AUX LED and AUX control button Activates and deactivates the auxiliary output EVO192 Wiring Diagram

Before adding any modules to the control panel make sure Please Note: When powering up the EVO control panel , the
you shut down the AUX output by pressing and holding the panel will begin a module scan to verify that all modules
AUX button for 3 seconds. connected to the panel are operational. The scanning process
The signal transmission to the Central Station may be performed by following methods:
will take between 30 seconds and 3 minutes to complete
Landline (PSTN), Internet, and GPRS. Only Internet, and GPRS method of transmission
Caution: Disconnect the battery depending on the number of modules connected to the control
may be used for Commercial applications.
before replacing the fuse. panel. The module scan is complete when the LCD keypad
begins to show the partition status. Only after the module scan is
completed will the control panel be fully operational.
When Installing the combus wires in a noisy environment or
when connecting the combus across separate buildings, you
must use a shielded cable. Refer to section 2.15.1.

SERIAL
Please see ETL and ETLC Warnings for and information in the
+– appendix.

EBUS
Wiring methods that shall be in accordance with the National
12Vdc 7Ah STATUS Electrical Code, ANSI/NFPA 70, the Standard for Installation

DIALER
Rechargeable Lead- and Classification of Burglar and Holdup Alarm Systems, UL
Acid backup battery 681, and the Standard for Central-Station Alarm Services, UL

MEM KEY
AUX 827.
Intended wiring methods must be in keeping with the
RED
Battery Capacity for emergency standby at least 4 hours requirements of CSA C22.1, Canadian Electrical Code, Part I,
AUX

BATT
WARNING: To prevent risk of electric shock, disconnect Safety Standard for Electrical Installations.
BLK
AC battery and phone cord BEFORE Servicing. PARADOX
Trigger The system should be installed in accordance with Chapter
+ - 2 of the National Fire Alarm Code, ANSI/NFPA 72
AUX
(8) Red “STATUS” LED
Flashing – indicates proper operation
For residential installations use transformer made by
Always on – panel is using a phone lilne
Universal Power Group model: UB1640W
Fast Flash – indicates a control panel failure
Off – Control panel error
SERVICE
CAN KEYPAD E V O Location for connecting an optional VDMP3 module
For US: UL/ETL
Listed Class 2 wall/ UL 120VAC/
building 17VAC
120VAC/60Hz Notes:
120VAC/ transfor- AC AC + – 1 2 3 4 COM N.C. N.O. + – GRN YEL COM Z1 Z2 Z3 Z4 COM Z5 Z6 Z7 Z8 COM R-1 T-1 RING TIP (1) ETL note: Use an ETL/UL approved bell/siren.
power supply with 17VAC mer BELL PGM RELAY AUX BUS
(2) Wiring conventions have to be in the same room
restraining means. transfor- (1) (2) (6) (6) (4)
(2) of these terminals.
mer (3) Zone Input Specifications:
For Canada: CSA/ AWG#14 single conductor solid
(5) To anti- Maximum loop current (shorted loop): 2.2 mA
ULc/ETLc Listed copper wire
Auxiliary supply tamper switch Maximum loop voltage (open loop): 5.0 VDC
Class 2 Power can provide: (4) Disconnect Telecom jack before servicing.
Supply with NO Max. 700 mA (3) For hardwired connections see (5) The anti-tamper switch needs to be connected to
restraining means. single zone and double zone
To power-on To metalic enclosure a separate zone configured for 24 hrs.
indicator LED COMBUS connections. (6) For Maximum number of devices to be employed
Transformer Requirements: 120VAC/17VAC , 40 VA to recharge at 850mA, YEL refer to the Features in section 1.1.
20VA to charge at 350mA (7) The minimum permissible wire size to be employed
GRN shall be not smaller than No. 22 AWG (0.32 mm2).
Auxiliary Supply can provide: max. 700mA
Automatic Shut Down 1.1a BLK (8) PGM Trigger: This jumper allows you to choose whether the

KEYPAD
Usable Battery Charge Currents: 850mA max. solid-state relay PGMs are grounded (-) or give out 12V (+).
RED
The COMBUS supports a maximum of 254 (EVO192) modules.
Do not short the terminals of the transformer together. This causes the internal fuse to blow. PGM
Although external power supplies can be used to provide power
Z1 to modules connected far from the control panel the total
The transformer must be connected to a 120 VAC, 24-hour outlet not controlled by a switch other than an
distance of all runs of wire combined cannot exceed 914m
approved over-current protection device.
WHT RED BLK
(3000 ft.). For example if ten runs of wire measuring 305m
(1000 ft.) each are connected to the control panel, the total
For continued protection against risk of fire, replace fuses only with fuses of the same type and rating.
distance would be 3048m (10000 ft.) which exceeds the system
*A 1 KU resistor is required if MR 3
ANY DETECTOR

YEL capacity.
the Bell is not equipped with an GRN (optional) UL
The "BELL" output will internal resistor. Position the
+ – BLK All knockouts provided for connection of a field-wiring system to a
shutdown if the current AC AC resistor as close as possible to
BELL the Bell. A resistor is not BRN YEL field-wiring compartment shall accommodate conduit of the trade
exceeds 3A. RED
required for sirens. size according to NEC.
SELF-CONTAINED BELL/SIREN
COM
N.C. N.O. The metal housing which enclosed the Fire and Burglary system
RED
housing has knockouts on the sides and in the back enclosure.
N.O.
N.C.
COM

ANY MODULE
COM

AC AC + – 1 2 3 4 Z1
GRN The wiring method requires that bushings are used for wiring
BELL PGM RELAY
through the metal box. Including the transformer with Plug in
BLK
The sum total of the current draw from the bell/siren and the AUX Power Supply.
YEL
must be llimitted to 2.0A. Exceeding this limit will overload the panel
power supply and lead to complete system shutdown.
EVO-EA03 | Printed in Canada 10/2014