Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

STEDY 

ENGINEERING LTD, LAGOS STRUCTURE FOR 33KV CT OR VT  2X30/40MVA 132/33KV


 MK'CVT/5' SUBSTATION  OKITIPUPA 

SUPPORT STRUCTURE FOR SINGLE STAND 33KV VOLTAGE TRANSFORMER  MK'CVT/5'
GENERAL NOTES
QUALITY OF STEEL                                                                                                =ASTM A36 OR A500
QUALITY OF BOLTS & NUTS                                                                              ‐ ASTM A325 OR A394
DESIGN SHALL CONFORM TO                                                                        ‐ BS 5950: PART 1 2000
DESIGN WIND SPEED V                         ‐ 44.40                  M/sec
WIND PRESSURE FOR STRUCTURE P                         ‐ SF X 6.1084       X      10^ ‐4  X V2
AND EQUIPMENT                    2   X 6,1084        X      10^ ‐ 4  X 44.40^2
                   2.408371                       kPa
                   245.5                               kg/sq.Mtr
2.4 kN/m2
WIND PRESSURE ON INSULATOR & CONDUCTOR      P                   = SF   X  6.1084  X  10^ ‐4   X  V2
                   0.6    X  6.1084   X 10^ ‐4 X 44.40  2
                   0.722511                       kPa
                   73.65                              Kg/Sq.Mtr
0.72 kN/m2
OVERLOAD FACTOR                    1.5

EQUIPMENT TO EQUIPMENT CONNECTION CENTIPEDE  (BS‐215(part 1):1970      AAC
AREA OF CONDUCTOR 415.2 mm2
OUTSIDE DIA                    0.027 m
MASS OF CONDUCTOR  ‐ 1.145 kg/m
SPAN 3m
WIND LOAD PER MTR. OF CONDUCTOR  0.027x0.72x1.0  kN/m2            ‐ 0.02 kN/m
STATIC TENSION ON TERMINAL 0.6 kN
SHORT CIRCUIT TENSION ON TERMINAL 1.5 kN
BOND STRESS BETWEEN STEEL & CONCRETE (M:20)      t 1.2 N/mm2
COMPRESSIVE STRENGHT OF CONCRETE fcu 20 N/mm2
WEIGHT OF CONDUCTOR PER PHASE 0.03 KN
TOTAL WEIGHT OF CONDUCTORS 0.10 KN
WIND LOAD ON CONDUCTOR 0.06 KN

MECHERINT LTD, ABUJA 1 30th OCTOBER 2017
STEDY ENGINEERING LTD, LAGOS STRUCTURE FOR 33KV CT OR VT  2X30/40MVA 132/33KV
 MK'CVT/5' SUBSTATION  OKITIPUPA 

B          STRUCTURE LOADING CALCULATIONS SET OF  CURRENT TRANSFORMERS ON A SINGLE STAND  MK 'CVT/5'

I DATA FOR STRUCTURE LOADING CALCULATIONS
REFERENCE STRUCTURE LOADING DIAGRAM 
DETAILS OF EQUIPMENT
MAKE PRAGATI HGT‐30
DRG.NO. ETHG‐090
HEIGHT OF EQUIPMENT                                                                        1375 mm
HEIGHT OF TERMINAL FROM BASE OF EQUIPMENT                        1200 mm
DIAMETER OF EQUIPMENT                                                                  300 mm
SELF WEIGHT OF EQUIPMENT                                                              175 Kg
C.G. OF EQUIPMENT                                                                       = 687.5 mm

DETAILS OF STRUCTURE
HEIGHT OF STRUCTURE FROM PLINTH LVL 2580 mm
WIDTH OF STRUCTURE (A/A) 540 mm
WIDTH OF STRUCTURE (B/B) 540 mm
NO. OF PANELS 2.5
HEIGHT OF PANELS 900 mm
LENGTH OF BRACING 557 mm
MOUNTING HOLES   4No                                                                   ‐ 450X 450 mm
Dia OF MOUNTING HOLE                                                                  ‐ 18 mm

 WEIGHT OF STRUCTURE IN Kg 213.6 Kg
 WEIGHT OF STRUCTURE IN KN 2.1 KN
TOTAL WEIGHT OF EQUIPMENT ON STRUCTURE  5.1 KN
EXPOSED AREAS CALCULATION
FRONT VIEW
EQUIPMENT
HEIGHTXWIDTH 0.41 m2
WIND PRESSURE STRUCTURE 2.4 KN/m2 EQUIPMENT AND CONDUCTOR 0.72 KN/m2
 STRUCTURE FRONT VIEW LONGITUDINAL
NO. OF  TOTAL 
MEMBER EXPOSED AREA 
PCS AREA
m m Sq.Mtr
W L
LEG 0.070 2.480 2 0.347
BRACING 0.045 0.557 5 0.125
SUPPORT BRACKET 0.045 0.749 2 0.067
BOOM 0.07 2.694 1 0.189
BRACING 2 0.045 0.57 1 0.026
CHANNEL 0.1 0 6 0.000
TOTAL 0.754 m2
WING FORCE ON STRUCTURE 1.8 kN
TOTAL

