CONSUMER LIST
Revision: 03
Ashdod Desalination Plant Issued: 14/11/2011
Project:
Title:
CONSUMER LIST
Prepared: CMG
Revised: JPC
Approved: JDC
CONTROL OF CHANGES
Edit. Changes
DISTRIBUTION
INDEX
1.- OBJECT
The object of this document is to present the list of electrical consumers of the Desalination
Plant of Ashdod.
2.1.- GENERAL
The electrical consumers are distributed in two electrical lines and one secure power panel.
Depending on the service of the consumers they pertain to the following switchboards at
different voltage levels:
The electrical consumers are listed in the next section. To each one of them it is provided the
information of the main characteristics showed below:
Equipment tag
Tag name
T T - Aa Bnn - NN
Description
Equipment Group
Equipment Type
Area/Subarea
Process cell
Sequence Num.
Application
Starting method
Indicates the type of starting method of the consumer: soft starter, variable-
frequency drive (VFD) or direct start (DOL).
Pinst (kW)
cos φ
Power factor.
Line type
Indicates the type of the electrical line installed: sigle-phase (M), two-phase (B) or
three-phase (T).
Voltage (kV or V)
Sim. Coef.
Pdem (kW)
Ir (A)
ELECTRICAL BUILDING 1
BOARD B6-I1E01-01
Supply Characteristics Simultaneousness
FROM: TR1
Outlet number Application Equipment tag Starting Pins (kW) cos Voltage Ir (A) Sim. Coef. Pdem (kW)
method (kV)
BOARD B6-I1E02-01
Supply Characteristics Simultaneousness
FROM: B2-I1E02-01
Outlet number Application Equipment tag Starting method Pins (kW) cos Voltage Ir (A) Sim. Coef. Pdem
(kV) (kW)
BOARD B6-I1E03-01
Supply Characteristics Simultaneousness
FROM: B2-I1E03-01
Outlet Application Equipment tag Starting method Pins (kW) cos Line Voltage Ir (A) Sim. Pdem
number type (V) Coef. (kW)
(M,B,T)
TRC TRANSFORMER CONNECTION B6-I1E03-01 2992.50 0.95 T 690 2635.7 1.00 1702.34
N-01 VFD ERD Booster Pump 1 B4-E2R01-01 341.84 0.95 T 690 301.1 0.83 283.72
N-02 VFD ERD Booster Pump 2 B4-E2R02-01 341.84 0.95 T 690 301.1 0.83 283.72
N-03 VFD ERD Booster Pump 3 B4-E2R03-01 341.84 0.95 T 690 301.1 0.83 283.72
N-04 VFD ERD Booster Pump 4 B4-E2R04-01 341.84 0.95 T 690 301.1 0.83 283.72
N-05 VFD ERD Booster Pump 5 B4-E2R05-01 341.84 0.95 T 690 301.1 0.83 283.72
N-06 VFD ERD Booster Pump 6 B4-E2R06-01 341.84 0.95 T 690 301.1 0.83 283.72
N-07 ERD Booster Pump 1 P1-E2R01-01 VFD 331.58 0.85 T 690 326.4 0.83 275.21
N-08 ERD Booster Pump 2 P1-E2R02-01 VFD 331.58 0.85 T 690 326.4 0.83 275.21
N-09 ERD Booster Pump 3 P1-E2R03-01 VFD 331.58 0.85 T 690 326.4 0.83 275.21
N-10 ERD Booster Pump 4 P1-E2R04-01 VFD 331.58 0.85 T 690 326.4 0.83 275.21
N-11 ERD Booster Pump 5 P1-E2R05-01 VFD 331.58 0.85 T 690 326.4 0.83 275.21
N-12 ERD Booster Pump 6 P1-E2R06-01 VFD 331.58 0.85 T 690 326.4 0.83 275.21
Reserve (%)
BOARD B6-I1E04-01
Supply Characteristics Simultaneousness
FROM: B2-I1E04-01
Outlet Application Equipment tag Starting method Pins (kW) cos Line Voltage Ir (A) Sim. Pdem
number type (V) Coef. (kW)
(M,B,T)
TRC TRANSFORMER CONNECTION B6-I1E04-01 2153.67 0.86 T 400 3608.4 1.00 1228.57
N-01 Capacitors B7-I1E04-01 0.12 0.80 T 400 355.5 1.00 0.12
N-04 Feeding to Common Service Panel 5.26 1.00 T 400 7.6 0.95 5.00
N-05 Lighting & Power 52.63 0.85 T 400 89.4 0.95 50.00
N-06 Motorized Valves 15.00 0.85 T 400 25.5 0.80 12.00
N-07 Air Dryers 21.05 0.85 T 400 35.7 0.81 17.05
N-08 Air Compressors 47.37 0.85 T 400 80.4 0.81 38.37
