Universal
Overcurrent Relay
P111
P111
MiCOM P111
Universal Overcurrent
Protection Relay
with Communication
T&D
Energy Automation & Information
MiCOM P111
Low Cost Universal Overcurrent
Protection Relay with Communication
2
Table 1 Models available
Codes A B C E F G
3 Phase Overcurrent I>> (DT) 50/51 X X X X X
Output latching 86 X X X X X X
Input S1-S2 X X X X X X
Input T1-T2 X X X X X
2 setting groups X X X X X X
3
- output relays operate, as for Ip>. - LED "Ip>" illuminates, 1) circuit-breaker,
Once the defined time delay has - information is sent to a system via 2) protection-contactor,
elapsed: RS485, 3) bay terminal-contactor.
- circuit breaker or contactor - output relays - see, like for Ip>. Selecting a specific switch type results in
(depending on an application) is P111 operation according to one of the
tripped via P1 output relay, Non-Directional Earthfault following schemes:
- LED "I>" illuminates, Overcurrent Io>> Ad. 1) P1 configured to "circuit-breaker"
- information bit is sent to a system (model:,B, C, E, F, G) mode. If trip of any protection which is
via RS485 link,
Parameters and features of Io>> set to "trip" takes place or a trip signal is
- output relays - see, like for Ip>.
protection are the same as for Io>. sent via RS485, a 0.5s impulse is
Io>> trigger and trip operations are generated (P1 contacts close).
Overcurrent I>> (A, B, C, E, F) indicated by Io> LED indicator. Close operation of the circuit-breaker
This is a 3-phase protection with a DT can be performed through P2 output
characteristic. The protection can clear External Protection ZZ relay, which must therefore be
up faults in applications where either a configured to "close CB" mode. Closing
(model: A, B, C, E)
circuit breaker or a contactor, with a of the CB can be initiated via:
The protection operates if an input state - V1-C input (if configured to "close
capacity to trip short-circuit current is
(S1-S2, T1-T2 or V1-C or CB" command,
used. In a typical contactor application,
V2-C) (see Table 1), which is - "close CB" command sent from
I>> protection should be disabled, for a
programmed to operate in "ZZ" mode, the system via RS485 link.
fuse to clear up short-circuit faults.
changes its state. The protection can be
If the protection is triggered: configured to "trip" or send a "warning If close operation is initiated the P2
- LED "I>>" start flashing, signal" (alarm). Trip operation is contacts are closed for a period of 0.5s.
- timing is commenced, instantaneous and make: Closing of the CB may only be done
- output relays operate, as for Ip>. - circuit breaker or contactor after protection LEDs' have been cleared
Once the defined time delay has elapsed: (depending on an application) trip up, which is in order to prevent from
- circuit breaker or contactor (depending via P1 output relay, multiple switching-onto-fault operations.
on an application) is tripped via P1 output - LED "ZZ" illuminate, Ad. 2) P1 configured to "protection-
relay, - information bit send to a system via contactor" mode. This mode is for
- LED "I>>" illuminates, RS485, applications where a contactor is not to be
- information is sent to a system via - output relays - see, like for Ip>. controlled via Rs485 and P111 is used as
RS485, protection only.
- output relays - see, like for Ip>. Contactor control is performed in a
Overtemperature (input for PTC standard arrangement. After auxiliary
sensors) (model A, B, C, E, F) supply voltage Vx has been applied, the
Non-Directional Earthfault If T1-T2 input is configured as PTC input output relay P1 is closed, and thus allows
Overcurrent Io> (B, C, E, F, G) and resistance of the sensors' loop to close the contactor. Trip of any
This is an overcurrent protection with DT connected to T1-T2 increase, then protection, which is set to "trip" mode,
or IDMT time delay setting, to co-operate protection operates instantaneously. Up makes P1 relay open together with the
with external earthfault ring type to 6 PTC sensors can be connected in contactor. P1 is kept open as long as the
transformers (Ion=1A) or Holmgreen series. The PTC input operates protection and assigned LEDs' are not
residual current arrangement (Ion=5A). instantaneously, thus making: reset. Reset can be done through:
The protection can be programmed to - circuit breaker or contactor - relay keypad,
"trip" or send a "warning signal" (alarm). (depending on an application) trip - binary input S1-S2 (if set to "reset
If IDMT is chosen, then one of the three via P1 output relay, LED and latching" mode),
characteristics can be selected, (SI or VI - LED "PTC" illuminate, - communication link RS485.
