Corridor Plumbing Wall Assembly Per UL W304 (AO)
Corridor Plumbing Wall Assembly Per UL W304 (AO)
DLEIHS TAEH
DLEIHS TAEH
1 1-HOUR
WALL plan
A6.7
CB CB
144
1/2" FRAMING PER STRUCTURAL PLANS,
SEE GA FILE AND REPORT LISTED
BELOW FOR MINIMUM
REQUIREMENTS
HEAT SHIELD
146 NOTE:
CONTRACTOR SHALL READ AND BE FAMILIAR WITH
THE GA FILE AND RELATED REPORTS LISTED PRIOR
3. NO
IN
PIPING, WIRE OR CONDUIT
THE AIR SPACE BETWEEN
THE STUDS. RUN ALL SERVICES
TO ASSEMBLY INSTALLATION. THROUGH THE STUDS.
Action. There are locations that include a furred wall for plumbing. RD Olson described the need for gypsum
board on the inside of the wall. VA believes that this can be eliminated with the adoption of UL W304
(http://database.ul.com/cgi-
bin/XYV/template/LISEXT/1FRAME/showpage.html?name=BXUV.W304&ccnshorttitle=Fire-
resistance+Ratings+-
+ANSI/UL+263&objid=1088005542&cfgid=1073741824&version=versionless&parent_id=1073984818&seque
nce=1 ). This assembly eliminates the need for the inner layer of gypsum board.
Nom. 5/8 in. thick gypsum board, paper or vinyl faced with beveled, square, tapered or
rounded edges. Gypsum board nailed to each stud 7 in. OC with 6d cement coated nails, 1-7/8
in. long, 0.0915 in. shank diam and 1/4 in. diam head. As an alternate, No. 6 bugle head
drywall screws, 1-7/8 in. long, may be substituted for the 6d cement coated nails. Gypsum
board may be applied vertically or horizontally. When Items 5 or 5a are used, fastener
length adjusted to accommodate the thickness of the panel. When Items 1a and 2a are used,
the gypsum layer located between Items 1a and the alternating studs, Item 1, may be omitted.
www.veneklasen.com
BXUV.W304 - Fire-resistance Ratings - ANSI/UL 263 Page 1 of 3
BXUV - Fire Resistance Ratings - ANSI/UL 263 Certified for United States
See General Information for Fire Resistance Ratings - CAN/ULC-S101 Certified for Canada
Design Criteria and Allowable Variances
This design was evaluated using a load design method other than the Limit States Design Method (e.g., Working Stress Design
Method). For jurisdictions employing the Limit States Design Method, such as Canada, a load restriction factor shall be used — See
Guide BXUV or BXUV7
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as
Canada), respectively.
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=BX... 1/2/2019
BXUV.W304 - Fire-resistance Ratings - ANSI/UL 263 Page 2 of 3
1. Wood Studs — Nom 2 by 4 in. alternating on opposite sides of nom 2 by 6 in. wood plates. Spaced 16 in. OC max on
each side of wood plates, staggered 8 in. OC (or staggered equally if less than 16 in. OC) on opposite side.
1a. Wood Studs — (Optional) — Nominal 2x4 in. spaced 16 in. on center max, on single 2x4 in. bottom plate with 2x4 in.
top plate.
2. Gypsum Board* — Any 5/8 in. thick UL Classified Gypsum Board that is eligible for use in Design Nos. L501,
G512 or U305 — Nom. 5/8 in. thick gypsum board, paper or vinyl faced with beveled, square, tapered or rounded edges.
Gypsum board nailed to each stud 7 in. OC with 6d cement coated nails, 1-7/8 in. long, 0.0915 in. shank diam and 1/4 in.
diam head. As an alternate, No. 6 bugle head drywall screws, 1-7/8 in. long, may be substituted for the 6d cement coated
nails. Gypsum board may be applied vertically or horizontally. When Items 5 or 5a are used, fastener length adjusted to
accommodate the thickness of the panel. When Items 1a and 2a are used, the gypsum layer located between Items 1a and
the alternating studs, Item 1, may be omitted.
When Furring Channels (Item 7) are used, gypsum board attached to furring channels with 1 in. long Type S bugle-head
steel screws spaced 12 in. OC.
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=BX... 1/2/2019
BXUV.W304 - Fire-resistance Ratings - ANSI/UL 263 Page 3 of 3
2a. Gypsum Board* — Optional — Any 5/8 in. thick UL Classified Gypsum Board that is eligible for use in Design
Nos. L501, G512 or U305 - Installed as described in Item 2.
3. Joints and Nail heads — Not Shown — Gypsum board joints covered with tape and joint compound. Nail heads covered
with joint compound.
4. Batts and Blankets* — Min 3-1/2 in. thick glass or mineral fiber batt insulation woven between alternating studs with a
minimum density of 0.8 pcf. When item 7 is used - A minimum of 6 inches of min. 0.8 pcf glass fiber insulation friction fit in
the stud cavities.
See Batts and Blankets (BZJZ) category for list of Classified companies.
5. Wood Structural Panel Sheathing — (Optional) — Oriented strand board (OSB) or structural plywood applied
vertically or horizontally. Fastened as required by local authority.
5a. Wood Structural Panel Sheathing — (Optional) — Oriented strand board (OSB) or structural plywood applied
vertically or horizontally. Fastened as required by local authority.
7. Furring Channel — Optional - Not Shown - For use on one side of the wall with item 2a - Resilient channels, 25 MSG
galv steel, spaced vertically 24 in. OC, flange portion screw attached to one side of the studs with 1-1/4 in. long diamond
shaped point, double lead Phillips head steel screws.
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification
(such as Canada), respectively.
© 2018 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following
format: "© 2018 UL LLC".
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=BX... 1/2/2019