N-09 Transfer Pump 1 P1-E9W01-01 DOL 3.16 0.85 T 400 5.4 0.63 1.99
N-10 Transfer Pump to CIP 1 P1-E9W01-03 DOL 3.16 0.85 T 400 5.4 0.81 2.56
N-11 CIP Pump 1 P1-E9W01-05 soft starter 189.47 0.85 T 400 321.7 0.33 62.53
N-12 Flushing Pump 1 P1-E3W01-01 soft starter 22.00 0.85 T 400 37.4 0.33 7.26
N-13 Flushing Pump 2 P1-E3W02-01 soft starter 22.00 0.85 T 400 37.4 0.33 7.26
N-20 Turbocharger Pump 1 E3-E3R01-01 DOL 14.74 0.85 T 400 25.0 0.95 14.00
N-21 Turbocharger Pump 2 E3-E3R02-01 DOL 14.74 0.85 T 400 25.0 0.95 14.00
N-22 Turbocharger Pump 3 E3-E3R03-01 DOL 14.74 0.85 T 400 25.0 0.95 14.00
N-23 Turbocharger Pump 4 E3-E3R04-01 DOL 14.74 0.85 T 400 25.0 0.95 14.00
N-24 Turbocharger Pump 5 E3-E3R05-01 DOL 14.74 0.85 T 400 25.0 0.95 14.00
N-25 Turbocharger Pump 6 E3-E3R06-01 DOL 14.74 0.85 T 400 25.0 0.95 14.00
N-36 Crane 1 (HPF and HP Pumps) A3-E0M01-01 soft starter 28.00 0.85 T 400 47.5 0.27 7.56
N-37 Crane 3 (RO Building) A3-E0M01-03 soft starter 28.00 0.85 T 400 47.5 0.18 5.04
N-38 Crane 4 (RO Building) A3-E0M01-04 soft starter 28.00 0.85 T 400 47.5 0.18 5.04
N-39 Control and Command 1 0.10 0.85 M 230 0.5 1.00 0.10
N-40 Control and Command 2 0.10 0.85 M 230 0.5 1.00 0.10
GC GENERATOR CONNECTION 1297.09 0.86 T 400 2396.0 1.00 1297.09
E-03 B6-I1E04-03 B6-I1E04-03 1008.16 0.86 T 400 1683.8 0.90 907.35
Reserve (%)
BOARD B6-B2E02-01
Supply Characteristics Simultaneousness
FROM: B2-B2E02-01
Outlet number Application Equipment tag Starting method Pins (kW) cos Voltage Ir (A) Sim. Coef. Pdem (kW)
(kV)
BOARD B6-B2E04-01
Supply Characteristics Simultaneousness
FROM: B2-B2E04-01
Outlet Application Equipment tag Starting Pins (kW) cos Line Voltage Ir (A) Sim. Pdem
number method type (V) Coef. (kW)
(M,B,T)
TRC TRANSFORMER CONNECTION B6-B2E04-01 212.50 0.85 T 400 360.8 1.00 122.21
N-01 Capacitors B7-B2E04-01 0.01 0.80 T 400 41.7 1.00 0.01
N-02 IB UPS Power Supply B3-B2E04-01 20.00 0.85 T 400 34.0 0.59 11.80
N-03 Jellyfish Blower 1 K3-B3A01-01 5.79 0.85 T 400 9.8 0.81 4.69
N-04 Travelling Screen 1 F6-B0T03-01 4.21 0.85 T 400 7.1 0.81 3.41
N-05 Travelling Flushing Pump 1 P1-B0P01-01 soft starter 15.79 0.85 T 400 26.8 0.64 10.11
N-06 Motor Valve SW Intake Pump 1 DN1200-BTMVB0P01-01 0.39 0.85 M 230 2.0 0.30 0.12
N-07 Motor Valve SW Intake Pump 2 DN1200-BTMVB0P02-01 0.39 0.85 M 230 2.0 0.30 0.12
N-08 Motor Valve SW Intake Pump 3 DN1200-BTMVB0P03-01 0.39 0.85 M 230 2.0 0.30 0.12
N-09 Motor Valve Service Water 1 DN80-BTMVB0L17-01 0.39 0.85 M 230 2.0 0.30 0.12
N-10 Motor Valve Service Water 2 DN80-BTMVB0L20-02 0.39 0.85 M 230 2.0 0.30 0.12
N-11 Motor Valve Traveling Washing System 1 DN150-BTMVB0T03-01 0.39 0.85 M 230 2.0 0.30 0.12
N-12 Sodium Hypochlorite Dosing Pump 1 P3-B3G01-01 DOL 0.79 0.85 T 400 1.3 0.71 0.56
N-13 Sodium Hypochlorite Dosing Pump 2 P3-B3G01-02 DOL 0.79 0.85 T 400 1.3 0.71 0.56
N-14 Solenoid Valve Sodium Hypoclorite 1 DN25-BASVB3G01-03 0.20 0.85 M 230 1.0 0.30 0.06
N-15 Solenoid Valve Sodium Hypoclorite 2 DN80-BASVB3G01-04 0.20 0.85 M 230 1.0 0.30 0.06
N-16 Solenoid Valve Sodium Hypoclorite 3 DN80-BASVB3G01-06 0.20 0.85 M 230 1.0 0.30 0.06
N-17 Building Utilities 90.00 0.85 T 400 152.8 1.00 90.00
N-18 Air Supply 1 0.00 0.85 T 400 0.0 1.00 0.00
N-19 Control & Command 1 0.10 0.85 M 230 0.5 1.00 0.10
N-20 Control & Command 2 0.10 0.85 M 230 0.5 1.00 0.10
Reserve (%)
PRE-TREATMENT
