UV radiation, local climatic conditions and, when needed, to
hot bitumen.

Materials shall withstand the stresses likely to occur during installation and operation.

Gullies made of materials which are not inherently corrosion-resistant shall be protected by corrosion prevention
treatment.

8
EN 1253-1:2003 (E)

8 Design and construction

8.1 General

Gullies shall be capable of being connected to pipework systems covered by relevant European Standards and,
when installed in accordance with the manufacturer's instructions, shall form an integral part of the building. There
DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

shall be no movement possible between the gully and the floor or roof construction, which would impair the
functioning of the installed gully.

In areas where pressure testing of the pipe system is necessary gullies for use in the ground floor shall enable such
test to be performed.

The upper surfaces of frame and grating shall be flush, except in unused flat roofs. When in position, it shall not be
possible for gratings and covers to be dislodged from the frame, but they shall be easy to release.

Bell traps shall be prevented from floating or becoming displaced by a design feature such as fixing or weight.

A
Gullies and their components shall be resistant to normal actions of mechanical, chemical and thermal character.
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

Gullies shall be delivered with installation instructions.

All joints to and from the gully shall be designed to be watertight in accordance with EN 476.

8.2 Appearance
SIJ
Internal and external surfaces shall be free from sharp edges and imperfections which could impair functioning of
the gully or give risk of injury to persons.

8.3 Depth of water seal


MI
Trapped gullies for wastewater shall provide a minimum depth of water seal of 50 mm and shall be tested in
accordance with prEN 1253-2:2002, 5.1.

8.4 Resistance of water seal to pressure

When tested in accordance with prEN 1253-2:2002, 5.2 the applied pressure which just causes passage of air shall
be > 400 Pa.

Gullies with sediment buckets with water seals of a depth of > 60 mm are deemed to satisfy this requirement.
KO

8.5 Apertures in gratings

Apertures can be holes or slots of any shape.

Permissible aperture dimensions for gratings are given in table 1.

Table 1 — Apertures in gratings

Dimensions of apertures in gratings


Class Minimum Maximum
mm mm
a
H 1,5 6 15
K 3 6 10 (max. 8 mm in barefoot areas)
L 15b 6 15 (max. 8 mm in barefoot areas)
M 125b 6 25
a
) Where a gravel guard is incorporated the maximum can be up to 25 mm.
b) In commercially used premises, gratings may also be used with apertures up to 31 mm x 31mm.

In commercially used premises, gratings may also be used with apertures up to 31 mm × 31 mm.

9
EN 1253-1:2003 (E)

Gratings for installation in unused flat roofs shall project not less than 30 mm above the roof covering. If the height
of any subsequent surfacing cannot be specified, the grating shall project not less than 70 mm above the
connecting surfaces. Dimensions shall be tested in accordance with prEN 1253-2:2002, clause 6.

NOTE Where situation dictates appropriate means can be provided to prevent the ingress of fine particles such as gravel
into a roof outlet.
DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

8.6 Blockage prevention: trapped gullies

8.6.1 Access for cleaning

Trapped gullies should have provision for mechanical cleaning of the outlet pipe systems leading to and from the
gully. When an opening with an airtight and watertight cover or plug is provided, the clear diameter of such opening
shall not be less than 32 mm in a gully having a nominal outlet size of DN 110 or below, and not less than 50 mm in
a gully of nominal outlet size DN 125 to DN 200.

Any opening provided for mechanical cleaning shall be tested in accordance with prEN 1253-2:2002, 7.1.

A
8.6.2 Self-cleansing capacity
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

The self-cleansing capacity of gullies which cannot be cleaned when installed by removing the trap, or by an
access for cleaning according to 8.6.1 shall be tested in accordance with prEN 1253-2:2002, 7.2.

SIJ
When tested in accordance with prEN 1253-2:2002, 7.2, the expelled volume of glass beads for each of the flow
rates in the interval between 0,3 l/s and 0,6 l/s shall be greater than that indicated by the straight line between the
two end points 0 % at 0,3 l/s and 50 % at 0,6 l/s. Expulsion of glass beads shall commence at a flow rate less than
0,3 l/s, and at least 50 % of the glass beads shall have been expelled at a flow rate of 0,6 l/s.

8.6.3 Anti-blockage
MI
Gullies and their components shall not be liable to clogging. Gullies with gratings or covers removed shall be
capable of accommodating the passage of a 8 mm diameter ball when tested in accordance with
prEN 1253-2:2002, 7.3.

8.7 Side inlets

There are two types of gully with side inlets as follows:

Type I:
KO

side inlets either partially or totally below the water level;

Type II:
side inlets completely above the water level.

The positioning of side inlets shall be checked in accordance with prEN 1253-2:2002, clause 8.