or EI acc. to EN 60255-3) - information bit send to a system
If the protection is triggered: via RS485 link,
After reset has been performed the
- LED "Io>" start flashing, - output relays - see, like for Ip>.
contacts of P1 relay close again, thus
- timing is commenced, PTC input may be used to receive other allowing to close the contactor.
- output relays operate, as for Ip>. external signals e.g. from temperature,
Ad. 3) P1 configured to "bay terminal-
If the operating mode is set to "warning Bucholtz-type or other protection
contactor" mode. This mode is for
signal" (alarm), the following events take implemented in an application. If this is
applications where contactor control via
place, after a defined time delay has the case the normally closed output relay
RS485 is requested. V1-C input must be
elapsed: of ZZ external protection should be used
configured to "close" mode and V2-C to
- LED "Io>" illuminates, and connected to terminals T1-T2 of
"switch state" mode.
- information is sent to a system via RS485, P111 relay.
After auxiliary supply voltage Vx has
- output relays P2 or P3 operate been applied, the output relay P1 status
(if they are set to "warning signal"
mode). Relay configuration does not change (P1 contacts remain
Selecting a switch open), as it does when "contactor" mode
If the mode of operation is set to "trip": has been selected.
- circuit-breaker or contactor The main switch is selected by configuring Contactor closing is initiated if:
(depending on an application) is the mode of operation for P1 output relay. - auxiliary supply voltage is applied
tripped via P1 output relay, There are three options available: to binary input V1-C,
4
- "close" command is sent from the status (applies to "protection-contactor" Output Relays (see Table 1)
system via communication link or "bay terminal-contactor" modes), as Depending on a relay version chosen
RS485. well as reset P2 and P3 latched, if set to the following output relays are available:
Closing of the contactor may only be latching. · P1: normally open; terminals:
done, if all tripping signals (LEDs') have "External trip ZZ" mode enables to trip 13-14;
been reset. This feature prevents from the relay from an external protection via · P2: normally open; terminals:
accidental closing of the contactor after S1-S2, T1-T2 inputs. 23-24;
an overcurrent protection have tripped. “blocking of any remote control" mode · P3: normally open; terminals:
Once closing has been initiated P1 disables remote control the relay via 33-34;
closes for a period of 150ms. Then the RS485. · P4: change-over; terminals:
contactor state is checked through its V1-C binary input is controlled by 41-42-44.
auxiliary contacts connected to V2-C applying auxiliary supply voltage Vx to Output relay P1 is used to trip the
input. If contactor is closed the P1 terminals V1-C. main switch (contactor or circuit-
remains closed, too. V1-C input may be configured: breaker). If "bay terminal-contactor"
NOTE: if any protection trips, P1 relay - to close a contactor or circuit- mode is chosen the relay is also used to
instantaneously opens, regardless of breaker: "local CB close" mode; close the contactor. The modes of
actual state of P111 (higher priority of - as an external trip input: “external operation are described in section
"trip" command over "close" command). trip ZZ" mode; "Relay Configuration - Selecting a
The contactor may be opened by: - to block output relays: “blocking of Switch".