BOARD B6-I4E01-01
Supply Characteristics Simultaneousness
FROM: B6-I1E01-01
Outlet number Application Equipment tag Starting method Pins (kW) cos Voltage Ir (A) Sim. Coef. Pdem (kW)
(kV)
BOARD B6-I4E03-01
Supply Characteristics Simultaneousness
FROM: B2-I4E03-01
Outlet Application Equipment tag Starting method Pins (kW) cos Line Voltage Ir (A) Sim. Pdem
number type (V) Coef. (kW)
(M,B,T)
BOARD B6-I4E04-01
Supply Characteristics Simultaneousness
FROM: B2-I4E04-01
Outlet Application Equipment tag Starting Pins (kW) cos Line Voltage Ir (A) Sim. Pdem
number method type (V) Coef. (kW)
(M,B,T)
TRC TRANSFORMER CONNECTION B6-I4E04-01 2152.55 0.86 T 400 3608.4 1.00 554.07
N-01 Capacitors B7-I4E04-01 0.10 0.80 T 400 293.6 1.00 0.10
N-02 LVMB Valves I4E04-01 2.48 0.85 T 400 4.2 1.00 2.48
N-03 Feeding to Common Service Panel 10.00 0.85 T 400 17.0 1.00 10.00
N-04 Filtration Control & Instrumentation 1.26 0.85 T 400 2.1 0.81 1.02
N-05 Crane (UF Feed Pump) A3-D3M01-01 30.00 0.85 T 400 50.9 0.25 7.50
N-06 UF CIP Pump 1 P1-D2W01-01 soft starter 31.58 0.85 T 400 53.6 0.64 20.21
N-07 UF CIP Heater H4-D2W01-01 40.00 1.00 T 400 57.7 0.26 10.40
N-08 Backwash Pump 1 P1-D2P01-01 soft starter 315.79 0.85 T 400 536.2 0.85 268.42
N-09 UF Sulphuric Acid Dosing Pump 1 P7-D8G03-01 DOL 1.16 0.85 T 400 2.0 0.76 0.88
N-10 UF Sulphuric Acid Dosing Pump 2 P7-D8G03-02 DOL 1.16 0.85 T 400 2.0 0.76 0.88
N-11 UF Sodium Hydroxide Dosing Pump 1 P7-D8G09-01 DOL 0.84 0.85 T 400 1.4 0.76 0.64
N-12 UF Sodium Hydroxide Dosing Pump 2 P7-D8G09-02 DOL 0.84 0.85 T 400 1.4 0.76 0.64
N-13 UF Sodium Hypochlorite Dosing Pump 1 P7-D8G01-01 DOL 1.16 0.85 T 400 2.0 0.76 0.88
N-14 UF Sodium Hypochlorite Dosing Pump 2 P7-D8G01-02 DOL 1.16 0.85 T 400 2.0 0.76 0.88
N-15 Coagulant (Ferric Chloride) Dosing Pump 1 P7-D8G02-01 DOL 0.13 0.85 T 400 0.2 0.79 0.10
N-16 Coagulant (Ferric Chloride) Dosing Pump 2 P7-D8G02-02 DOL 0.13 0.85 T 400 0.2 0.79 0.10
N-17 Effluents BW Pump 1 P2-F2P01-01 soft starter 55.00 0.85 T 400 93.4 0.21 11.55
N-18 Floculation Mixer 1 V3-F2T01-01 3.16 0.85 T 400 5.4 0.81 2.56
N-19 Wastewater (Neutralization) Pump 1 P2-F2P02-01 soft starter 15.79 0.85 T 400 26.8 0.78 12.32
N-20 Neutralization Flash Mixer 1 V3-F2T04-01 DOL 2.32 0.85 T 400 3.9 0.81 1.88
N-21 Coagulation Flash Mixer 1 V3-F2T01-01 0.12 0.85 T 400 0.2 0.81 0.10
N-22 Thickener 1 F7-F2T01-01 DOL 0.79 0.85 T 400 1.3 0.81 0.64
N-23 Sludge Recirculation Pump 1 P3-F2P03-01 DOL 7.50 0.85 T 400 12.7 0.69 5.18
N-24 Sludge Feed to Centrifuge Pump 1 P3-F2P04-01 soft starter 37.00 0.85 T 400 62.8 0.69 25.53
N-25 Sludge Feed to Centrifuge Pump 2 P3-F2P04-02 soft starter 37.00 0.85 T 400 62.8 0.69 25.53
N-26 Drying Sludge Pump 1 P3-F2P06-01 DOL 5.79 0.85 T 400 9.8 0.81 4.69
N-27 Floculant Preparation Equipment 1 V8-F8G06-01 2.60 0.85 T 400 4.4 0.85 2.21
N-28 Floculant Helicoidal Pump 1 P7-F8G06-01 DOL 0.39 0.85 T 400 0.7 0.21 0.08
N-29 Floculant Helicoidal Pump 2 P7-F8G06-02 DOL 0.39 0.85 T 400 0.7 0.21 0.08
N-30 Floculant Helicoidal Pump 3 P7-F8G06-03 DOL 0.39 0.85 T 400 0.7 0.21 0.08
N-31 Centrifugal Decanter Dehydrater 1 F5-F2P05-01 34.74 0.85 T 400 59.0 0.79 27.44
N-32 Storage Silo V6-F2T06-01 0.39 0.85 T 400 0.7 0.30 0.12
N-33
Coagulant (Ferric Chloride) Dosing Pump 1 (Effluent Plant) P7-D8G12-01 DOL 0.19 0.85 T 400 0.3 0.79 0.15
N-34