8.8 Thermal behaviour

8.8.1 Temperature cycling for floor gullies

All floor gullies and their components shall be resistant to a wastewater temperature when tested in accordance
with prEN 1253-2:2002, 9.1.1.

8.8.2 Additional mounting conditions and test conditions for gullies for use with sheet floor covering

Floor gullies for use with sheet floor covering shall be tight when tested in accordance with prEN 1253-2:2002,
9.1.2.

10
EN 1253-1:2003 (E)

8.8.3 Roof outlets

Roof outlets and their components shall be resistant to the influence of weather conditions. They shall be frost
resistant to at least - 20 °C and heat resistant to not less than 80 °C when tested in accordance with
prEN 1253-2:2002, 9.2.
DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

8.8.4 Behaviour when exposed to hot bitumen or asphalt

Gullies exposed to hot bitumen or asphalt during installation shall be resistant to a temperature of (220 ± 5) °C
when tested in accordance with prEN 1253-2:2002, 9.3.

8.9 Tightness

8.9.1 Odourtightness: trapped gullies

When tested in accordance with prEN 1253-2:2002, 10.1 the pressure shall not drop below 180 Pa over a period of

A
15 min.
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

8.9.2 Watertightness for gully bodies

Bodies shall be watertight when subjected to a pressure of 0,01 MPa (100 mbar or 1 meter height water column).

8.9.3 Gullies and roof outlets for use with a membrane SIJ
No leaks shall be observed when tested in accordance with prEN 1253-2:2002, 10.2.

Gullies and roof outlets for use with a membrane shall be fitted with a connecting flange in accordance with table 2.

Table 2 — Connecting flanges


MI
Minimum effective flange widths
mm
Connecting flange with
Type of seal in the flange area
counter-flange Flange for Flange for
a bonding welding
fixed ) loose

Bitumen covering
– bonded - - 100 -
KO

– clamped 70 60 - -
Membranes and roof coverings made of plastics or
elastomers
- attached with adhesive - - 100 -
- clamped 50 40 - -
- welded on membrane - - - 50
a
) This value is also applicable to gullies fitted with a skirt membrane at the manufacturer`s works.

For gullies where a clamping collar without weepholes is used, the connection of the flange shall be tight when
tested in accordance with prEN 1253-2:2002, 10.3.1 or 10.3.2 as appropriate.

8.9.4 Gullies for use with a sheet floor covering

Gullies for use in floor constructions where the floor covering is a watertight synthetic material such as PVC shall
be fitted with a sealing flange in accordance with table 2, and/or with a membrane clamping collar and shall be
watertight when tested in accordance with prEN 1253-2:2002, 10.3.1 or 10.3.2 as appropriate.

8.9.5 Gullies with factory fixed skirt membrane

Gullies with factory fixed skirt membranes attached to the body shall be watertight when tested in accordance with
prEN 1253-2:2002, 10.2.

11
EN 1253-1:2003 (E)

8.9.6 Watertightness for extensions

Where the situation dictates tightness between extension and body, the joint between extension and body shall be
watertight when tested in accordance with prEN 1253-2:2002, 10.2.

8.10 Mechanical strength


DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

8.10.1 Extensions for gullies for use with sheet floor covering

Gullies with extensions which are intended for non-imbedded use where deformations between gully and extension
may occur shall be tested in accordance with prEN 1253-2:2002, 10.4.1 and shall afterwards comply with the
requirement of 8.9.2.

8.10.2 Membrane clamping ring

When tested in accordance with prEN 1253-2:2002, 10.4.2 the clamping ring shall not be dislodged.

A
8.10.3 Gullies with factory affixed skirt membrane
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

When tested in accordance with prEN 1253-2:2002, 10.4.3 no peeling shall occur.

8.11 Flow rates

8.11.1 Water through the grating SIJ


When tested in accordance with prEN 1253-2:2002, 11.1 gullies shall be capable of discharging at rates given in
table 3. For roof outlets for use with siphonic systems see table 4.

Table 3 — Minimum flow rates for gullies and conventional (i.e. non-siphonic) roof outlets
MI
Nominal size of outlet Floor gullies Conventional roof outlets

DN/OD DN/ID Flow rate Head of water a Flow rate Head of water a
l/s mm l/s mm
32 30 0,4 - -
40 40 0,6
- -
50 50 0,8 0,9
KO

63 0,8 1,0
75 70 0,8 1,7
20 35
90 75 0,8
100 1,4
110 100 1,4 4,5
125 125 2,8 7,0 45
160 150 4,0 8,1
200
NOTE: Where a trapped gully without side inlets is used to receive the discharge from a single shower head the
minimum flow rate of 0,4 l/s is applicable in accordance with EN 274-1.

