SecoGear-SecoVac Catalogue English Ed09-11 680878-U
SecoGear-SecoVac Catalogue English Ed09-11 680878-U
Industrial Solutions
SecoGear ™
17.5kV Metal Clad Switchgear
SecoVac ™
3.3kV - 17.5kV
Embedded Pole Vacuum
Circuit Breaker
GE imagination at work
SecoGear™
To date, this interrupter design has been the world leader in vacuum technology and has
accumulated over 45 years of reliable field service.
Precision tooled parts, computer aided design and advanced production techniques, as
well as the protection of the “E Coat” (cathodic electrocoating) paint process has resulted
in a standard of excellence.
Universal Applications
SecoVac is designed, assembled and tested to meet or exceed applicable IEC, GB and DL
standards. It is suitable for applications in all major industries including Transmission and
Distribution (T&D), Oil & Gas, Automotive, Processing plants, Iron and Steel mills, Mining,
Commercial buildings, etc.
It provides protection for all types of applications: cable, overhead lines, motors,
capacitors, transformers, busbar sections, etc.
Environment
Selecting low environmental impact technologies has become increasingly important to
engineers tasked with choosing equipment for an application.
With commitment to environment protection, the solid insulation of epoxy resin is used
for SecoVac series MV embedded pole vacuum circuit breakers instead of SF6 gas.
1
SecoGear™
General
SecoGear metal clad switchgear is designed and manufactured
with advanced technology and has been comprehensively and
successfully type tested by KEMA.
SecoGear switchgear is typically used in power plants,
substations and suitable to provide control and protection for
transformers, capacitors and motors.
The rated voltage of SecoGear is 12kV - 17.5kV and rated
current ranges from 630A to 4000A (4000A has force cooling).
All SecoGear with switching device are equipped with SecoVac
vacuum circuit breaker with corresponding specifications.
2
SecoGear™
3
SecoGear™
Arc-Proof Tested
The metal clad design, sturdy door hinges and lock system,
enables SecoGear to successfully pass 40kA/1s internal
arcing test in accordance with IEC 62271-200 in
all its three primary compartments.
SecoGear metal clad switchgear is designed to meet
protection degree of IP40X as per IEC 60529. The grounded
metal enclosure protects operators from live and moving
parts inside the switchgear. The enclosure is sealed to
eliminate penetration of external objects, which may
cause short-circuit of the system.
4
SecoGear™
Space Heaters
SecoGear offers space heaters in the cable compartment
as a standard feature to avoid condensation inside the
switchgear due to high humidity. Space heaters should
Environmental Conditions
SecoGear is equipped with the following components which
guarantee successful operations under adverse climatic and
environment conditions:
5
SecoGear™
Performance Features
Reliability Safety
The three primary compartments and one secondary SecoGear is designed with a number of interlocking systems
Metal Clad Switchgear
compartment are completely self contained and segregated to prevent mal operation:
from each other, which limits the influence between
compartments and prevents spreading of an arc-fault • The circuit breaker can only be moved from test to connect
between compartments. position and vice versa when the circuit breaker is opened.
• The earthing switch can’t be closed when the circuit
SecoGear is equipped with a quick-action earthing switch breaker is in the connect position and in the traveling
type JN (ESW) with short-circuit making capability. position between test and connect.
A heat-shrinkable material with high dielectric and strength • The cable compartment door can only be opened when
properties insulates the busbar. The main busbar is provided the earthing switch is closed and at the same time the
with inter-unit bushings to prevent travel of arcing to the earthing switch can be opened only when the cable
entire main busbar lineup. compartment door is closed.
SecoGear is equipped with a highly reliable SecoVac vacuum • The secondary plug can only be inserted or removed when
circuit breaker with excellent electrical and mechanical the circuit breaker is in the test position.
performance. The circuit breaker has three positions: • The circuit breaker can only be closed when the circuit
connect, test and disconnect. breaker is precisely in the definite test or connect position.
• When the circuit breaker is removed from connect position,
the metal shutters will close automatically.
