2019-2021 BerlinerLuft. Rect.-Ducting
2019-2021 BerlinerLuft. Rect.-Ducting
Airtightness classes: A, B and C as per DIN EN 1507 Sheet thickness 0.8 mm and 1.0 mm, corners sealed
or whole joint sealed (corners, frames, and seams)
Turning vanes as per DIN EN 1505
Longitudinal seams folded, end connection with frame, turning
Longitudinal seams folded, end connection with frame or slip joint
vanes as per DIN EN 1505, walls reinforced with corrugations,
Walls reinforced with trapezoidal corrugation additional reinforcement as per BerlinerLuft. factory standard,
spot welds treated
Additional reinforcement for pressure ratings M and HR
as per BerlinerLuft. Technik GmbH factory standard Standard duct section length 1,500 mm
Width of frame sections for pressure rating L Frame section width 20 mm: up to edge length 1,000 mm
Frame width 20 mm: up to edge length 1000 mm Frame section width 30 mm: > edge length 1,000 to 2,000 mm
Air Conduction | 33
Overview of folded ducting components
Sheet metal ducts and fittings with a rectangular cross section Sheet metal ducts and fittings with rectangular cross section
similar to EN 1505, 1507 and DIN 18379 for harsher conditions
Folded sheet metal ducts and fittings made of aluminium AlMg3 Sheet metal ducts and fittings, folded, made of sendzimir
galvanised thin sheet metal, quality DX51D + Z275MA-C
Sheet thickness 1.0 mm and 1.2 mm, corners sealed or whole
(DIN EN 10346 and DIN EN 10143),
joint sealed (corners, frames, and seams)
Sheet metal thickness up to 1,000 mm, edge length 0.95 mm,
Longitudinal seams folded, end connection with frame, turning from 1,001 mm to 2,000 mm, edge length 1.15 mm, airtightness
vanes as per DIN EN 1505, walls reinforced with corrugations, class A or B in accordance with DIN EN 1507, longitudinal seams
additional reinforcement as per BerlinerLuft. factory standard folded, end connection with frame
Standard duct section length 1,500 mm Turning vanes as per DIN EN 1505
34 | Air Conduction
Overview of folded ducting components, welded
Sheet metal ducts and fittings with rectangular cross section, Welded sheet metal ducts and fittings with rectangular cross
galvanised, folded and insulated section as per DIN EN 1505, 1507 and VDI 3803
Sheet metal ducts and fittings made of Sendzimir galvanised Welded sheet metal ducts and fittings made of Sendzimir
thin sheet steel grade DX51D + Z275MA-C galvanised thin sheet steel grade DX51D + Z275MA-C
(DIN EN 10346 and DIN EN 10143) (DIN EN 10346 and DIN EN 10143) and black sheet S 235 JRG2
as per DIN EN 10025
Sheet thickness depending on pressure rating L or M
Sheet thickness for pressure rating HR
Airtightness class A or B as per DIN EN 1507
Airtightness class C and D as per DIN EN 1507
Folded longitudinal seams, end connection with frame
End connection with angle frame or formed frame, perforated
Turning vanes as per DIN EN 1505. Walls reinforced with cor-
as per factory standard (hole spacing 125 mm), turning vanes
rugations, additional reinforcement as per BerlinerLuft. factory
as per DIN EN 1505
standard
Standard duct section length 1,500 mm Fixed duct length depending on the frame connection
Air Conduction | 35
Overview of folded ducting components, welded
Sheet metal ducts and fittings with rectangular cross section Sheet metal ducts and fittings with rectangular cross section
similar to DIN EN 1505, 1507 and VDI 3803 similar to DIN EN 1505, 1507 and VDI 3803
