SUPPORT STRUCTURE FOR SINGLE STAND 33KV VOLTAGE TRANSFORMER MK'CVT/5'
GENERAL NOTES
QUALITY OF STEEL =ASTM A36 OR A500
QUALITY OF BOLTS & NUTS ‐ ASTM A325 OR A394
DESIGN SHALL CONFORM TO ‐ BS 5950: PART 1 2000
DESIGN WIND SPEED V ‐ 44.40 M/sec
WIND PRESSURE FOR STRUCTURE P ‐ SF X 6.1084 X 10^ ‐4 X V2
AND EQUIPMENT 2 X 6,1084 X 10^ ‐ 4 X 44.40^2
2.408371 kPa
245.5 kg/sq.Mtr
2.4 kN/m2
WIND PRESSURE ON INSULATOR & CONDUCTOR P = SF X 6.1084 X 10^ ‐4 X V2
0.6 X 6.1084 X 10^ ‐4 X 44.40 2
0.722511 kPa
73.65 Kg/Sq.Mtr
0.72 kN/m2
OVERLOAD FACTOR 1.5
EQUIPMENT TO EQUIPMENT CONNECTION CENTIPEDE (BS‐215(part 1):1970 AAC
AREA OF CONDUCTOR 415.2 mm2
OUTSIDE DIA 0.027 m
MASS OF CONDUCTOR ‐ 1.145 kg/m
SPAN 3m
WIND LOAD PER MTR. OF CONDUCTOR 0.027x0.72x1.0 kN/m2 ‐ 0.02 kN/m
STATIC TENSION ON TERMINAL 0.6 kN
SHORT CIRCUIT TENSION ON TERMINAL 1.5 kN
BOND STRESS BETWEEN STEEL & CONCRETE (M:20) t 1.2 N/mm2
COMPRESSIVE STRENGHT OF CONCRETE fcu 20 N/mm2
WEIGHT OF CONDUCTOR PER PHASE 0.03 KN
TOTAL WEIGHT OF CONDUCTORS 0.10 KN
WIND LOAD ON CONDUCTOR 0.06 KN
MECHERINT LTD, ABUJA 1 30th OCTOBER 2017
STEDY ENGINEERING LTD, LAGOS STRUCTURE FOR 33KV CT OR VT 2X30/40MVA 132/33KV
MK'CVT/5' SUBSTATION OKITIPUPA
I DATA FOR STRUCTURE LOADING CALCULATIONS
REFERENCE STRUCTURE LOADING DIAGRAM
DETAILS OF EQUIPMENT
MAKE PRAGATI HGT‐30
DRG.NO. ETHG‐090
HEIGHT OF EQUIPMENT 1375 mm
HEIGHT OF TERMINAL FROM BASE OF EQUIPMENT 1200 mm
DIAMETER OF EQUIPMENT 300 mm
SELF WEIGHT OF EQUIPMENT 175 Kg
C.G. OF EQUIPMENT = 687.5 mm
DETAILS OF STRUCTURE
HEIGHT OF STRUCTURE FROM PLINTH LVL 2580 mm
WIDTH OF STRUCTURE (A/A) 540 mm
WIDTH OF STRUCTURE (B/B) 540 mm
NO. OF PANELS 2.5
HEIGHT OF PANELS 900 mm
LENGTH OF BRACING 557 mm
MOUNTING HOLES 4No ‐ 450X 450 mm
Dia OF MOUNTING HOLE ‐ 18 mm
WEIGHT OF STRUCTURE IN Kg 213.6 Kg
WEIGHT OF STRUCTURE IN KN 2.1 KN
TOTAL WEIGHT OF EQUIPMENT ON STRUCTURE 5.1 KN
EXPOSED AREAS CALCULATION
FRONT VIEW
EQUIPMENT
HEIGHTXWIDTH 0.41 m2
WIND PRESSURE STRUCTURE 2.4 KN/m2 EQUIPMENT AND CONDUCTOR 0.72 KN/m2
STRUCTURE FRONT VIEW LONGITUDINAL
NO. OF TOTAL
MEMBER EXPOSED AREA
PCS AREA
m m Sq.Mtr
W L
LEG 0.070 2.480 2 0.347
BRACING 0.045 0.557 5 0.125
SUPPORT BRACKET 0.045 0.749 2 0.067
BOOM 0.07 2.694 1 0.189
BRACING 2 0.045 0.57 1 0.026
CHANNEL 0.1 0 6 0.000
TOTAL 0.754 m2
WING FORCE ON STRUCTURE 1.8 kN
TOTAL
TRANSVERSE
NO. OF TOTAL
MEMBER EXPOSED AREA
PCS AREA
m m Sq.Mtr
W L
LEG 0.070 2.480 2 0.347
BRACING 0.045 0.557 5 0.125
SUPPORT BRACKET 0.045 0 2 0.000
BOOM 0.07 0 1 0.000
BRACING 2 0.045 0 1 0.000
CHANNEL 0.1 0.68 1 0.068
TOTAL 0.541 m2
WING FORCE ON STRUCTURE 1.3 kN
MECHERINT LTD, ABUJA 2 30th OCTOBER 2017
STEDY ENGINEERING LTD, LAGOS STRUCTURE FOR 33KV CT OR VT 2X30/40MVA 132/33KV
MK'CVT/5' SUBSTATION OKITIPUPA
WIND FORCES
TRANSVERSE (Y‐DIRECTION)
EQUIPMENT 0.297 kN