Adaptability • The switchgear is internally arc-proof.
SecoGear cable compartment provides ample space for easy • All high primary compartments are provided with pressure
power cable connection. relief flaps located on the topside of the switchgear.
• Any overpressure inside the compartment by internal
Standard current transformers, zero sequence current arcing will be released through the pressure relief flaps.
transformer, voltage transformers, surge arresters, protection
relays and other instruments can be easily installed into the
switchgear.
6
SecoGear™
Technical Data
7
SecoVac™
Vac
Embedded Pole Vacuum Circuit Breaker
Vacuum Circuit Breaker
8
SecoVac™
General
SecoVac series circuit breaker designed by GE Energy is a
three-phase AC indoor breaker with 3.3kV - 17.5kV rated
Terminal disc
Insulator
Fixed contact
Arc
motion
Moving contact
Arching chamber
Metal bellows
Guide
Operating and
Vacuum
connecting bolt
interrupter
9
SecoVac™
C C C
Pole Technology
SecoVac Series MV embedded pole vacuum circuit Our patented LSR (Liquid Silicon Rubber) buffering layer and
breaker uses the latest technology of Automatic Pressure double APG (Auto Pressure Gelatin) Process adopted in the
Gelatin (APG) to embed the vacuum interrupter and connection producing of the embedded pole thoroughly eliminate the
terminals within epoxy resin. The vacuum interrupter is cast cracking of the epoxy resin caused by the large difference
in the epoxy resin, without screw fixation which can cause of the thermal expansion coefficient between epoxy resin
the concentrated harsh electrical field and result in decrease and ceramic in case of rapid changing of the ambient
of the electrical insulation strength of the pole. Thanks to temperature. APG process for LSR buffering layer ensures
the embedded pole technology, the assembly of the pole is that there will not be any air gap or bubble between the
simplified, and the assembly accuracy as well as quality of buffering layer and ceramic housing, hence, the high
the embedded pole is easily controlled by the state of the electrical insulation strength of the embedded pole of
art production process. The embedded pole technology will SecoVac Series MV embedded pole vacuum circuit breaker
also improve the environmental resistant capability of the is guaranteed.
breaker, as the primary circuit of the breaker is completely
embedded inside the epoxy resin, the risk of insulation fault The partial discharge value of embedded pole manufactured
caused by adverse operating environment such as dust, by our patented LSR (Liquid Silicon Rubber) buffering layer
humidity, vermin, polluted ambient and high altitude operating and double APG (Auto Pressure Gelatin) process is below 5 pC
site are eliminated. (Maximum Permissible Partial Discharge) with an applied
testing voltage of 1.2Um.
The key know-how of the embedded pole technology is the
buffering layer between epoxy resin and ceramic housing of
the vacuum interrupter, where the material and processing of
the buffering layer is essential to ensure the integrity of
epoxy resin of the embedded pole providing adequate
adhesion between each other in any circumstance.
10
SecoVac™
The high quality of the embedded pole is achieved by Before delivery, the following
lowing tests and inspections will be
using the latest APG (Auto Pressure Gelatin) technology and done for SecoVac embedded dd d pole
l vacuum circuit bbreaker
k in
advanced vacuum mixing and degassing technology that are the factory by means of advanced testing equipment:
carried out by the equipment. The Vogel clamping machine
is an essential piece of equipment to ensure the mechanical • Dynamic characteristics measurement
and insulating strength of the embedded pole of SecoVac • Power frequency withstand voltage testing
Series MV embedded pole vacuum circuit breaker. • Inspection of interlocking system between
breaker and withdrawable unit
As well as the processing facilities, the testing facilities are • Secondary wiring inspection
also very important to the quality control of the breaker. • Circuit resistance measurement
In the manufacturing process of SecoVac, from incoming
material quality control to the final inspection and testing,
every step is strictly calibrated and tested by means of
testing facilities.