Welded sheet metal ducts and fittings made of stainless steel Welded sheet metal ducts and fittings made of aluminium
1.4301 and 1.4571, matt or polished finish AL 99.5 hh and AlMg3, sheet thickness 2.0 mm and 3.0 mm
Sheet thickness as required for airtightness class C or D as Airtightness class C and D as per DIN EN 1507. Stricter
per DIN EN 1507. Stricter requirements such as nekal tightness requirements such as nekal tightness as per DIN on request
as per DIN on request
End connection with angle frame, perforated as per
End connection with angle frame or formed frame, perforated factory standard (hole spacing 125 mm), turning vanes
as per factory standard (hole spacing 125 mm), turning vanes as per DIN EN 1505
as per DIN EN 1505
Fixed duct length depending on the frame connection Fixed duct length depending on the frame connection
Fixed duct length with flush angle frame: 1,500 mm Fixed duct length with flush angle frame: 1,500 mm
30 mm formed frame 30/15: 1,350 mm 30 mm formed frame 30/15: 1,350 mm
40 mm formed frame 40/20: 1,350 mm 40 mm formed frame 40/20: 1,350 mm
60 mm formed frame 60/30: 1,300 mm 60 mm formed frame 60/30: 1,300 mm
80 mm formed frame 80/40: 1,200 mm 80 mm formed frame 80/40: 1,200 mm
60 mm: > edge length 1,000 mm 60 mm: > edge length 1,000 mm
80 mm: > edge length 2,000 mm 80 mm: > edge length 2,000 mm
36 | Air Conduction
Design of ducting components – frames
Ability to withstand pressure (VDI 3803) Welded air duct with angle frame (4)
Airtightness class (DIN EN 1507) Can be used for special requirements of airtightness class D
1 2 3 4
Air Conduction | 37
Sheet metal ducts and fittings
V1 V2
V1 V2
b
1 l a 2
l a
V1 V2
V1
b
b
f
3 l a 4 l a
f a V1 V2 c
d
b
V1 V2
b
According to
manufacturer's design
5 l c 6 l a
V1 α
b
V1V1 V2
V2
r
7 l l dd 8 V2
e
38 | Air Conduction
AS PER DIN EN 1505, 1507 AND DIN 18379
a
V1 α
V1
b
b
f r
r
α
V2 V2
e
1 d a 2 f a
a f
V1 V2 V1
b/a
b
α
l c
r
e
V3
e
V2
3 f d a 4 c/a d/a
f g a
V1
b/a
V1
c/a
V2
α
V2
α
r2
r1
V3
e
5 d/a K/a 6 l c
f-Axis c -f
V1 V2
-e
V1
V2
d
b
d
b
7 8
g a
l a l e-Axis
e-Axis
Air Conduction | 39
Sheet metal ducts and fittings
f-Axis -f
V2 V2
-e
V1
d
b
b
V1
e
g
1 l a 2 l a
e-Axis e-Axis
l a
f-Axis c V2
V1
d
b
Q2
e
e
a
d
m
r
b
V3
Q1
3 l a 4 n h a
l a
f-Axis
V2
-e
-e
V1 V1
V2 h m d a
d
b
a
b
a
m
r
V3 V3
a a
5 n h 6 l
e-Axis
V1 V1
V1 V2 V2 d
d
b
e
e
f c f
40 | Air Conduction
Table of ducting components
Galvanised steel
Stainless steel
Black steel
Aluminium
Platal
FAL
Design
Folded • • • •
Welded • • • • •
Connection
Frame • • • •
Slip joint • • • • •
Screw connection • • • • •
Welded butt joint • • •
Airtightness
Airtightness class B • • •
Airtightness class C • • •
Airtightness class D • • • • • •
Aerosol-tight • • • •
Surface
Hot-dip galvanised •
Primed/painted • • •
Chlorine-resistant paint • •
Fatty acid-resistant paint • •
Powder coating • • • •
Insulation
Double wall • • • •
Mineral wool/perforated plate, inside • • •
Cellular rubber internal/external • • • • • •
Anti-drone coating • • •
Air Conduction | 41
Standards and guidelines
HVAC is undergoing a period of upheaval in terms of stand- This means that there is always an obligation to check that
ards and regulations: Some of the DIN standards have been the standards are up to date.
withdrawn and replaced by EN standards. Although there is
Here is a list of standards which must always be observed
basic freedom of contract, withdrawn DIN standards may no
for ducting:
longer be used.
