Air System Sizing Summary for AHU-DINING HALL

Project Name: SENIOR MESS HALL-AL MAHA CAMP -ADNOC 06/23/2023


Prepared by: Empire Estate 01:32PM

Air System Information


Air System Name AHU-DINING HALL Number of zones 1
Equipment Class CW AHU Floor Area 902.3 m²
Air System Type SZCAV Location Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 157.4 kW Load occurs at Jul 1500
Sensible coil load 118.2 kW OA DB / WB 52.0 / 30.0 °C
Coil L/s at Jul 1500 9260 L/s Entering DB / WB 23.8 / 17.8 °C
Max block L/s 9260 L/s Leaving DB / WB 13.2 / 12.6 °C
Sum of peak zone L/s 9260 L/s Coil ADP 12.0 °C
Sensible heat ratio 0.751 Bypass Factor 0.100
L/(s kW) 58.8 Resulting RH 56 %
m²/kW 5.7 Design supply temp. 13.0 °C
W/m² 174.5 Zone T-stat Check 0 of 1 OK
Water flow @ 5.6 K rise 6.78 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 9260 L/s Fan motor BHP 10.81 BHP
Standard L/s 9230 L/s Fan motor kW 8.57 kW
Actual max L/(sꞏm²) 10.26 L/(sꞏm²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(sꞏm²) 0.00 L/(sꞏm²)

Hourly Analysis Program 5.10 Page 1 of 7


Zone Sizing Summary for AHU-DINING HALL
Project Name: SENIOR MESS HALL-AL MAHA CAMP -ADNOC 06/23/2023
Prepared by: Empire Estate 01:32PM

Air System Information


Air System Name AHU-DINING HALL Number of zones 1
Equipment Class CW AHU Floor Area 902.3 m²
Air System Type SZCAV Location Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(sꞏm²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 9167 9167 10.16 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 110.3 Jul 1500 10.0 902.3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(sꞏm²)
Zone 1
DINING HALL 1 110.3 Jul 1500 9167 10.0 902.3 10.16

Hourly Analysis Program 5.10 Page 2 of 7


Air System Design Load Summary for AHU-DINING HALL
Project Name: SENIOR MESS HALL-AL MAHA CAMP -ADNOC 06/23/2023
Prepared by: Empire Estate 01:32PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 52.0 °C / 30.0 °C HEATING OA DB / WB 5.0 °C / 3.0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 30 m² 1789 - 30 m² - -
Wall Transmission 611 m² 9335 - 611 m² 5214 -
Roof Transmission 902 m² 16558 - 902 m² 4385 -
Window Transmission 30 m² 472 - 30 m² 287 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 10 m² 815 - 10 m² 99 -
Floor Transmission 902 m² 0 - 902 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 11279 W 11278 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 18046 W 18045 - 0 0 -
People 612 48959 36720 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 3060 2448 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 110313 39168 - 9985 0
Zone Conditioning - 108546 39168 - 8169 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 9260 L/s 0 - 9260 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 9260 L/s 8574 - 9260 L/s -8574 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 1103 - 1% 100 -
>> Total System Loads - 118223 39168 - -305 0
Central Cooling Coil - 118223 39194 - 0 0
>> Total Conditioning - 118223 39194 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 3 of 7


System Psychrometrics for AHU-DINING HALL
Project Name: SENIOR MESS HALL-AL MAHA CAMP -ADNOC 06/23/2023
Prepared by: Empire Estate 01:32PM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 52.0 0.01788 0 400 0 0
Vent - Return Mixing Outlet 23.8 0.01035 9260 8745 - -
Central Cooling Coil Outlet 13.2 0.00891 9260 8745 118223 39194
Supply Fan Outlet 13.9 0.00891 9260 8745 8574 -
Cold Supply Duct Outlet 14.0 0.00891 9167 8745 - -
Zone Air - 23.9 0.01036 9167 8749 108546 39168
Return Plenum Outlet 23.9 0.01036 9167 8749 0 -
Duct Leakage Air Outlet 13.9 0.00891 93 8745 - -
Return Duct Outlet 23.8 0.01035 9260 8745 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.203 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2938.2 W/(L/s)
Site Altitude = 26.8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 110313 Cooling 108546 23.9 9167 8749 0 0

Hourly Analysis Program 5.10 Page 4 of 7


System Psychrometrics for AHU-DINING HALL
Project Name: SENIOR MESS HALL-AL MAHA CAMP -ADNOC 06/23/2023
Prepared by: Empire Estate 01:32PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5.0 0.00389 0 400 0 0
Vent - Return Mixing Outlet 20.0 0.01157 9260 800 - -
Central Cooling Coil Outlet 19.9 0.01157 9260 800 0 0
Supply Fan Outlet 20.7 0.01157 9260 800 8574 -
Cold Supply Duct Outlet 20.7 0.01157 9167 800 - -
Zone Air - 20.0 0.01157 9167 800 -8169 0
Return Plenum Outlet 20.0 0.01157 9167 800 0 -
Duct Leakage Air Outlet 20.7 0.01157 93 800 - -
Return Duct Outlet 20.0 0.01157 9260 800 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.203 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2938.2 W/(L/s)
Site Altitude = 26.8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -9985 Deadband -8169 20.0 9167 800 0 0

Hourly Analysis Program 5.10 Page 5 of 7


System Psychrometrics for AHU-DINING HALL
Project Name: SENIOR MESS HALL-AL MAHA CAMP -ADNOC 06/23/2023
Prepared by: Empire Estate 01:32PM

Location: Abu Dhabi, United Arab Emirates


Altitude: 26.8 m.
Data for: July DESIGN COOLING DAY, 1500
0.020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Duct Heat
4. Room Air 0.018
5. Return Duct Outlet

0.016

Specific Humidity ( kg/kg )


0.014

0.012
4
5
1 23
0.010

0.008

0.006

0.004

0.002

0.000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program 5.10 Page 6 of 7


System Psychrometrics for AHU-DINING HALL
Project Name: SENIOR MESS HALL-AL MAHA CAMP -ADNOC 06/23/2023
Prepared by: Empire Estate 01:32PM

Location: Abu Dhabi, United Arab Emirates


Altitude: 26.8 m.
Data for: WINTER DESIGN HEATING
0.020
1. Supply Fan Outlet
2. Duct Heat
3. Duct Heat
4. Room Air 0.018
5. Return Duct Outlet

0.016

Specific Humidity ( kg/kg )


0.014
4 12 0.012
5
3
0.010

0.008

0.006

0.004

0.002

0.000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program 5.10 Page 7 of 7