- opening the contactor's control any remote control" mode;
Output relay P2 may be configured
circuit (external switch-off contact). - to change between active setting
to the following modes:
Then the contactor, which is groups: “switch settings group”
- "remote or local CB close"; in this
controlled by V2-C input, opens. If mode”.
mode the relay is assigned to
auxiliary supply voltage is “local CB close" mode is meant to
close the circuit-breaker;
interrupted at V2-C input (contactor perform close operation of a contactor
- "trigger of any protection to trip";
switched-off), instantaneous or circuit-breaker. It is enabled if P1 relay
in this mode P2 is assigned to
opening of P1 relay takes place, is configured to "circuit-breaker" or "bay
trigger state of overcurrent
- remote "trip" command via RS485, terminal-contactor" modes and it is
protections (Ip>, I>, I>>, Io>,
which makes P1 relay open, disabled if "protection-contactor" mode
Io>>);
- trip of a protection, which is set to is chosen (for standard arrangements of
- “trip of any protection"; P2 is
"trip" mode. contactor control the protection relay is
assigned to trip state of any
NOTE: Regardless a switch mode chosen, not integrated into the control circuit).
protection, which trips a main
RS485 port may be used to read out the "external trip ZZ" mode: as for S1-S2,
switch (ZZ, PTC, I>, I>>, Io>,
relay status (current values, input / output T1-T2 inputs.
Io>>, Ip>);
status) and to reset the relay after tripping. "Outputs in maintenance state" mode is
- "alarm (warning signal) of any
used to lock all output relays (energising
protection"; in this mode P2 is
Binary Inputs (see Table 1) from protection, inputs are blocked).
assigned to any protection, which
Depending on a relay version, the Such state is kept for as long as auxiliary
is set to "alarm (warning signal)".
following binary inputs are available: supply voltage Vx is present at terminals
· S1-S2, T1-T2 V1-C.
Output relay P3 may be configured
· V1-C and V2-C. V2-C binary input is controlled by
to:
applying auxiliary supply voltage Vx to
- "trigger of any protection to trip"
S1-S2, T1-T2 binary inputs are terminals V2-C. The input may be
mode, same as P2;
controlled by shorting its terminals by configured:
- “trip of any protection" mode,
means of an external contact or switch - for 1 bit indication of a switch
same as P2;
(no auxiliary voltage is required). (circuit- breaker or contactor)
- "alarm (warning signal) of any
Both inputs may be configured: status: "CB state" mode;
protection" mode, same as P2
- to reset latching of output relays - as an external trip input: "external
trip ZZ" mode (same as for - “Io> trip” mode: trip of Io>
and LEDs': “reset of LEDs and
S1-S2, T1-T2); protection .
latchings" mode;
- as an external trip input: "external - to change between active setting Output relay P4 may be configured
trip ZZ" mode; groups: “switch settings group” to:
- to block remote control (via mode”. - "trigger of any protection to trip"
RS485)facility: "blocking of any “CB state" mode may be used to mode, same as P2;
remote control" mode; remotely indicate a switch status to a - “trip of any protection" mode,
- to change between active setting supervisory system via RS485. same as P2;
groups: “switch settings group” NOTE: in order to operate a contactor, - "no protection alarm (warning
mode”; P1 must be configured to "bay terminal- signal)" mode; when this option is
- apart from the above options, contactor" mode and V2-C must be set chosen then supply voltage
T1-T2 may be configured as to “CB state" mode. presence is monitored. P4
PTC sensors input. contacts are energised after
"Reset of LEDs and latchings" mode auxiliary supply voltage Vx is
enables to reset LEDs' and P1 relay applied. If auxiliary supply is
interrupted or if the device fails or
5
tripping of any protection, which Binary inputs