DIN EN 1505 Sheet metal air ducts and fittings with rectangular cross section – Dimensions
DIN EN 1507 Sheet metal air ducts with rectangular section – Requirements for strength and leakage
DIN EN 12097 Requirements for ducting components to facilitate maintenance of ducting systems
DIN EN 12599 Test procedures and measurement methods to hand over air conditioning and ventilation systems
DIN 24193-1* Ducting components for ventilation equipment; flanges; series 1 angle flanges
DIN 24193-2* Ducting components for ventilation equipment; flanges; series 2 angle flanges
VDI 6022 Hygiene requirements for ventilation and air-conditioning systems and units
* DIN 24193 Parts 1 and 2 have been withdrawn. However, they can be used by mutual agreement, as no equivalent EN standard exists.
42 | Air Conduction
Materials
METALLIC MATERIALS
Sealants 1 2
Single-component sealant Silicone-free VDI 6022 + 80 °C
Basis: Acrylic Certified
Silyl modified polymer (SMP)
Resistant to fatty acids
Permanently elastic and UV-resistant
Ducting can be made from different metallic materials, de- Surface preparation/washing and passivation
pending on the application. The surface finish and corrosion
Undercoat or primer
protection depend on the requirements.
Painting
The necessary coating thickness depends on the application
and must be specified by the user, taking into account the rel- Powder coating
evant corrosion protection guidelines. A surface finish can be
EPD coating (see page 450)
applied to the either black or galvanized sheet steel.
Stainless steel
Blasting
Grinding
Brushing
Air Conduction | 43
Sheet thickness and pressure ratings
as per VDI 3803
Pa Pa Pa Pa Pa Pa Pa Pa
a b
+1000 -500 +2000 -750 +3000 -1500 +6000 -2500
100 100
200 200
300 300
1.0
400 400
600 600
1000 1000
1200 1200
1400 1400
1800 1800
2000 2000
Nominal dimensions
Special non-standard components are manufactured on request.
outside
For the tender specification, the customer must state specific requirements for the sheet thickness and frame joint.
DIN EN 1505
They will be invoiced as special components.
> 2000 to 3000
1
Edge lengths a and b can be combined as desired
2
For intermediate sizes, the sheet thickness is the one stated for the next higher edge length
3
The wall thickness is the nominal thickness as per DIN 10143
H Folded industrial design for restricted high pressure use with increased sheet thickness
R
and additional reinforcement (available in airtightness class B), max. duct length 1,000 mm
44 | Air Conduction
Turning vanes
1
Turning vanes as per DIN EN 1505
Edge length b as per DIN 18379 (VOB Part C)
b r ≥100 mm
Air Conduction | 45
Airtightness
AIRTIGHTNESS
To ensure that the air conditioning system operates reliably average internal pressure1, the leakage rate is read off of the
and energy-efficiently, the ducting must meet specific airtight- diagram and multiplied by the duct surface area. The table be-
ness requirements. DIN EN 1507 defines the permissible leak- low shows the airtightness requirements in DIN EN 1507 and
age rate per m2 of ducting surface, depending on the static the recommendations for use in DIN EN 16798-3 and VDI 3803.
internal pressure. 1
Static pressure difference between the internal duct pressure
Diagram 1 can be used to estimate the expected leak loss and the ambient pressure (both positive and negative pressure)
for a ducting system or one of its sections. Starting with the
10
8
PROOF OF AIRTIGHTNESS
6
The airtightness class must be certified on an installed section
4 A
sc lass
tnes
of the ductwork, containing a representative number of ducts
igh
2 Airt and fittings and a surface area of at least 10 m2 (see DIN EN 1507,
sB measuring procedure in DIN EN 12599).
Air leak rate in 10-3 m3 /sm2
clas
1 tn ess
0,8 Airtigh The quality of installation has a significant effect on the
0,6 airtightness of the ducting. In order to achieve a particular
sC
0,4 s clas airtightness class, all components designed for the class in
igh tnes
Airt question must be produced at a high quality, and the instal-
0,2
D lation must be carried out according to exacting standards.
ass
es s cl
ightn To monitor the quality of installation, it is advisable to carry out
0,1 Airt
0,08 a sample test of the leak rate in accordance with DIN EN 15599
0,06 during the assembly phase.