Coagulant (Ferric Chloride) Dosing Pump 2 (Effluent Plant) P7-D8G12-02 DOL 0.19 0.85 T 400 0.3 0.79 0.15
N-35 Sulphuric Acid Dosing Pump 1 (Effluent Plant) P3-D8G13-01 DOL 0.16 0.85 T 400 0.3 0.76 0.12
N-36 SWRO Antiscalant Dosing Pump 1 (1st pass) P3-E8G05-01 DOL 0.16 0.85 T 400 0.3 0.76 0.12
N-37 SWRO Antiscalant Dosing Pump 2 (1st pass) P3-E8G05-02 DOL 0.16 0.85 T 400 0.3 0.76 0.12
N-38 Sodium Hydroxide Dosing Pump 1 (Effluent Plant) P7-D8G19-01 DOL 0.79 0.85 T 400 1.3 0.81 0.64
N-39 Sodium Metabisulphite Mixer 1 V3-E8G04-01 1.16 0.85 T 400 2.0 0.81 0.94
N-40 Sodium Metabisulphite Dosing Pump 1 P7-E8G04-01 DOL 0.55 0.85 T 400 0.9 0.81 0.45
N-41 Sodium Metabisulphite Dosing Pump 2 P7-E8G04-02 DOL 0.55 0.85 T 400 0.9 0.81 0.45
N-42 Sodium Hidroxide Heating Coil H4-D6G09-01 60.00 1.00 T 400 86.6 0.26 15.60
N-43 Building Utilities 90.00 0.85 T 400 152.8 1.00 90.00
N-44 Control & Command 1 0.10 0.85 M 230 0.5 1.00 0.10
N-45 Control & Command 2 0.10 0.85 M 230 0.5 1.00 0.10
Reserve (%)
CONNECTION B6-I4E04-01 LVMB Valves 01 2.48 0.85 T 400 4.2 1.00 2.24
C-01 Solenoid Valve UF Line 1 0.20 0.85 M 230 1.0 0.30 0.06
C-02 Motor Valve UF Line 1 DN1800-BTMVD0L62-01 0.39 0.85 M 230 2.0 0.30 0.12
C-03 Motor Valve (out of spec) DN1600-BTMVD0L67-01 0.39 0.85 M 230 2.0 0.30 0.12
C-04 Motor Valve (to RO Line 1) DN1600-BTMVD0L91-01 0.39 0.85 M 230 2.0 0.30 0.12
C-05 Motor Valve (to backwash tank) DN600-BTCVD0L81-01 0.39 0.85 M 230 2.0 0.30 0.12
C-06 Motor Valve (RW feed supply) DN400-BTCVD1U01-02 0.39 0.85 M 230 2.0 0.30 0.12
C-07 Solenoid Valve Sodium Bisulphite 1 DN15-BASVE8G04-02 0.20 0.85 M 230 1.0 0.30 0.06
C-08 Solenoid Valve Antiscalant 1 DN15-BASVE8G05-02 0.20 0.85 M 230 1.0 0.30 0.06
C-09 Motor Valve UF Backwash 1 DN600-BTMVD2P01-03 0.39 0.85 M 230 2.0 0.30 0.12
C-10 Motor Valve UF Backwash 2 DN600-BTMVD2P02-04 0.39 0.85 M 230 2.0 0.30 0.12
C-11 Solenoid Valve Backwash (sodium hydroxide) DN15-BASVD2G09-02 0.20 0.85 M 230 1.0 0.30 0.06
C-12 Solenoid Valve Backwash (sulphuric acid) DN15-BASVD2G03-02 0.20 0.85 M 230 1.0 0.30 0.06
C-13 Solenoid Valve Backwash (sodium hypoclorite) DN15-BASVD2G01-02 0.20 0.85 M 230 1.0 0.30 0.06
C-14 Solenoid Valve Service Water DN15-BASVD2W01-14 0.20 0.85 M 230 1.0 0.30 0.06
C-15 Motor Valve UF Feed Pump 1 DN1400-BTMVD3P01-01 0.39 0.85 M 230 2.0 0.30 0.12
C-16 Motor Valve UF Feed Pump 2 DN1400-BTMVD3P02-01 0.39 0.85 M 230 2.0 0.30 0.12
C-17 Motor Valve UF Feed Pump 3 DN1400-BTMVD3P03-01 0.39 0.85 M 230 2.0 0.30 0.12
C-18 Motor Valve UF Feed Pump 4 DN1400-BTMVD3P04-01 0.39 0.85 M 230 2.0 0.30 0.12
C-19 Motor Valve UF Feed Pump out 1 DN900-BTMVD3P01-02 0.39 0.85 M 230 2.0 0.30 0.12
C-20 Motor Valve UF Feed Pump out 2 DN900-BTMVD3P02-02 0.39 0.85 M 230 2.0 0.30 0.12
C-21 Motor Valve UF Feed Pump out 3 DN900-BTMVD3P03-02 0.39 0.85 M 230 2.0 0.30 0.12
C-22 Motor Valve UF Feed Pump out 4 DN900-BTMVD3P04-02 0.39 0.85 M 230 2.0 0.30 0.12
C-23 Solenoid Valve CG Coagulant 1 DN25-BASVD3G01-02 0.20 0.85 M 230 1.0 0.30 0.06
Reserve (%)
RO BUILDING
BOARD B6-I2E02-01
Supply Characteristics Simultaneousness
FROM: B2-I2E02-01
Outlet number Application Equipment tag Starting method Pins (kW) cos Voltage (kV) Ir (A) Sim. Coef. Pdem
(kW)
POST-TREATMENT
BOARD B6-I3E04-01
Supply Characteristics Simultaneousness
FROM: B2-I3E04-01
Outlet Application Equipment tag Starting Pins (kW) cos Line Voltage Ir (A) Sim. Pdem (kW)
number method type (V) Coef.