For every embedded pole, before it goes into the breaker
assembly line, it shall go through the following inspections
and testing carried out in the factory:
• X-ray inspection
• Power frequency withstand voltage test
• Partial discharge measurement
• Extremely high and low temperature impulse test
11
SecoVac™
Overall Dimensions
a
b
ØD
f
g
e SecoVac h h
j
户内高压真空断路器
e GE Consumer & Industrial Systems
Vacuum circuit breaker
产品型号
Type designation
出厂编号
Serial number
额定电压 kV
Rated voltage(Ur)
额定电流
A
Rated normal current(Ir)
额定频率 Hz
Rated frequency
k
额 定 雷 电 冲 击 耐 压 (峰值) kV
Rated lightning impulse withstand voltage(Up)
额定短路开断电流 kA
Rated short-circuit breaking current(Isc)
额定短时耐受电流 kA
Rated short time withstand current (4s)
额定电缆充电开断电流 A
l
Rated cable-charging breaking current
电机电压
V
motor voltage
分闸合闸装置电压
Rated supply voltage of closing and opening devices
V 注意!
执行标准
Relevant standarder
高压危险!请严格遵守操作规程。
额定操作顺序 O-0.3s-CO-180s-CO
Warning!
Rated operating sequence
重量 kg High voltage dangerous! Always observe
Weight
the instruction manual and follow the rules.
出厂日期
Manufacture date
上海通用电气开关有限公司
Shanghai GE Breakers Co.,Ltd. 4
n
m
19
p
c q r
d
e
630A / 1250A 1600A / 2000A / 2500A / 630A / 1250A 1600A / 2000A / 2500A /
3150A / 4000A 3150A / 4000A
(mm) 31.5kA (650mm) 40kA (1000mm) (mm) 31.5kA (650mm) 40kA (1000mm)
a 488 838 j 275 310
b 201.5 376.5 k 280 295
c 503 853 l 78 86
d 516 864 m 76 76
e 531 881 n 95.5 95.5
f 498 836 o 637 375
g (456) (794) p 436 361
h 150 275 q 599 586
i Ø 35/49(1) Ø 109 r 200 200
SecoVac L-frame
w d
12
SecoVac™
Withdrawable
11 2 4 47 57 55
V2
13 33 23 53
CC
V1 K0 14 S9 34 S9 24 S9 54 S9
V5 A~
(13) C+ B~
(14) S2 Y4 1
ZC D~
BC
M S4 2
53 54 31 32 16 13 15 17 19 33 37 38 39 18 40 21 22 51 50 12 14 48 49 58 56
36 34 35 20
S1~S3: Energy storing travel switch BC: Electromagnet for locking (optional) TC: Opening coil
S4: Electromagnet for locking auxiliary switch CC: Closing coil V1~V4: Rectifier
S5: Auxiliary switch KO: Anti-pumping relay (optional) ZC: Electromagnet for locking truck (optional)
S8: Limit switch (testing position) M: Energy storing motor
S9: Limit switch (working position)
Notes
1. This wiring diagram describes that a breaker is uncharged and is in an opening state, and the handcart is in the testing position.