TRANSVERSE
NO. OF  TOTAL 
MEMBER EXPOSED AREA 
PCS AREA
m m Sq.Mtr
W L
LEG 0.070 2.480 2 0.347
BRACING 0.045 0.557 5 0.125
SUPPORT BRACKET 0.045 0 2 0.000
BOOM 0.07 0 1 0.000
BRACING 2 0.045 0 1 0.000
CHANNEL 0.1 0.68 1 0.068
TOTAL 0.541 m2
WING FORCE ON STRUCTURE 1.3 kN

MECHERINT LTD, ABUJA 2 30th OCTOBER 2017
STEDY ENGINEERING LTD, LAGOS STRUCTURE FOR 33KV CT OR VT  2X30/40MVA 132/33KV
 MK'CVT/5' SUBSTATION  OKITIPUPA 

WIND FORCES
TRANSVERSE (Y‐DIRECTION)
EQUIPMENT 0.297 kN
ON STRUCTURE 1.3 kN
CONDUCTOR 0.06 kN
1.7
LONGITIDUNAL (X‐DIRECTION)
EQUIPMENT 0.9 kN
ON STRUCTURE 1.8 kN
2.7
WEIGHTS

WEIGHT OF EQUIPMENT 5.1 kN
WEIGHT OF STRUCTURE 2.1 kN
ERECTION LOAD  (WT OF MAN + 80kG TOOLS)          = 1.5 kN
TOTAL    VL+EL         = 8.74 kN

MOMENT ARMS

Wind load on  5.1 KN Static/     Short circuit tensions 


Equipment   0.6 KN 1.5 KN
X‐Direction 0.891 KN 1.5 m
Y‐Direction 0.297 KN 0.03 KN
3.3 m

Wind load on  3.78 m
Structure  2.1 KN
X‐Direction   1.8 KN
Y‐Direction   1.3 KN
1.29 m

LOAD CASES Load HEIGHT


VL VERTICAL LOAD 7.2 kN
ST STATIC TENSION 0.6 kN
SCT SHORT CIRCUIT TENSION 1.5 kN
EL ERECTION LOAD 1.5 kN
WX WIND IN THE X DIRECTION  2.7 kN
WY WIND IN THE Y DIRECTION  1.7 kN

FV FX FY Mx My
1 VL+ST+WX 7.2 3.3 0 7.5 0
2 VL+ST+WY 7.2 0.6 1.3 2.3 2.6
3 VL+SCT+WX 7.2 4.2 0 11 0
4 VL+SCT+WY 7.2 1.5 1.7 5.7 2.9
5 VL+ST+EL 8.7 0.6 0 2.3

LOAD CASES 3 AND 4 ARE THE WORST CASES AND  USED FOR OUR ANALYSIS

DESIGN OF LEG MEMBER
LONGITIDUNAL DIRECTION CASE 3 D 0.54 c 0.0193
MOMENTS AT PLINTH LVL DUE TO, EFF. WIDTH FORCE =
kN m M (kNm) W (m) M/2W (kN)
WIND ON CONNECTOR 0 3.78 0.00 D‐2c
WIND ON EQUIPMENT 0.891 3.3 2.91
WIND ON STRUCTURE 1.8 1.29 2.33
CONDUCTOR MOMENT 0.03 1.5 0.05
SHORT CIRCUIT TENSION 1.5 3.78 5.67
TOTAL 4.2 10.97 0.5014 10.9 kN

MECHERINT LTD, ABUJA 3 30th OCTOBER 2017
STEDY ENGINEERING LTD, LAGOS STRUCTURE FOR 33KV CT OR VT  2X30/40MVA 132/33KV
 MK'CVT/5' SUBSTATION  OKITIPUPA 

TRANSVERSE DIRECTION CASE 4 D 0.54 c 0.0193


MOMENTS AT PLINTH LVL DUE TO, EFF. WIDTH FORCE =
kN m M (kNm) W (m) M/2W (kN)
WIND ON CONNECTOR 0.00 3.78 0.0 0.55
WIND ON EQUIPMENT 0.30 3.3 1.0 2 X 0.017
WIND ON STRUCTURE 1.30 1.29 1.7
CONDUCTOR MOMENT 0.03 1.5 0.1
SHORT CIRCUIT TENSION 1.50 3.78 5.7
TOTAL 3.13 8.4 0.5014 8.3 kN

AXIAL LOAD/LEG DUE TO
HORIZONTAL LOAD                                                                =      10.9 kN
VERTICAL LOAD     (VL+EL)/4                                                        2.2 kN
Ult FORCE
TOTAL LOAD IN COMPRESSION                                13.1 kN 19.7 kN
TOTAL LOAD IN TENSION                                           8.8 kN 13.1 kN