ON STRUCTURE 1.3 kN
CONDUCTOR 0.06 kN
1.7
LONGITIDUNAL (X‐DIRECTION)
EQUIPMENT 0.9 kN
ON STRUCTURE 1.8 kN
2.7
WEIGHTS
WEIGHT OF EQUIPMENT 5.1 kN
WEIGHT OF STRUCTURE 2.1 kN
ERECTION LOAD (WT OF MAN + 80kG TOOLS) = 1.5 kN
TOTAL VL+EL = 8.74 kN
MOMENT ARMS
Wind load on 3.78 m
Structure 2.1 KN
X‐Direction 1.8 KN
Y‐Direction 1.3 KN
1.29 m
FV FX FY Mx My
1 VL+ST+WX 7.2 3.3 0 7.5 0
2 VL+ST+WY 7.2 0.6 1.3 2.3 2.6
3 VL+SCT+WX 7.2 4.2 0 11 0
4 VL+SCT+WY 7.2 1.5 1.7 5.7 2.9
5 VL+ST+EL 8.7 0.6 0 2.3
LOAD CASES 3 AND 4 ARE THE WORST CASES AND USED FOR OUR ANALYSIS
DESIGN OF LEG MEMBER
LONGITIDUNAL DIRECTION CASE 3 D 0.54 c 0.0193
MOMENTS AT PLINTH LVL DUE TO, EFF. WIDTH FORCE =
kN m M (kNm) W (m) M/2W (kN)
WIND ON CONNECTOR 0 3.78 0.00 D‐2c
WIND ON EQUIPMENT 0.891 3.3 2.91
WIND ON STRUCTURE 1.8 1.29 2.33
CONDUCTOR MOMENT 0.03 1.5 0.05
SHORT CIRCUIT TENSION 1.5 3.78 5.67
TOTAL 4.2 10.97 0.5014 10.9 kN
MECHERINT LTD, ABUJA 3 30th OCTOBER 2017
STEDY ENGINEERING LTD, LAGOS STRUCTURE FOR 33KV CT OR VT 2X30/40MVA 132/33KV
MK'CVT/5' SUBSTATION OKITIPUPA
AXIAL LOAD/LEG DUE TO
HORIZONTAL LOAD = 10.9 kN
VERTICAL LOAD (VL+EL)/4 2.2 kN
Ult FORCE
TOTAL LOAD IN COMPRESSION 13.1 kN 19.7 kN
TOTAL LOAD IN TENSION 8.8 kN 13.1 kN
DESIGN OF BRACING/ BELT
AXIAL FORCE IN BRACING = 1.8 /2 cos44 = 1.3 kN
Ultimate AXIAL FORCE 1.95 kN
MECHERINT LTD, ABUJA 4 30th OCTOBER 2017
STEDY ENGINEERING LTD, LAGOS STRUCTURE FOR 33KV CT OR VT 2X30/40MVA 132/33KV
MK'CVT/5' SUBSTATION OKITIPUPA
DESIGN OF BASE
BASE PLATE
COMPRESSION DESIGN
Required Area Axial load/0.6*fcu = 19400/(0.6*20) 1616 mm2
Try 110x110mm plate = 12100 mm2
TENSION DESIGN Ft
L3 L3
L4
t
Moment of Tensile force about Bolt Axis= Section modulus* fy of base plate
ANCHOR BOLT
Check for tensile stress in bolts try 20mm Dia bolt Grade 4.6 of Steel grade S275
TENSILE FORCE IN LEG F = 13.1 kN
ULTIMATE SHEAR PER LEG Fs = 1.6 kN
GROSS AREA OF BOLT = 3.143 cm2
NET AREA OF BOLT At = 2.45 cm2
SHEAR STRENGHT OF BOLT (ps) = 39.2 kN
TENSILE STRENGHT OF BOLT (pt) = 47 kN
Tensile force in leg < Tensile strenght of bolt
Check for Shear stress in bolts
(Fs/ps + Ft/pt) = 0.32 < 1.0 O.K
Shear Stress within limit
Embedded Length
EMBEDDED LENGTH Ld = ∅fs/(4t)
Where t bond stress
∅ Diameter of the bolt = 20 mm
2
fs 41.8 N/mm
Ld = 174 mm
USE 600mm MINIMUM EMBEDDED LENGTH
FOUNDATION LOADING
FV FX FY Mx My
1 VL+ST+WX 7.2 3.3 0.0 7.5 0.0
2 VL+ST+WY 7.2 0.6 1.3 2.3 2.6
3 VL+SCT+WX 7.2 4.2 0.0 10.9 0.0
4 VL+SCT+WY 7.2 1.5 1.7 5.7 2.9
5 VL+ST+EL 8.7 0.6 0.0 2.3
MECHERINT LTD, ABUJA 5 30th OCTOBER 2017
STEDY ENGINEERING LTD, LAGOS STRUCTURE FOR 33KV CT OR VT 2X30/40MVA 132/33KV
MK'CVT/5' SUBSTATION OKITIPUPA
OUTLINE SKETCH SINGLE STAND 33KV CT OR VT SUPPORT
2550
550
2600
550
550
550
BASE
550
ALL DIMENSIONS IN MM
MECHERINT LTD, ABUJA 6 30th OCTOBER 2017