(M,B,T)
TRC TRANSFORMER CONNECTION B6-I3E04-01 340.00 0.85 T 400 577.4 1.00 123.61
N-01 Capacitors B7-I3E04-01 0.02 0.80 T 400 58.1 1.00 0.02
N-02 Motor Valves 0.00 0.85 T 400 0.0 0.30 0.00
N-03 Sodium Hypochlorite Dosing Pump 1 P7-F8G01-01 DOL 0.19 0.85 T 400 0.3 0.79 0.15
N-04 Sodium Hypochlorite Dosing Pump 2 P7-F8G01-02 DOL 0.19 0.85 T 400 0.3 0.79 0.15
N-05 Sodium Hydroxide Dosing Pump 1 P7-E8G19-01 DOL 0.13 0.85 T 400 0.2 0.79 0.10
N-06 Sodium Hydroxide Dosing Pump 2 P7-E8G19-02 DOL 0.13 0.85 T 400 0.2 0.79 0.10
N-07 BWRO Antiscalant Dosing Pump 1 P7-E8G15-01 DOL 0.13 0.85 T 400 0.2 0.79 0.10
N-08 BWRO Antiscalant Dosing Pump 2 P7-E8G15-02 DOL 0.13 0.85 T 400 0.2 0.79 0.10
N-09 CO2 Dosing System 1 H3-F8G08-01 10.00 0.85 T 400 17.0 0.85 8.50
N-10 Limestong Air Blower 1 K3-F1A01-01 78.95 0.85 T 400 134.1 0.86 67.90
N-11 Limestong Backwash Pump 1 P1-F2W01-01 soft starter 15.79 0.85 T 400 26.8 0.57 9.00
N-12 Crane Limestong 1 A3-F1M01-01 5.00 0.85 T 400 8.5 0.26 1.30
N-13 Building Utilities 33.00 0.85 T 400 56.0 1.00 33.00
N-14 Control & Instrumentation 1 3.00 0.85 T 400 5.1 1.00 3.00
N-15 Control & Command 1 0.10 0.85 M 230 0.5 1.00 0.10
N-16 Control & Command 2 0.10 0.85 M 230 0.5 1.00 0.10
Reserve (%)
ELECTRICAL BUILDING 1
BOARD B6-I1E01-02
Supply Characteristics Simultaneousness
FROM: TR2
Outlet number Application Equipment tag Starting Pins (kW) cos Voltage Ir (A) Sim. Coef. Pdem
method (kV) (kW)
BOARD B6-I1E02-02
Supply Characteristics Simultaneousness
FROM: B2-I1E02-02
Outlet number Application Equipment tag Starting method Pins cos Voltage Ir (A) Sim. Coef. Pdem
(kW) (kV) (kW)
BOARD B6-I1E03-02
Supply Characteristics Simultaneousness
FROM: B2-I1E03-02
Outlet Application Equipment tag Starting method Pins (kW) cos Line Voltage Ir (A) Sim. Pdem
number type (V) Coef. (kW)
(M,B,T)
TRC TRANSFORMER CONNECTION B6-I1E03-02 2992.50 0.95 T 690 2635.7 1.00 1702.34
N-01 VFD ERD Booster Pump 7 B4-E2R07-01 341.84 0.95 T 690 301.1 0.83 283.72
N-02 VFD ERD Booster Pump 8 B4-E2R08-01 341.84 0.95 T 690 301.1 0.83 283.72
N-03 VFD ERD Booster Pump 9 B4-E2R09-01 341.84 0.95 T 690 301.1 0.83 283.72
N-04 VFD ERD Booster Pump 10 B4-E2R10-01 341.84 0.95 T 690 301.1 0.83 283.72
N-05 VFD ERD Booster Pump 11 B4-E2R11-01 341.84 0.95 T 690 301.1 0.83 283.72
N-06 VFD ERD Booster Pump 12 B4-E2R12-01 341.84 0.95 T 690 301.1 0.83 283.72
N-07 ERD Booster Pump 7 P1-E2R07-01 VFD 331.58 0.85 T 690 326.4 0.83 275.21
N-08 ERD Booster Pump 8 P1-E2R08-01 VFD 331.58 0.85 T 690 326.4 0.83 275.21
N-09 ERD Booster Pump 9 P1-E2R09-01 VFD 331.58 0.85 T 690 326.4 0.83 275.21
N-10 ERD Booster Pump 10 P1-E2R10-01 VFD 331.58 0.85 T 690 326.4 0.83 275.21
N-11 ERD Booster Pump 11 P1-E2R11-01 VFD 331.58 0.85 T 690 326.4 0.83 275.21
N-12 ERD Booster Pump 12 P1-E2R12-01 VFD 331.58 0.85 T 690 326.4 0.83 275.21
Reserve (%)
BOARD B6-I1E04-02
Supply Characteristics Simultaneousness
FROM: B2-I1E04-02
Outlet Application Equipment tag Starting method Pins (kW) cos Line Voltage Ir (A) Sim. Pdem
number type (V) Coef. (kW)
(M,B,T)
TRC TRANSFORMER CONNECTION B6-I1E04-02 2169.09 0.87 T 400 3608.4 1.00 1234.59
N-01 Capacitors B7-I1E04-02 0.11 0.80 T 400 321.8 1.00 0.11