MEMBER DESIGN LEG TRY. L 60X60X6


UNSUPPORTED LENGTH 900.0 mm
CG 16.9 mm
Ag 691 mm2
r 13.7 mm
2
An 209.9 mm
Kl/r 66
pc 201 N/mm2 BS 5950: PART 1 :2000 SECTION 4     TABLE 24   CURVE A
py 235 N/mm2
pb(Bending)  179 N/mm2 BS 5950: PART 1 :2000 SECTION 4    TABLE 16

ULTIMATE COMPRESSIVE STRENGHT pc*Ag= 138.9 kN      > 19.7 kN


ULTIMATE TENSILE STRENGHT py*An= 49.3 kN      > 13.1 kN
Bending pb*Ag= 37.6 kN      > 12.7 kN

DESIGN OF BRACING/ BELT
AXIAL FORCE IN BRACING =  1.8 /2 cos44       = 1.3 kN
Ultimate  AXIAL FORCE 1.95 kN

MEMBER DESIGN LEG TRY. L 45x45x5


UNSUPPORTED LENGTH 646.0 mm
CG 12.5 mm
Ag 390 mm2
r 8.7 mm
An 149.5 mm2
Kl/r 74
pc 191 N/mm2 BS 5950: PART 1 :2000 SECTION 4     TABLE 24   CURVE A
py 235 N/mm2
pb(Bending)  159 N/mm2 BS 5950: PART 1 :2000 SECTION 4    TABLE 16

ULTIMATE COMPRESSIVE STRENGHT pc*Ag= 74.49 kN    > 1.95 kN


ULTIMATE TENSILE STRENGHT py*An= 35.1 kN    > 1.95 kN
Bending pc*Ag= 62.0 kN    > 1.95 kN

MECHERINT LTD, ABUJA 4 30th OCTOBER 2017
STEDY ENGINEERING LTD, LAGOS STRUCTURE FOR 33KV CT OR VT  2X30/40MVA 132/33KV
 MK'CVT/5' SUBSTATION  OKITIPUPA 

DESIGN OF BASE
BASE PLATE
COMPRESSION  DESIGN
Required Area Axial load/0.6*fcu        = 19400/(0.6*20) 1616 mm2
Try 110x110mm plate = 12100 mm2

TENSION DESIGN Ft

L3 L3
L4
t

Moment of Tensile force about Bolt Axis= Section modulus* fy of base plate

t= 6*(Ft*L3) Ft = 13127 N


Fy*L4 L3 = 46.4 mm
L4= 156 mm
fy 410 N/mm2
t= 7.6 mm
USE BASE PLATE (mm) 110X110X10 QUALITY S235

ANCHOR BOLT
Check for tensile stress in bolts  try 20mm Dia bolt Grade 4.6 of Steel grade S275
TENSILE FORCE IN LEG   F                            = 13.1 kN
ULTIMATE  SHEAR PER LEG   Fs         = 1.6 kN
GROSS AREA OF BOLT                                                      = 3.143 cm2
NET AREA OF BOLT  At                                                      = 2.45 cm2
SHEAR STRENGHT OF BOLT (ps)                             = 39.2 kN
 TENSILE STRENGHT OF BOLT (pt)                         = 47 kN
Tensile force in leg < Tensile strenght of bolt
Check for Shear stress in bolts  
(Fs/ps + Ft/pt)      =   0.32  <  1.0 O.K
Shear Stress within limit
Embedded Length
EMBEDDED LENGTH  Ld             =           ∅fs/(4t)             
Where  t bond stress 
∅ Diameter of the bolt =  20 mm
2
fs 41.8 N/mm

Ld          = 174 mm
USE 600mm MINIMUM EMBEDDED LENGTH

FOUNDATION LOADING

FV FX FY Mx My
1 VL+ST+WX 7.2 3.3 0.0 7.5 0.0
2 VL+ST+WY 7.2 0.6 1.3 2.3 2.6
3 VL+SCT+WX 7.2 4.2 0.0 10.9 0.0
4 VL+SCT+WY 7.2 1.5 1.7 5.7 2.9
5 VL+ST+EL 8.7 0.6 0.0 2.3

MECHERINT LTD, ABUJA 5 30th OCTOBER 2017
STEDY ENGINEERING LTD, LAGOS STRUCTURE FOR 33KV CT OR VT  2X30/40MVA 132/33KV
 MK'CVT/5' SUBSTATION  OKITIPUPA 

OUTLINE SKETCH SINGLE STAND 33KV CT OR VT  SUPPORT

2550

550

2600

550
550

550
BASE

550

ALL DIMENSIONS IN MM

MECHERINT LTD, ABUJA 6 30th OCTOBER 2017