0,04
0,02
0,01
100 200 400 600 800 1000 1500 2000
Average internal pressure in the ducting system in Pa
Diagram 1
46 | Air Conduction
Energy savings from use
of airtightness class C
DK D DK C DK B DK A Ducting leakage rate (DK A) Difference when a higher airtightness class is selected
14000 4
500
1400 4000 12000
400 1200
10000 m²
1000 3000 00
10 ²
300 8000 0m
800 2 80 ²
0m
-C
2000 6000 60
²
A
200 600
0m
-D
5000 5 0
²
A
500 1500
150 4000 0 0m
4
400 1 ²
125 m
1000 0
3000
0.8 30
100 300
800
80 0.6 0 m²
2000 20
200 600
60 ²
500 1500 15 0m
0.4
50 150
400
40
0 m²
1000 10
100 300
30 800
80 0.2
200 600
20 60
500
50 150
15 400
40 0.1
100 300
10 30 0.08
80
8 0.06
200
20 60
100 200 300 400 500 750 1000 1500 0.1 0.2 0.4 0.6 0.8 1.0 2.0 4.0
,0 0
10
8000
8,
5
4,
Example
0
6000
3,
2 ,0
Pressure 250 Pa1)
)
P 6 FP
s*
em
S
4000
4
st
25
sy
SF
Ducting surface 300 m²
,
SF
om
1
FP
*)
ro
S
ing
n
*)
ea
ion
DK C instead of DK A (A-C)
g
Cl
dit
tin
3
on
75
2000
ea
FP
ir c
0,
rh
)S
ll a
5
Fu
t*
0,
ith
en
2
W
tm
P
SF
ea
Energy saving €700/a
1
tr
P
ir
s
SF
1000
³/
ta
rm
ou
pe
800
W
kW
100
Leakage of observed 0 m² 600
800
ducting section in m³/h m²
600 400
m²
500
m²
1)
Average pressure in the observed 400
m²
ducting section. 300
m² 200
The leakage loss is approximately the same
200
for positive and negative pressure. 10 m²
0 150
m m²
²
100
0 1 2 3 4 5 6 7 8 9 10 0.1 0.2 0.4 0.6 0.8 1.0 2.0 4.0
* The assignment of SFP classes to the type of system only includes the cost of ducting (as a rough guide)
Comparison: advantages of using airtightness class C instead The amortisation period is calculated using the following for-
of class A, which typically has been used up to now mula, using current cost developments and the operating time:
Air Conduction | 47
Component joints — maximum and
minimum dimensions
Pressure rating L M L M H H H
0 to 500 30 x 5
20 20 20 20 40
501 to 1000 30 x 3 40 x 5
1001 to 1250
30 30 30 30 40 60 x 6
1251 to 2000 40 x 4
> 2000 3 40 40 40 50 x 5 60 x 10
LP C+1 formed frame on ducting and fitting (except US, UA, HS, BE, BD)
1
2
LP1 attached frame for the above fittings and special parts
3
components with edge lengths greater than 2,000 mm are non-standard and are manufactured as special parts.
The type of component joint must be specified by the user according to the requirements of use.
COMPONENT REINFORCEMENTS
The reinforcements on duct walls are based on the compo- For certain pressure ratings and component dimensions, ad-
nent requirements in DIN EN 1507 as regards limit values for ditional side wall reinforcements are required. These take the
rigidity and stability of form. form of
The specific requirements are compiled in an internal factory Internal tubular supports
standard.
Internal or external sheet metal rails
Generally, the following types of reinforcement are used.
External ribs
Walls of duct and fittings up to a sheet thickness of 1.25 mm
(only on welded ducting when necessary)
generally have a trapezoidal corrugated profile.