12
EN 1253-1:2003 (E)

8.11.2 Water through the grating and side inlets

When tested in accordance with prEN 1253-2:2002, 11.2 floor gullies shall be capable of discharging at flow rates q
given below.

a) gullies up to DN 63 with one or more side inlets:


DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

1) qfloor see table 3

2) qside  0,8 l/s

3) qside = 0,8 l/s and qfloor  0,3 l/s (a = 20 mm)

b) gullies equal or greater DN 70 with one or more side inlets:

1) qfloor see table 3

A
2) qside  0,8 l/s (each side)
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

3) qside and qfloor = 0,8 l/s + 0,6 l/s (a = 20 mm)

4) qside 1 and qside 2 = 0,8 l/s + 0,3 l/s.

8.11.3 Water through the side inlet SIJ


When tested in accordance with prEN 1253-2:2002, 11.2 the least favourably placed side inlet shall be capable of
passing a minimum flow rate of 0,8 l/s.

8.12 Roof outlets for siphonic drainage systems


MI
8.12.1 Fitness for the purpose

When tested in accordance with prEN 1253-2:2002, 11.3.2 the roof outlets shall be capable of discharging at the
minimum flow rates given in table 4.

Table 4 — Minimum flow rates for roof outlets for siphonic drainage systems
KO

Nominal size of the spigot of roof outlet Minimum flow rate at a maxi-
mum head of water a of
55 mm a)
DN/OD DN/ID
l/s

40 2,5
40 3
50 4
50 6
75 70 12
75 14
a
) The effective flow rate of a roof outlet for siphonic drainage system depends on the specific
installation conditions and results from the calculation of the system using the coefficient of hydraulic
loss in accordance with prEN 1253-2:2002, 11.3.3.

8.12.2 Coefficient of hydraulic loss

For designing a siphonic drainage system, the coefficient of hydraulic loss of the complete ready for use roof outlet,
with and without possible extensions, shall be determined in accordance with prEN 1253-2:2002, 11.3.3.

13
EN 1253-1:2003 (E)

9 Marking
Gullies and their components shall bear the following clear and durable markings, for example, cast on, by
engraving, painting, stamping or labelling (see table 5):

a) EN 1253;
DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

b) name and/or mark of the manufacturer;

c) period of manufacture (coded or not);

d) identification of independent certification body, where applicable;

e) identification of DN, classes.

Further marking may be added (e.g. for the application). The marking shall be visible where possible, after the unit
is installed.

A
Table 5 — Location of marking of gullies
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

a
Gully body Grating Components ) Packaging

EN 1253
Name/mark of
manufacturer
Period of manufacture
Independent
b
certification body )
x
x
x
x
SIJ x
x
x
x

x
x

Loading class x x
MI
Class: Side inlet x
DN x
a
) where possible
b
) where applicable

When the application of the marking would be detrimental to the production and/or functioning of the product, the
marking shall be included on the packaging.
KO

10 Quality control
The quality control shall be provided as given in EN 1253-3.

NOTE Annex A (informative) of EN 1253-3 gives information in the case that third party control is carried out.

14
EN 1253-1:2003 (E)

Annex A
(informative)

A-Deviation
DOZVOLJENO SAMO ZA JEDNOG KORISNIKA. ZABRANJENO UMNOŽAVANJE I KORIŠCENJE NA MREŽI !

A-deviation: National deviation due to regulation, the alteration of which is for the time being outside the
competence of the CEN Member.

This European Standard is not covered by a European Directive. In the relevant CEN country this A-deviation is
valid instead of the provision of the European Standard until it has been removed.

A
With regard to this European Standard covered by Directive 90/531/EEC the national A-deviation has been
requested by Denmark with reference to the following national regulation:
ZA RAD KOMISIJE, G. DUŠAN PAJOVIC, 1. jun 2011

Danish Building Regulation BR 1995


(published by the National Building and Housing Agency)

Clauses

4 Loading strength SIJ


According to Danish Building Regulations, DS 432, clause 2.3.10, gratings, used in areas where it is a requirement
that rats shall not be allowed to pass through gullies, shall be fastened with screws or in some other way. Gratings
shall be made of materials which cannot be destroyed or penetrated by rats and which shall pass the following
method of test.
MI
The gully shall be placed as prescribed in prEN 1253-2:2002, 4.4. The grating is loaded in the centre or at the inner
edge by a force of 20 N perpendicular to the surface and in the opposite direction in which the grating is mounted

The grating shall not loose firm contact to the gully body in any situation.

8.7 Side inlets


KO

According to Danish Building Regulations BR 95 and BR S 98, DS 432, only type II gullies are permitted.

15