2. The polarity in dashed frame should be consistent when the operation voltage is direct current.
Technical Data
Description Unit Data
Rated voltage kV 3.3kV 17.5
Rated current A 630/1250/1600/2000/2500/3150/4000(1)
Rated power frequency withstand voltage (1min) kV 28 38
Rated lightning impulse withstand voltage (peak values) kV 75 95
Rated short-circuit breaking current kA 25/31.5/40
Rated short time withstand current (3s) kA 25/31.5/40
Rated peak withstand current kA 65/82/104
Rated peak making current kA 65/82/104
Capacitor bank switching current A 400
Electrical endurance No. of times 274(E2)
Mechanical endurance No. of times 10,000 (M2)
Operating cycle No. of times O-0.3s-CO-15s-CO
Rated auxiliary control voltage V 24/30/36/48/60/110/125/220V DC 110/220 V AC
Opening time ms 20~50
Breaking time ms 25~35
Closing time ms 30~70
(1) 4000A is 3150A VCB with force cooling
13
SecoVac™
Ordering Information
Coding System of Vacuum Circuit Breaker
Symbol
Operation voltage
Rated voltage (kV)
Anti-pump device
Rated current (A)
Motor voltage
cart blocked
Basic model
14
SecoGear™/SecoVac™
Certificates
TIC 2025-11 TIC 2026-11 2027-11
TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE TYPE TEST CERTIFICATE OF SWITCHING PERFORMANCE TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE
A three-phase moulded-case withdrawable vacuum A three-phase moulded-case withdrawable vacuum A three-phase moulded-case withdrawable vacuum
circuit-breaker in a metal-enclosed Switchgear unit circuit-breaker in a metal-enclosed Switchgear unit circuit-breaker in a metal-enclosed Switchgear unit
15
Protection and control
SR350 SR345
Monitoring and Metering Feeder Protection Transformer Protection
• Fault locator, record of last 10 faults -metering, current, Features: Features:
voltage, power, energy, frequency and harmonics • Phase, neutral and ground • Dual slope, dual breakpoint
• Breaker operation and trip failure TOC and IOC characteristic restrained
• Total breaker arcing current • Undervoltage, overvoltage, differential
• Event recorder - 479 events frequency • Second harmonic inrush and
• High resolution oscillography and data logger, • Neutral/ground directional fifth harmonic over-excitation
with programmable sampling rate • Negative sequence overcurrent inhibits
• Metering: V - I - Hz - W - VA - PF • ANSI, IAC, IEC, flex curves • Instantaneous differential
• Demand: Ia - Ib - Ic - Ig - Isg - I2 - MW - MVA • Cable thermal model protection • Restricted ground fault
• Configurable graphical HMI interface • Breaker failure • Thermal model
• Alarm panel • Cold load pick-up • Neutral timed and instantaneous
• Four-shot auto-reclose overcurrent
• 8 digital inputs, 7 contact • Phase and ground timed and
Protection and Control outputs instantaneous overcurrent
• Time, instantaneous & directional phase, neutral, • Two setting groups • Negative sequence timed
ground and sensitive ground overcurrent overcurrent
• Manual close with cold load pick-up control via • Breaker failure
PLC, forward power and directional power units • Logic elements
• Load encroachment supervision SR339
• Wattmetric ground fault detection
• Positive and negative sequence based over/ Motor Protection
undervoltage elements Features: User Interface
• Four-shot auto-recloser with synchronism check • Thermal model biased with • 4 line display for easy viewing
• Breaker control and breaker failure RTD and negative sequence of key data
• Abnormal frequency protection (rate of change, current feedback • 10 LED indicators for quick
under- and overfrequency) • Phase and ground TOC and IOC diagnostics
• Broken conductor and locked rotor • Start supervision and inhibit • Front USB and rear RS485 serial
• Synchrocheck - V and Hz • Mechanical jam communications
• Up to 64 programmable digital inputs and up • Current unbalance
to 16 digital outputs • Undervoltage / Overvoltage • Multiple communication protocols:
• Trip circuit supervision • Underfrequency / Overfrequency IEC 61850
• Voltage phase reversal IEC 61850 GOOSE,
• Acceleration time MODBUS TCP/IP, MODBUS RTU,
EnerVista™ Software • Undercurrent / Underpower DNP 3.0,
• Sophisticated software for configuration • Starts per hour IEC 60870-5-104, IEC 60870-5-103
and commissioning
• Document and software archiving
• EnerVista™ integrator providing easy
integration of data in the F650 into new or
existing monitoring and control systems Find out more on
http://www.gedigitalenergy.com/multilin/catalog/F650.htm
http://www.gedigitalenergy.com/multilin/catalog/3Series.htm
16
Protection and control
Services
• System integrity protection schemes (SIPS), also called
Power System Protection (PSP) or Wide Area Protection
schemes
17
GE Energy
101783
Industrial Solutions
www.ge.com/ex/industrialsolutions
GE imagination at work
680878
I/3288/E/EX 6.0 Ed. 09/11
© Copyright GE Industrial Solutions 2011