48 | Air Conduction
Flange connections
4-hole
Section connection, corner joint
LP C 1500
formed plus
Folded componentsmm
duct clamps
4-hole
Section connection, corner joint
LP 1500
attached plus
duct clamps
Bolted joint
Angle flange,
W1 Hole spacing 125 mm 1480
recessed
or special hole spacing
Welded componentsmm
Bolted joint
Angle flange,
W2 Hole spacing 125 mm 1500
welded flush
or special hole spacing
Air Conduction | 49
Assembly recommendation
HR Folded industrial design for restricted high pressure level with increased sheet thickness and additional reinforcement
(available in airtightness class B), maximum duct length 1,000 mm
TOLERANCE RANGES
Edge length [mm] Max. deviation [mm] Component dimensions Max. deviation [mm]
0
a or b a, b, c, d, e, f
-4
l, lp, r
0 0
100-1000
-3 -5
> 15/< 100 mm
0 0
1001-2000 > 100
-4 -4
0 0
> 2000 > 2000
-5 -10
50 | Air Conduction
Transport and storage
CLEANLINESS OF DUCTWORK (VDI 6022, SHEET 1) The standard version offered by the manufacturer are visibly
clean, non-packaged components.
Depending on the hygienic requirements, ducts and fittings
may have to be protected from dirt during transport and on site Other requirements (such as cleaning; closed ends; com-
storage or may have to be cleaned before assembly. In accord- plete, single packaging or complete, multiple packaging) must
ance with VDI 6022, sheet 1, requirements for the cleanliness be specified at the planning stage.
of components are divided into cleanliness levels.
Cleanliness level Packaging Protection during Protection during Cleaning Sealing openings
ex works transport storage on site on site
> 2000
The price is calculated per m2 of component surface area. L5 F5
(outside standard)
The calculation formulas are standardised for each compo-
nent. The costs are calculated in price groups.
Air Conduction | 51
Special versions
Ducting for kitchens is subject to special hygiene and Exhaust air ducting in kitchens must be greaseproof and
safety requirements. The basis for this is DIN 18869 Part 4 aerosol-proof. The following materials can be used: galvanised
and VDI 2052. sheet steel and stainless steel (V2A 1.4301 or V4A 1.4571 or
1.4404)
Stainless Airtightness
Ducting type Galvanised steel Seal Notes
steel class
52 | Air Conduction
Thermal and acoustic insulation
INSULATION REQUIREMENTS FOR DUCTING In addition to insulating after complete assembly of the
ducting, there is also the option of using ready-insulated com-
Reduced heat loss
ponents. This option is used indoors when insulation after
Temperature dropping below dew point installation is not possible due to lack of space.
Reduced sound emissions
Note
The customer must always check that the type and structure of
the insulation is suitable for the application.
100 0.45
up to EL 1000 17.5
> EL 1000 20.5
Sound insulation
Mineral wool with glass fibre fabric
and perforated sheet metal shell
up to EL 1000 12.5
> EL 1000 14
100
up to EL 1000 15
> EL 1000 16.5
Air Conduction | 53
Smoke extraction — XDuct® smoke
extraction duct
XDuct® is smoke extraction ducting made of galvanised Smoke extraction ducting with cross sections up to W x H =
steel as per DIN EN 12101-7 with CE marking. The test was car- 1,250 x 1,000 mm are used. The installation material required
ried out using 1500 Pa negative pressure and at 600 °C with for the XDuct® system (wall anchors, duct crossbeams, duct
500 Pa negative pressure over a period of 120 minutes as per tape, sealing compound) is also subject to certification for fire
DIN EN 1366-9. safety and is also supplied on request. (DIN EN 12101-7, para-
graph 4.2.5, other components)
The smoke extraction ducting is a complete system with
ducts and fittings made of folded, galvanised sheet steel and XDuct® ventilation duct sections are branded with the CE con-
complies with the administrative requirements of the Technical formity mark.
Building Regulations. The tested system is impressive due to
Accessories tested as per DIN EN 1366-9 are marked with the
its lower pressure loss, reduced risk of transport damage, and
product code according to the classification report. A wide
lower weight. The installation is thus easier than other similar
range of tested accessories, such as expansion joints, smoke
solutions made of calcium silicate panels. The ducts and fit-
extraction grilles, silencers, inspection panels are available.
tings are made of 1 mm galvanised sheet steel with additional
A height offset between duct axes of up to 2,500 mm is also
reinforcements and a 30 mm lightweight section frame.
available.