N-02 Feeding to Common Service Panel 5.26 1.00 T 400 7.6 0.95 5.00
N-03 Lighting & Power 52.63 0.85 T 400 89.4 0.95 50.00
N-04 Motorized Valves 15.00 0.85 T 400 25.5 0.80 12.00
N-05 Air Dryers 21.05 0.85 T 400 35.7 0.81 17.05
N-06 Air Compressors 47.37 0.85 T 400 80.4 0.81 38.37
N-07 Transfer Pump 2 P1-E9W01-02 3.16 0.85 T 400 5.4 0.63 1.99
N-08 Transfer Pump to CIP 2 P1-E9W01-06 3.16 0.85 T 400 5.4 0.81 2.56
N-09 CIP Pump 2 P1-E9W01-04 189.47 0.85 T 400 321.7 0.33 62.53
N-10 CIP Heater H4-E9W01-01 44.00 1.00 T 400 63.5 0.75 33.00
N-11 CIP Mixer V3-E9W01-01 0.75 0.85 T 400 1.3 0.85 0.64
N-12 Flushing Pump 3 P1-E3W03-01 22.00 0.85 T 400 37.4 0.33 7.26
N-13 Turbocharger Pump 7 E3-E3R07-01 14.74 0.85 T 400 25.0 0.95 14.00
N-14 Turbocharger Pump 8 E3-E3R08-01 14.74 0.85 T 400 25.0 0.95 14.00
N-15 Turbocharger Pump 9 E3-E3R09-01 14.74 0.85 T 400 25.0 0.95 14.00
N-16 Turbocharger Pump 10 E3-E3R10-01 14.74 0.85 T 400 25.0 0.95 14.00
N-17 Turbocharger Pump 11 E3-E3R11-01 14.74 0.85 T 400 25.0 0.95 14.00
N-18 Turbocharger Pump 12 E3-E3R12-01 14.74 0.85 T 400 25.0 0.95 14.00
N-19 Crane 2 (HPF and HP Pumps) A3-E0M01-02 28.00 0.85 T 400 47.5 0.18 5.04
N-20 Crane 5 (RO Building) A3-E0M01-05 28.00 0.85 T 400 47.5 0.18 5.04
N-21 Control & Command 3 0.10 0.85 M 230 0.5 1.00 0.10
N-22 Control & Command 4 0.10 0.85 M 230 0.5 1.00 0.10
GC GENERATOR CONNECTION 1298.25 0.86 T 400 2396.0 1.00 1298.25
E-01 B6-I1E04-03 B6-I1E04-03 1008.16 0.86 T 400 1683.8 0.90 907.35
Reserve (%)
BOARD B6-B2E02-02
Supply Characteristics Simultaneousness
FROM: B2-B2E02-02
Outlet number Application Equipment tag Starting method Pins (kW) cos Voltage Ir (A) Sim. Coef. Pdem
(kV) (kW)
BOARD B6-B2E04-02
Supply Characteristics Simultaneousness
FROM: B2-B2E04-02
Outlet Application Equipment tag Starting Pins cos Line Voltage Ir (A) Sim. Pdem
number method (kW) type (V) Coef. (kW)
(M,B,T)
TRC TRANSFORMER CONNECTION B6-B2E04-02 212.50 0.85 T 400 360.8 1.00 114.41
N-01 Capacitors B7-B2E04-02 0.01 0.80 T 400 40.7 1.00 0.01
N-02 Control & Instrumentation 5.79 0.85 T 400 9.8 0.81 4.69
N-03 Jellyfish Blower 2 K3-B3A01-02 5.79 0.85 T 400 9.8 0.81 4.69
N-04 Crane (Solid Hopper) A3-B0M01-01 0.40 0.85 T 400 0.7 0.26 0.10
N-05 Travelling Screen 2 F6-B0T04-01 4.21 0.85 T 400 7.1 0.81 3.41
N-06 Travelling Flushing Pump 2 P1-B0P02-01 15.79 0.85 T 400 26.8 0.64 10.11
N-07 Motor Valve SW Intake Pump 4 DN1200-BTMVB0P04-01 0.39 0.85 M 230 2.0 0.30 0.12
N-08 Motor Valve SW Intake Pump 5 DN1200-BTMVB0P05-01 0.39 0.85 M 230 2.0 0.30 0.12
N-09 Motor Valve Service Water 3 DN80-BTMVB0L17-03 0.39 0.85 M 230 2.0 0.30 0.12
N-10 Motor Valve Traveling Washing System 2 DN150-BTMVB0T04-01 0.39 0.85 M 230 2.0 0.30 0.12
N-11 Sodium Hypochlorite Dosing Pump 3 P3-B3G01-03 0.79 0.85 T 400 1.3 0.71 0.56
N-12 Solenoid Valve Sodium Hypochlorite 4 DN25-BASVB3G01-01 0.20 0.85 M 230 1.0 0.30 0.06
N-13 Solenoid Valve Sodium Hypochlorite 5 DN25-BASVB3G01-06 0.20 0.85 M 230 1.0 0.30 0.06
N-14 Solenoid Valve Sodium Hypochlorite 6 DN25-BASVB3G01-08 0.20 0.85 M 230 1.0 0.30 0.06
N-15 Building Utilities 90.00 0.85 T 400 152.8 1.00 90.00
