Type VTT 11, 12

Definite Time Delay Relay


Type VTT 11, 12
Definite Time Delay Relay

Type VTT
with cover removed

Features Description Type VTT 12 units have a delayed


drop-off, i.e., the output relay is
l Consistent accuracy. A stabilised voltage is applied to a normally energised. Timing is
resistance/capacitance circuit. The started by opening an initiating
l Reliability.
potential developed across the contact and the output relay is
l Low burden. capcitor is applied to a transistor deenergised at the end of the set
l Reduced maintenance. switching circuit which, in turn, time. The unit resets when the
operates an attracted armature relay initiating contact is reclosed.
l Immunity to transients and when the potential reaches the
surges; withstands 5 KV impulse trigger level. Technical data
voltage test.
The time delay is varied by altering
l Relays with heavy-duty magnetic the resistance value in the Voltage ratings
blow-out contacts also available. resistance/capacitance circuit by a DC supply
potentiometer calibrated in seconds. 30, 110 or 220V. Satisfactory
Application A circuit is incorporated to protect operation is maintained between
the transistors from damage due to 70% and 130% of rated voltage.
Type VTT static time delay relay is
high peak transients in the supply
particularly suitable for applications Units for use on 110 or 220V are
voltage. A diode is also fitted in the
requiring large number of supplied with a suitable external
circuitry to take care of inadvertent
operations and consistent accuracy resistor.
connection of supply with reversed
with little or no maintenance over
polarity. AC supply
long periods. It is also commonly
used in industrial processes. Type VTT 11 units have a delayed 110, 240 or 415V at 50 Hz. Relays
pick-up, i.e., timing is started by suitable for operation from ac
closing an initiating contact and the supply have a built-in power pack.
output relay is energised at the end Satisfactory operation is maintained
of the set time. The unit resets when between 80% and 115% of rated
the initiating contact is reopened. voltage.
Figure 1:
Basic circuit diagram for VTT 11 relay

Figure 2:
Typical connection diagram for
ac VTT 11 relays

Figure 3:
Typical connection diagram for
dc VTT 11 relays
Timing ranges Within ±5% of setting or ±25 Note
Models with the following setting milliseconds whichever is greater Relays with heavy duty magnetic
ranges (in seconds) — for supply voltage variation for blowout contacts are also
continuously adjustable — are ±30%. Operating tempearture available on request.
available: range –5ºC to +50ºC.

0.05 - 0.5 Operation indicator


0.10 - 1.0 Contacts
A hand reset mechanical flag
0.50 - 5.0 Four pairs of self-reset contacts in operation indicator can be
1.00 - 10.0 any combination of normally provided on the output relay.
2.50 - 25.0 open or normally closed with a
6.00 - 60.0 maximum of 2 normally closed Insulation
12.00 - 120.0 contacts are provided on the The relay meets the requirements
30.00 - 300.0 output attracted armature unit of of IS-3231/IEC 255-5 Series-C-2
VTT 11 relays. Hand reset kV for 1 minute.
Accuracy contacts can be provided. For
Within ±5% of setting or ±10 VTT 12 relays three pairs of self- Impulse voltage
milliseconds whichever is greater, reset contacts with maximum of
The relay complies with the
at nominal voltage and at an 2 normally closed contacts are
requirements of IS-8686/IEC
ambient temperature within the available.
255-4, Appendix-E to Class III.
range of 10ºC and 30ºC.
High frequency interference
Burdens
The relay complies with IS-8686/
(when energised) IEC 255-22-1, Appendix-C to
DC 30V 110V 220V Class III.

Burden (W) 1.26 4.46 9.1 Case


AC 110V 240V 415V The VTT 11 and VTT 12 are
supplied in 1/2N non-drawout
Burden (VA) 2.4 2.3 2.6 moulded cases suitable for flush
mounting. Non-drawout cases
are finished bright black. Relays
Dimensions and weights can also be supplied in drawout
Maximum overall dimensions Approximate cases on request.
Relay Case size Height Width Depth* gross weight Information required
mm mm mm Kg.
with order
VTT 11 or 1/2 N hor. 124 153 130 1.75
1. Relay type (delay on pick-up
VTT 12
or delay on drop-off)
* Add 76 mm for maximum length of terminal studs, alternatively, 2. Timing range
29 mm for terminal screws.
3. Voltage rating
The approximate gross weights given above is inclusive of cartons,
mounting appendages and terminal details. 4. Contact combination
The relays comply fully with the requirements of IS 3231 and are 5. Case
suitable for use in normal tropical environments.

Contact ratings
Make and carry Make and carry Break
continuously for 3 seconds

AC 1250VA with 7500VA with 1250VA with


maxima of 5A maxima of 30A maxima of 5A
and 660V and 660V and 660V

DC 1250W with 7500W with 100W (resistive)


maxima of 5A maxima of 30A 50W (inductive)
and 660V and 660V with maxima of
5A and 660V
ALSTOM Limited Pallavaram Works: 19/1, GST Road, Pallavaram, Chennai-600 043. India.
Tel: 91-044-2368621 Fax: 91-044-2367276 Email: plw.applications@alstom.sprintrpg.eml.vsnl.net.in.
© 1998 ALSTOM Limited

Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should
only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
ALSTOM Limited cannot be held responsible for any reliance on any decision taken on its contents without specific advice

PR:076:0799:A Printed in India.