54 | Air Conduction
Duct accessories
bxa
30
a max. = 800 mm
mind. b/2 b max = 500 mm
1 2 3 4
Airtightness class B C
Range of application -70 °C/+70 °C -70 °C/+100 °C up to 400 °C up to I thickness 50 mm
21 200 x 100
32 300 x 200
All listed types and dimensions are available in the following materials:
43 400 x 300
galvanised steel, corrosion-resistant steel (V2A and V4A), aluminium
54 500 x 400
65 600 x 500
RD = Inspection panel
RD-SKK = Inspection panel with self-adhesive
edge guard
RD-HT = Inspection panel for high temperatures
IRD = Insulated inspection panel
Air Conduction | 55
Tender specification texts
FOLDED GALVANISED STEEL DUCTS AND FITTINGS Additional requirements (as necessary)
Folded galvanised steel ventilation ducts and fittings as To ensure that the ducting is clean as per DIN EN 12097 or
per DIN EN 1505, DIN EN 1507 and VDI 3803 VDI 6022, sheet 1
56 | Air Conduction
FOLDED STAINLESS STEEL DUCTS AND FITTINGS Additional requirements (as necessary)
(1.4301 OR 1.4571)
To ensure that the ducting is clean as per DIN EN 12097 or
Folded stainless steel ventilation ducts VDI 6022, sheet 1
and fittings 1.4301 (1.4571)
Medium cleanliness level:
Pressure rating L (low pressure); +1,000/-500 Pa delivery without packaging or transport protection, protection
during storage, cleaning before assembly, openings sealed
Pressure rating M (medium pressure); +2,000/-750 Pa
High cleanliness level:
delivery with packaging and transport protection (e.g. end closure)
Sheet thickness min. 0.8 mm; max. 1.0 mm
protection during storage, cleaning before assembly,
openings sealed
Components suitable for assembling ducting systems in
Air Conduction | 57
Tender specification texts
58 | Air Conduction
WELDED VENTILATION DUCTS AND FITTINGS Additional requirements (as necessary)
Welded ventilation ducts and fittings as per DIN EN 1505, All components must be coated on the outside and/or inside
DIN EN 1507 and VDI 3803 made of with chemically resistant paint, RAL colour ................., coating
thickness ........ µm
galvanised steel with cold galvanised welds
To ensure that the ducting is clean as per DIN EN 12097 or
Stainless steel 1.4301 (1.4571), brushed welds
VDI 6022, sheet 1
Aluminium AlMg3
Medium cleanliness level:
Delivery without packaging or transport protection, protection
Welds may not be ground during storage, cleaning before assembly, openings sealed
Air Conduction | 59
Assembly information
Unloading and transporting components Subsequent, on-site sealing along the section frame, on the entire
interior of the frame and inside the corners (use only sealants
Visually check all components for external damage.
suitable for later use that is, for example, compliant with VDI 6022,
Check that airtightness class C is correctly shown on the labels. solvent-free, etc.)
Unload the components with care to avoid any damage. Do not fasten any additional attachments with self-tapping
screws (only with sealed blind rivets).
Use suitable equipment to transport the components
(do not pull on the frame joint). Seal attachments afterwards using a suitable sealant
(compliant with VDI 6022).
Store them in a proper manner on site.
Flexible connectors, multi-leaf dampers, silencers etc. must be
shown to meet the requirements of airtightness class C.
Assembly
Attach the duct tape crosswise in the corner area of the section. The tests should already be defined at the planning stage
and carried out during the assembly stage. See the informa-
Make sure the bolt connections on the corners are tight.
tion sheet “Measuring airtightness of ducting systems”
Use duct brackets for edge lengths above 400 mm, with a maxi- (see, www.berlinerluft.de – downloads)
mum spacing of 200 mm.
About 2 days later, check that the bolt connections on the frame
are tight (duct tape has settled).
60 | Air Conduction