N-16 Air Supply 2 0.00 0.85 T 400 0.0 1.00 0.00
N-17 Control & Command 3 0.10 0.85 M 230 0.5 1.00 0.10
N-18 Control & Command 4 0.10 0.85 M 230 0.5 1.00 0.10
Reserve (%)
PRE-TREATMENT
BOARD B6-I4E01-02
Supply Characteristics Simultaneousness
FROM: B6-I1E01-02
Outlet number Application Equipment tag Starting method Pins (kW) cos Voltage Ir (A) Sim. Coef. Pdem (kW)
(kV)
BOARD B6-I4E03-02
Supply Characteristics Simultaneousness
FROM: B2-I4E03-02
Outlet Application Equipment tag Starting Pins (kW) cos Line Voltage Ir (A) Sim. Pdem
number method type (V) Coef. (kW)
(M,B,T)
TRC TRANSFORMER CONNECTION B6-I4E03-02 2992.50 0.95 T 690 2635.7 1.00 1666.85
N-01 VFD UF Feed Pump 5 B4-D3P05-01 651.11 0.95 T 690 573.5 0.64 416.71
N-02 VFD UF Feed Pump 6 B4-D3P06-01 651.11 0.95 T 690 573.5 0.64 416.71
N-03 VFD UF Feed Pump 7 B4-D3P07-01 651.11 0.95 T 690 573.5 0.64 416.71
N-04 VFD UF Feed Pump 8 B4-D3P08-01 651.11 0.95 T 690 573.5 0.64 416.71
N-05 UF Feed Pump 5 P1-D3P05-01 VFD 631.58 0.85 T 690 621.7 0.64 404.21
N-06 UF Feed Pump 6 P1-D3P06-01 VFD 631.58 0.85 T 690 621.7 0.64 404.21
N-07 UF Feed Pump 7 P1-D3P07-01 VFD 631.58 0.85 T 690 621.7 0.64 404.21
N-08 UF Feed Pump 8 P1-D3P08-01 VFD 631.58 0.85 T 690 621.7 0.64 404.21
Reserve (%)
BOARD B6-I4E04-02
Supply Characteristics Simultaneousness
FROM: B2-I4E04-02
Outlet Application Equipment tag Starting method Pins (kW) cos Line Voltage Sim. Pdem
number type (V) Coef. (kW)
(M,B,T)
N-28
Coagulant (Ferric Chloride) Dosing Pump 2 (Effluent Plant) P7-D8G12-03 0.19 0.85 T 400 0.79 0.15
N-29 Sulphuric Acid Dosing Pump 2 (Effluent Plant) P3-D8G13-02 0.16 0.85 T 400 0.81 0.13
N-30 SWRO Antiscalant Dosing Pump 3 (1st pass) P3-E8G05-03 0.16 0.85 T 400 0.81 0.13
N-31 Sodium Hydroxide Dosing Pump 2 (Effluent Plant) P7-D8G19-02 0.79 0.85 T 400 0.81 0.64
N-32 Sodium Metabisulphite Mixer 2 V3-E8G04-02 1.16 0.85 T 400 0.81 0.94
N-33 Sodium Metabisulphite Dosing Pump 3 P7-E8G04-03 0.55 0.85 T 400 0.81 0.45
N-34 Building Utilities 90.00 0.85 T 400 1.00 90.00
N-35 Control & Command 3 0.10 0.85 M 230 1.00 0.10
N-36 Control & Command 4 0.10 0.85 M 230 1.00 0.10
Reserve (%)
CONNECTION B6-I4E04-02 LVMB Valves 02 2.29 0.85 T 400 3.9 1.00 2.06
C-01 Solenoid Valve UF Line 2 0.20 0.85 M 230 1.0 0.30 0.06
C-02 Motor Valve UF Line 2 DN1800-BTMVD0L74-01 0.39 0.85 M 230 2.0 0.30 0.12
C-03 Motor Valve (out of spec) DN1600-BTMVD0L75-01 0.39 0.85 M 230 2.0 0.30 0.12
C-04 Motor Valve (to RO Line 2) DN1600-BTMVD0L66-01 0.39 0.85 M 230 2.0 0.30 0.12
C-05 Motor Valve (to backwash tank) DN600-BTCVD0L80-01 0.39 0.85 M 230 2.0 0.30 0.12
C-06 Solenoid Valve Sodium Bisulphite 2 DN15-BASVE8G04-03 0.20 0.85 M 230 1.0 0.30 0.06
C-07 Solenoid Valve Antiscalant 2 DN15-BASVE8G05-03 0.20 0.85 M 230 1.0 0.30 0.06
C-08 Motor Valve UF Backwash 3 DN600-BTMVD2P02-05 0.39 0.85 M 230 2.0 0.30 0.12
C-09 Motor Valve UF Backwash 4 DN600-BTMVD2P03-03 0.39 0.85 M 230 2.0 0.30 0.12
C-10 Solenoid Valve Backwash (sodium hydroxide) DN15-BASVD2G09-04 0.20 0.85 M 230 1.0 0.30 0.06
C-11 Solenoid Valve Backwash (sulphuric acid) DN15-BASVD2G03-04 0.20 0.85 M 230 1.0 0.30 0.06
C-12 Solenoid Valve (sodium hypoclorite) DN15-BASVD2G01-04 0.20 0.85 M 230 1.0 0.30 0.06