is set to "alarm (warning signal)" Technical Data · S1-S2, T1-T2 input controlled by a
takes place, P4 contacts switch short
back to their original position; Measuring inputs · V1-C, V2-C inputs controlled by
- "relay healthy" indication; in this
(see Table 2 and 3) voltage applied
mode P4 contacts are energised
after auxiliary supply voltage Vx is · Control voltage range:
applied. If auxiliary supply is · Max. nominal network voltage (0.8 ¸ 1.1)Vx, where Vx is auxiliary
interrupted or if the device fails, applied directly to relay (without supply voltage
P4 contacts switch back to their external CT's) 1000V AC · Input burden:
original position; · Frequency range of 0.6 VA for 230V AC/DC
- “Io>> trip” mode: trip of Io>> phase current measurement 0.5 VA for 48V AC/DC
protection . 10 ¸ 1000Hz · PTC input:
P2 and P3 relays may be additionally · Frequency range of earthfault Max. resistance in cold state:
configured to operate in the following 1500W
current measurement 40 ¸ 70Hz
modes: Tripping resistance
· Phase current inputs capacity:
- "without latching"; in this mode if - continuously: 3xIN (3700 ¸ 4000)W
the relay contacts trigger or trip - for 1s: 100xIN Resetting resistance:
due to a fault, they switch back to - for 0.15s: 250xIN (but £10kA) (1900 ¸ 2100)W
their original position once the Max. number of PTC sensors
fault ceases, connected in series: 6
- "latching"; in this mode relay Protection features
contacts switch back to their (See Table 4 and 5)
original position only if trip or User interface
trigger state has been reset. - 4 digit LED display
Reset may be performed: · Inverse time characteristics
acc. to EN 60255-3: - 5 key keypad
- from the front panel keypad,
- standard inverse (SI) - 6 LED indicators
- or via S1-S2 input (if set to “reset
of LEDs and latchings" mode), - very inverse (VI)
- or via RS485 communication link - extremely inverse (EI) Software for setting
· Time delay setting: MiCOM S1 S&R Modbus 2.10.007 or
Communication - Ip>, I>, I>>, Io>, Io>> upper
Communication is performed using (independent settings):
Modbus RTU protocol via RS485 0.02 ¸ 99.90s; step 0.01s
Power supply
halfduplex port (2 wires: ‘Tr+’, ‘Tr-’). · TMS coefficient setting for IDMT
P111 does not incorporate a real time · Nominal auxiliary voltage Vx
characteristics:
clock, therefore all events transmitted via (options):
0.02 ¸ 9.90, step 0.01
RS485 may only be tagged with the (24 ¸ 48) V AC/DC
· Deviations: (60 ¸ 240) V AC/DC
date&time provided by a supervisory Current accuracy index:
control system.. - Ip>, I>: 5% · Voltage tolerance: (0.8 ¸1.1)Vx
Communication port enables: -I>>, Io>, Io>>: 10% · Burden: 4.5VA
· readout of phase and earthfault · Hold time on short auxiliary voltage
current values, interruption:
· readout of input and output states, Time measurement accuracy:
10ms+Tw 230V: AC - 2.2s ; DC - 1.3s
remote reset of LEDs and latched 110V: AC - 0.6s; DC - 0.3s
relays, Operating time Tw: 60ms at I=2xIset,
24V: AC - 0.03s; DC - 0.02s
· contactor or circuit-breaker control via Iset - current setting
RS485, Time index for IDMT: 10
· readout of protections' trigger and trip Communication
Relay outputs .
states, · RS485 halfduplex link
· Up to 4 output relays (3 NO, 1CO)
· readout and write settings, (2 wires "+", "-")
· Contact capacity:
· readout of fault record, · Protocol Modbus RTU
Making, continuously: 5 A
· reset of fault record, · Data rate (1200-19200) bps
· making maintenance state (out of Breaking:
order) or enable of P111, 5A (220V AC, cosj=0.4)
Weight
MiCOM S1 (S&R Modbus) is used for 0.1A (220V DC, L/R=40ms)
~0.5kg
local or remote changing of settings · Mechanical durability
7
10
P111 may be applied as a stand Housing
· Switching capacity
alone device or integrated in a 5
35mm DIN rail or flush mounted
system. Ask for an individual 10
publication: “Modbus Mapping
of P111”.
