Professional Documents
Culture Documents
A Novel PRD Control Method Damping Resonance in Grid-Connected Three-Phase SVPWM Current
A Novel PRD Control Method Damping Resonance in Grid-Connected Three-Phase SVPWM Current
A Novel PRD Control Method Damping Resonance in Grid-Connected Three-Phase SVPWM Current
Abstrac-- A novel control method based on the methods to avoid the problems in [6], the choice of the
proportional resonant differential (PRD) control is proposed virtual damping resistance is more complex for numbers
for the grid-connected current source inverter (CSI) used in of factors need to be considered [9]. The latter used the
the direct drive permanent magnet synchronous wind dynamic terms of the supply filter equations to eliminate
generation system. By the optimal design of the parameters
current oscillations under transient conditions [10],
of the PRD controller in two-phase stationary frame, the
CSI system can realize zero steady-state error control and however, the method is unable to damp the oscillations
effectively damp the resonance caused by its output LC which are from outside of the control loop [10].
filter just by feeding back the grid-connected current. This Unlike the previous work, this paper proposes a
not only greatly simplifies the controller design but also proportional resonant differential (PRD) control method
enhances the stability of the system. Simulation results show in stationary reference frame. In this method, the output
grid-connected CSI with this method has fast dynamic current of the CSI is fed back directly to actively
response and good steady-state performances. suppress the LC resonance incorporating with the optimal
configuration of the PRD, but without any feedback
Index Terms-- Grid-connected current source inverter; compensation and complex numerical calculations. In
proportional resonant differential (PRD); LC resonance; this way, the design of the controller is greatly simplified.
active damping. The simulation results show grid-connected CSIs with the
proposed method is capable of achieving high quality
I. INTRODUCTION dynamic and steady-state performances in addition to the
Grid-connected inverters are now widely used in many much lower current THD caused by both parallel and
utility applications to interface distributed generation series resonances.
systems, such as photovoltaic generation, wind
generation and fuel cells systems and alike. So, the II. MODEL OF GRID-CONNECTED OF THREE-PHASE CSI
controller design of such inverters becomes an important Fig. 1 shows the power stage and control structure of a
research orientation [1], [2]. According to the literatures grid-connected three-phase CSI in stationary reference
so far, in the case of inverter circuits for grid interfacing, frame, where Cf and Lf form a low-pass filter to filter out
voltage source inverters (VSI) are the dominant high frequency harmonics of the output current of
topologies[3]. However, current source inverters (CSI) do inverter, but to have the fundamental component fed into
offer some specific advantages, which include voltage the grid. Rf represents the equivalent resistance of the
boost from a lower magnitude input source, implicit inductor and the line. The values of all the parameters in
output short-circuit protection, significantly reduced
the circuit shown as in Table ĉ.
electromagnetic interference because of the capacitive
voltage filters located directly on the inverter output [4].
For the CSI system with output LC filter circuit, one
of the key issues is the damping of LC resonance. There iia ,b ,c ia ,b ,c Lf Rf ea ,b ,c
are two methods proposed in current literatures: passive
damping and active damping methods. As passive IDC
damping method using physical resistors in parallel or grid
series with the inductor or in parallel or series with the Cf abc
capacitor involves excessive energy losses [5], the αβ PLL
iα iβ
preferred approach is to use only a LC filter and design
the control algorithm to “actively” damp the resonance. iα θ
Currently used active damping methods can be divided controller
SVPWM
into two categories: feedback compensation methods and iβ
numerical methods. The former, say, high frequency controller
components of the capacitor voltage feedback method [6],
is simple, but high-pass filter would affect the control of Fig.1 The control structure of grid-connected three phase CSI
the fundamental component [7]. Although [8] presented
M a g n it u d e (d B )
s C f L f + sR f C f + 1
2
s C f L f + sR f C f + 1 0
= G ( s ) I i ( s ) − Ge ( s ) E ( s )
(1) -50
Where, Ge(s) is the grid-voltage disturbance transfer
function; G(s) is the LC filter transfer function, which is -100
a second-order system, and the natural frequency and 10 100 1000 10000
Frequency(Hz)
damping ratio can be obtained as ωn = 1 / C f L f and
Fig. 3. Bode plot of Gcsi with Gc1 controller.