C-13 Motor Valve UF Feed Pump 5 DN1400-BTMVD3P05-01 0.39 0.85 M 230 2.0 0.30 0.12
C-14 Motor Valve UF Feed Pump 6 DN1400-BTMVD3P06-01 0.39 0.85 M 230 2.0 0.30 0.12
C-15 Motor Valve UF Feed Pump 7 DN1400-BTMVD3P07-01 0.39 0.85 M 230 2.0 0.30 0.12
C-16 Motor Valve UF Feed Pump 8 DN1400-BTMVD3P08-01 0.39 0.85 M 230 2.0 0.30 0.12
C-17 Motor Valve UF Feed Pump out 5 DN900-BTMVD3P05-02 0.39 0.85 M 230 2.0 0.30 0.12
C-18 Motor Valve UF Feed Pump out 6 DN900-BTMVD3P06-02 0.39 0.85 M 230 2.0 0.30 0.12
C-19 Motor Valve UF Feed Pump out 7 DN900-BTMVD3P07-02 0.39 0.85 M 230 2.0 0.30 0.12
C-20 Motor Valve UF Feed Pump out 8 DN900-BTMVD3P08-02 0.39 0.85 M 230 2.0 0.30 0.12
C-21 Solenoid Valve CG Coagulant 2 DN25-BASVD3G02-02 0.20 0.85 M 230 1.0 0.30 0.06
Reserve (%)
RO BUILDING
BOARD B6-I2E02-02
Supply Characteristics Simultaneousness
FROM: B2-I2E02-02
Outlet number Application Equipment tag Starting Pins (kW) cos Voltage Ir (A) Sim. Coef. Pdem (kW)
method (kV)
POST-TREATMENT
BOARD B6-I3E04-02
Supply Characteristics Simultaneousness
FROM: B2-I3E04-02
Outlet Application Equipment tag Starting Pins (kW) cos Line Voltage Ir (A) Cable Sim. Pdem
number method type (V) medium Coef. (kW)
(M,B,T) lenght (m)
TRC TRANSFORMER CONNECTION B6-I3E04-01 340.00 0.85 T 400 577.4 10 1.00 123.51
N-01 Capacitors B7-I3E04-02 0.02 0.80 T 400 58.1 20 1.00 0.02
N-02 Motor Valves 0.00 0.85 T 400 0.0 300 0.30 0.00
N-03 Sodium Hypochlorite Dosing Pump 3 P7-F8G01-03 0.19 0.85 T 400 0.3 300 0.79 0.15
N-04 Sodium Hypochlorite Dosing Pump 4 P7-F8G01-04 0.19 0.85 T 400 0.3 300 0.79 0.15
N-05 Sodium Hydroxide Dosing Pump 3 P7-E8G19-03 0.13 0.85 T 400 0.2 300 0.79 0.10
N-06 Sodium Hydroxide Dosing Pump 4 P7-E8G19-04 0.13 0.85 T 400 0.2 300 0.79 0.10
N-07 BWRO Antiscalant Dosing Pump 3 P7-E8G15-03 0.13 0.85 T 400 0.2 300 0.79 0.10
N-08 CO2 Dosing System 2 H3-F8G08-02 10.00 0.85 T 400 17.0 300 0.85 8.50
N-09 Limestong Air Blower 2 K3-F1A01-02 78.95 0.85 T 400 134.1 300 0.86 67.90
N-10 Limestong Backwash Pump 2 P1-F2W01-02 15.79 0.85 T 400 26.8 300 0.57 9.00
N-11 Crane Limestong 2 A3-F1M01-02 5.00 0.85 T 400 8.5 300 0.26 1.30
N-12 Building Utilities 33.00 0.85 T 400 56.0 300 1.00 33.00
N-13 Control & Instrumentation 2 3.00 0.85 T 400 5.1 300 1.00 3.00
N-14 Control & Command 3 0.10 0.85 M 230 0.5 10 1.00 0.10
N-15 Control & Command 4 0.10 0.85 M 230 0.5 10 1.00 0.10
Reserve (%)
BOARD B6-I1E04-03
Supply Characteristics Simultaneousness
FROM: B6-I1E04-01 & B6-I1E04-02
Outlet number Application Equipment tag Starting method Pins cos Line Voltage Ir (A) Sim. Pdem (kW)
(kW) type (V) Coef.
(M,B,T)
4.- CONCLUSION
The consumption of each line, showed in the previous list of consumers, is:
The five pumps from the pumping station, the whole power for Mekorot Reservoir and all the
power of the secure power panel have been considered in both lines. Consequently, taking into
account these values, the total amount of power that will be actually demanded from the electric
grid by Ashdod Desalination Plant is:
P = L1 + L2 – SWIP – SP – MR
Where:
And considering the power factor 0.87, the apparent power is S = 78,886.69 kVA.