6
Table 2 Measuring inputs: Phase currents I
Housing Ordering Model Measuring Rated current Burden
(Options) range In
739000xxx31 A, B, C 40¸1000% 1A(5A)** <0.1VA at In
DIN rail* 739000xxx01 A, B, C 40¸1000% 5A (25A)** <0.2VA at In
Mounted 739000xxx11 A, B, C 80¸2000% 5A (50A)** <0.2VA at In
739000xxx21 A, B, C 160¸4000% 5A (100A)** <0.2VA at In
739100xxx41 E, F 50¸3000% 1A <0.2VA at In
739100xxx51 E, F 50¸3000% 5A <0.2VA at In
739001xxx31 A, B, C 40¸1000% 1A <0.1VA at In
Flush 739001xxx01 A, B, C 40¸1000% 5A <0.2VA at In
Mounted 739001xxx11 A, B, C 80¸2000% 5A <0.2VA at In
739001xxx21 A, B, C 160¸4000% 5A <0.2VA at In
739101xxx41 E, F 50¸3000% 1A <0.2VA at In
739101xxx51 E, F 50¸3000% 5A <0.2VA at In
*) For DIN rail mounted version it is possible to widen measuring range of the relay downwards by multiple interleaves of phase wires through the guiding
channels in the relay housing. E.g. a range of 0.5 - 12.5A in the relay with a measuring range of 2 - 50A can be obtained by four interleaves of each of the
phase wires through the relevant channels in the relay housing. If external CT's are used it is possible to extend a measuring range upwards (for both
housing versions).
**) Rated current if primary circuits (up to 1 kV) are directly connected to the relay.
***) It is possible to set the same current range for DT and IDMT characteristics, but IDMT will be cut at the maximum current value within the range. This
means, that time delay for any current value greater than the maximum value within the range will be the same as for the maximum. In case of I>>
protection, the cut of IDMT characteristics is not critical, since I>> threshold is always set below the maximum value of measuring range.
****) Measuring range is switched in menu of relay (software switch)
7
Immunity Frequency range during transport:
Connections Electrostatic discharge 10 to 150Hz, 1g
Threaded terminal ends M3, with wire EN 61000-4-2 level 3 Shock response and withstand test,
protection for conductor cross-sections Radiated electromagnetic energy bump test:
- up to 4mm2 single-core or EN 61000-4-3 level 2 Acc. to IEC 255-21-2 class 1
- up to 2.5mm2 finely stranded Radiotelephone radiated Acceleration 5g/15g
electromagnetic energy
Environmental Conditions EN 50204 level 3
· Degree of device protection Electrical fast transient/burst External CTs’ specification
- Case: IP 40 EN 61000-4-4 level 3 P111 may co-operate with external CTs',
- Terminals: IP 20 Surge test designed for protection applications.
- Front panel for flush EN 61000-4-5 level 3 The accuracy limit factor should be at
mounted case: IP54 1 MHz burst disturbance test least P10 (eg. 5VA 5P10 or 30VA
· Ambient temperature: Acc. to IEC 255-22-1 level 3 10P10, etc.).
Operating temp. (-20 ¸ +60)°C Voltage dips and interruptions CT's power should be greater than a
Storage temp. (-25 ¸ 70)°C Acc. to EN 61000-4-11 sum of power of analogue inputs and
· Ambient humidity range Conducted disturbance inducted by burden of current circuit at the relay's
Relative humidity to preclude any radio frequency fields terminals (resistance of wires, terminals,
condensation Acc. to EN 61000-4-6 level 3 etc.).
95% at 40°C If a range greater than 10IN is used,
Insulation then a CT of rated power greater than
Conformity statement Voltage test calculated should be matched, in order
Between independent circuits for the accuracy limit factor at real load
EC EMC Directive 89/336/EEC
2 kV AC, 50Hz, 60s to be sufficient (that is greater than
EC Low Voltage Directive maximum setting).
73/23/EEC Between contact circuits
1 kV AC, 50Hz, 60s Recommended CTs’ may be ordered
International Standard with the relay from the relay
EN 60255-6 Insulation resistance
manufacturer.
