Project: L&T Parel Phase 2 (LTPP)

Revision: 0
ESTIMATED ELECTRICAL LOAD CALCULATIONS
Prep.: SM
Chd SM

Sr. Conn. Demand Load DG Load DG Load Remarks for DG backup in Mains Power
Description Area in sq.ft Area in sq.m Watt/Sq.m Diversity
No. Load (KW) (KW) (MPF case) (Fire case) Failure (MPF) and Fire Case

A Tower B (Flats)
i 2 BHK S 124 599 56 75.00 4.18 0.4 1.67
517.7 207.09 No DG power No DG power
backup for backup in
ii 2 BHK L 108 721 67 75.00 5.03 0.4 2.01 Flat case of fire
542.8 217.10

iii 2 BHK L 124 725 67 75.00 5.05 0.4 2.02


626.6 250.65

iv 2 BHK L 62 726 67 75.00 5.06 0.4 2.02


313.7 125.50

v 3 BHK S 54 912 85 75.00 6.36 0.4 2.54


343.3 137.31

vi 3 BHK L 62 997 93 75.00 6.95 0.4 2.78


430.9 172.34

vii 3 BHK L 62 1,083 101 75.00 7.55 0.4 3.02


468.0 187.21

Total Load for-Flats in Tower B 3,243.01 1,297.20 0.00 0.00

B Tower A (Flats)
i 2 BHK S 108 599 56 75.00 4.18 0.4 1.67
450.9 180.37 No DG power No DG power
backup for backup in
ii 2 BHK L 124 721 67 75.00 5.03 0.4 2.01 Flat case of fire
623.2 249.27

iii 2 BHK L 124 725 67 75.00 5.05 0.4 2.02


626.6 250.65

iv 3 BHK S 62 880 82 75.00 6.13 0.4 2.45


380.3 152.12

v 3 BHK S 62 865 80 75.00 6.03 0.4 2.41


373.8 149.53

vi 3 BHK L 54 987 92 75.00 6.88 0.4 2.75


371.5 148.60

vii 3 BHK L 62 997 93 75.00 6.95 0.4 2.78


430.9 172.34

Total Load for-Flats in Tower A 3,257.19 1,302.88 0.00 0.00

Total load for FLAT TOWER A & B 6,500.20 2,600.08 0.00 0.00

II Electrical Load for Common Services of TOWERS

Sr. No. of Conn. Demand Load DG Load DG Load Remarks for DG backup in Mains Power
Description Area in sq.ft Area in sq.m Watt/Sq.ft Diversity
No. Flat Load (KW) (KW ) (MPF case) (Fire case) Failure (MPF) and Fire Case
Common Services for Tower B
3 Common area ( Lift Lobby +Corridor) 1,377 128 0.5 42.7 0.9 38.4 38.4 7.7
4 Terrace Floor 15,451 1,436 0.5 7.7 0.5 3.9 0.0 0.0
100% DG Backup both the case of MPF and
5 Stair Case (77 Landings * 18W LED)* 2 Staircases 5.5 0.9 5.0 5.0 5.0
in case of Fire.
50% DG Backup in case of MPF and only one
6 Lift - 13 Nos. 585.0 0.7 409.5 292.5 45.0
lift considered in case of Fire.
7 Fire Booster Pump 0.0 1.0 0.0 0.0 0.0
8 Pressurization Fans 767.0 1.0 0.0 0.0 767.0

Total for Common Services of Tower B 1,407.97 456.78 335.92 824.67

Common Services for Tower A


3 Common area ( Lift Lobby +Corridor) 1,377 128 0.5 42.7 0.9 38.4 38.4 7.7
4 Terrace Floor 5.0 0.5 2.5 2.5 0.5
100% DG Backup both the case of MPF and
5 Stair Case (77 Landings * 18W LED)* 2 Staircases 5.5 0.9 5.0 5.0 5.0
in case of Fire.
50% DG Backup in case of MPF and only one
6 Lift - 13 Nos. 585.0 0.7 409.5 292.5 45.0
lift considered in case of Fire.
7 Fire Booster Pump 0.0 1.0 0.0 0.0 0.0
8 Pressurization Fans 767.0 1.0 0.0 0.0 767.0

Total for Common Services of Tower A 1,405.24 455.42 338.42 825.17

Total for Common Services TOWER A & B 2,813.21 912.19 674.33 1,649.85
Project: L&T Parel Phase 2 (LTPP)
Revision: 0
ESTIMATED ELECTRICAL LOAD CALCULATIONS
Prep.: SM
Chd SM

Sr. Conn. Demand Load DG Load DG Load Remarks for DG backup in Mains Power
Description Area in sq.ft Area in sq.m Watt/Sq.m Diversity
No. Load (KW) (KW) (MPF case) (Fire case) Failure (MPF) and Fire Case

Common Services

Basement & Podium Car park 100% DG Backup in case of MPF and 20 %
703,950.00 65,422.86 0.50 32.71 0.80 26.17 26.17 5.23
(P1 & GF excluded as shops) DG backup in case of Fire.

Plumbing System 302.00 0.60 181.20 181.20 0.00 100% DG Backup in MPF case.

STP 150.00 0.70 105.00 105.00 0.00 100% DG Backup in MPF case.

Fire Fighting System 622.00 0.90 0.00 0.00 559.80 100% DG Backup in case of Fire.

HVAC
Lower Ground ventilation 195.30 0.70 136.71 0.00
100% DG Backup both the case of MPF and
Car park Ventilation Axil Fans 396.00 0.70 277.20 554.40 554.40
200% in case of Fire.
Parking Jet Fans 198.00 0.50 99.00 99.00 198.00 100% DG Backup in case of Fire.
789
Shops 117,240.00 10,892 200.00 198.00 0.67 132.00 0.00 0.00 No DG Backup
Street Lighting 5.27 1.00 5.27 0.00 0.00 No DG Backup
external/Landscape Lighting 5.00 1.00 5.00 0.00 0.00 No DG Backup

Grand Total 11418 3967 966 1317

1 Transformer Selection for Common Services


Total demand load for Common Services 3,966.92 kW
Overall diversity @ 0.80
Maximum demand load for Common Services 3,173.53 kW
kVA @ 0.9 PF 3,526.15 KVA
Transformer Rating @ 80 % loading 4,407.69 KVA

2 DG Selection Common Services & Tower B


Total demand load for Common Services 2,142.11 kW
Overall diversity @ 0.80
Maximum demand load for Common Services 1,713.69 kW
Overall power factor 0.80
Max. demand load for Common Services in kVA 2,142.11 kVA
DG Set Rating @ 85 % loading 2,520.13 kVA

3 DG Selection Tower A
Total demand load for Common Services -Tower 825.17 kW
Overall diversity @ 0.80
Maximum demand load for Common Services - 660.14 kW
Overall power factor 0.80
Max. demand load for Common Services -Tower 825.17 kVA
DG Set Rating @ 85 % loading 970.79 kVA

Number of Transformers
Description
(with 80% Loading)

3 nos. 1600 kVA Dry type


Transformers
Transformer
(Transformer selection shall be confirmed by Utility)

Number of DG SET (with


Description
85% Loading)
DG Selection Common Services & Tower B 1no. 2500 kVA Transformer
DG Selection Tower A 1no. 1010 kVA Transformer