>100MW
Impulse voltage withstand test between
Electromagnetic Compatibility independent circuits
(EMC) 5 kV
Interface suppression
According to EN 55011, level A
Mechanical Robustness
Vibration test:
Creepage distances Acc. to IEC 255-21-1 class 1
and clearances Frequency range during operation:
Per IEC 255-5 group C 10 to 60Hz, 0.035mm
60 to 150Hz, 0.5g
8
Dimensions
111.0
32.5
100.0 5.0 103.0
10.5
P111
L1 kA
23.0 23.0
L2
I>> L3 [S]
I>
75.0
Ip>
Io>
ZZ
PTC
Vx PTC
A1 A2 13 14 21 22 T1 T2 S2 S1
P111
L1 [%]
L2
I>> L3 [S]
106.5
101.5
I>
Ip>
Io>
ZZ
PTC
15
Connection Diagram
V1 V2 C 33 34 41 44 42 1 2 3 4 5 6 V1 V2 C 33 34 41 44 42
L3 L2 L1
P3 P4 Ver. C, E, F P3 P4 Ver. C, E, F
A1 A1
I / O card I / O card
Vx Vx
A2 Version B, C, E, F A2 Version B, C, E, F
P1 P2 Io RS485 P1 P2 Io RS485
13 14 23 24 T1 T2 S1 S2 K L Tr + Tr - 13 14 23 24 T1 T2 S1 S2 K L Tr+ Tr -
33 34 41 44 42
P3 P4
A1
Vx
A2
P1 P2 Io RS485
13 14 23 24 S1 S2 K L Tr + Tr -
Binary RS 485
Io input
contact
input
9
Application examples
PTC
N
L1 L2 L3
PW
PZ
IZ K S1
IZ K S2 Aw
S1
IZ K S1
S2
1 3 5 13 14 21 22 A1 A2
S2
P1 P2
T1
T2
2 4 6 K L S1 S2
k
RESET
l
Fig. 5: P111 model B in flush mounting case, with earthfault protection, without communication, to co-operate with a contactor.
10
"RESET" - Reset of protection trips and triggers
"PW" - Contactor switch-off contact
"PZ" - Contactor switch-on cotact
"Aw" - Protection trip indication
"AL" - Alarm or relay not healthy signal
PTC
N
L1 L2 L3
PW
PZ
Aw AL
13 14 23 24 42 41 V2 V1 C
P1 P2 P3 P4
K L S1 S2 T2 T1 A2 A1
k
l RESET
Fig. 6: P111 model C in DIN rail mounting case, with communication via RS485, to co-operate with a contactor.
11
L1
L2
L3
Circuit-breaker WY ZA
PW
S1
PZ
S2
S1
S2
+AwUp
S1 Aw AL
1 3 5 13 14 23 24 33 34 42 41 V2 V1 C
S2
P1 P2 P3 P4
2 4 6 K L S1 S2 T2 T1 A1 A2
k
RESET
l
PTC
TK
Fig. 7: P111 model E in flush mounting case, with communication via RS485, to co-operate with a circuit-breaker.
12
Ordering information P111
Variants Order No.
739 0 1
Model
A, B, C, G 0
E, F 1
Mounting
35mm DIN rail 0
flush 1
Relay type
A, base model 1
B, base model plus additional input Io, RS485 2
C, base model plus additional input Io, RS485 and I/O board 3
E, base model plus additional input Io, RS485, I/O board, extended measuring range 5
F, base model plus additional input Io, I/O board, extended measuring range 6
G, earthfault protection only, limited model C (without inputs: T1-T2, V1-C, V2-C) 7
Auxiliary supply Vx
60 ¸ 240V AC/DC 0
24 ¸ 48V AC/DC 1
T R A N S M I S S I O N & D I S T R I B U T I O N E n e r g y A u t o m a t i o n & I n f o r m a t i o n , L e S e x t a n t , 3 a v e n u e A n d ré M a l r a u x , 9 2 3 0 0 L e v a l l o i s - P e r r e t . F r a n c e
Tél: +33 (0) 1 41 49 20 00 Fax: +33 (0) 1 41 49 24 85 energy-automation.information@tde.alstom.com www.tde.alstom.com
Contact centre on line 24 hours a day: +44 (0) 1785 25 00 70
ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.
MiCOM is a registered trademark of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies.
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this
brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product
referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.