ζ = ( R f / 2) * C f / L f , respectively. Generally, for the Another quasi-PR controller [11],[12] is as follows:
low-pass filter with grid-connected inverter, the value of kr 2ω02
Gc 2 ( s ) = k p 2 + 2 (4)
Cf , Lf and Rf are micro farad, millihenry and milliohm s + 2ςω0 s + ω02
respectively, so, ζ<1, and the system is underdamped. Where, kp2 and kr2 are the proportional gain and
Therefore, if the controller cannot effectively suppress resonant gain respectively, ζ provides another degree of
the current component nearby ωn, the line current will be freedom for specifically regulating the tracking-error
in substantial distortion. So, for the design of the performance at the line frequency ω0. In this paper, let
controller, special requirements should be considered.
ζ= 0.005. When kp2=0.1 and kr2=22.4, the bode plot of
According to the structure of the CSI shown in Fig. 1,
Gc2(s) is shown in Fig. 4.
the proposed control block diagram is shown in Fig. 2. As Bode Diagram
100
the switching frequency (5kHz) is much higher than the
grid frequency, therefore, the impact of switching on the
Magnitude (dB)
50
-45
Phase (deg)
Cs
+−
I ref (s)
+ I (s ) -90
Gc (s)
e − sTS K pwm G (s )
− -135
-180
1 2 3 4
10 10 10 10
Frequency (Hz)
Fig. 2. Control block diagram of the proposed controller. Fig. 4. Bode plot of Gc2
Without considering grid voltage disturbance, the It can be seen from Fig. 4 that Gc2(s) has a positive
system open-loop transfer function can be written as: resonance magnitude at ω0 and a negative resonance
Gcsi ( s ) = K pwm e − sTs Gc ( s )G ( s ) (2) magnitude at 1 + kr 2 / k p 2 ω0 . So, if the parameters of
kp2 and kr2 are so matched that 1 + kr 2 / k p 2 ω0 = ωn ,
III. DESIGN OF CONTROLLER BASED ON PROPOSED
METHOD then the controller may damp the LC resonance. Based
on this deduction, in this paper, Gc2(s) is applied to the
In this section, the controller for the CSI is constructed CSI controller, and taking kp2=0.1, kr2=22.4, the bode plot
based on the analysis on two quasi-PR controllers, and of Gcsi(s) with Gc2 is shown in Fig. 5 (the blue line).
then the specific parameters of the controller is designed ,
finally the designed controller is analyzed in details.
A. Quasi-PR Controllers
The expression of widely used quasi-PR controller [1],
[2], [11] is shown as in (3), where kp1 and kr1 are the
proportional gain and resonant gain respectively, and ωc
488
3rd IEEE International Symposium on Power Electronics for Distributed Generation Systems (PEDG) 2012
100
Bode Diagram the system gain increases, but without effect on the phase
With 1st order dirrerential
Without 1st order dirrerential margin. According to control theory, the proper phase
margin is 40 degree. Therefore, the appropriate
Magnitude (dB)
50
parameters can be selected by the bode diagram.
0
C. Performance Analysis of the CSI with the proposed
controller
-50
90 With the reference current as input and the
0 grid-connected current as output, the final closed-loop
Phase (deg)
0
Fig. 5 (the red line), in which, the phase of Gcsi(s) is
boosted from -180 degree to 133 degree.
-45
k
s 2 + 2ςω0 s + (1 + r 2 )ω02
k p2 -90
Gc ( s ) = k p 2 (Td s + 1)
1 2 3
(5) 10 10 10
s 2 + 2ςω0 s + ω02
Frequency (Hz)
Fig. 7. Bode diagram of the closed-loop transfer function.
B. Design of Parameters IV. SIMULATION AND EXPERIMENTAL RESULTS
Firstly, the proposed control method is verified by
It can be seen from (5) that, there are three parameters simulation using Matlab/Simulink. System parameters for
needed to be designed. However, according to the the simulation are listed in Table , and Fig. 8 and Fig. 9
analysis above, 1 + kr 2 / k p 2 ω0 = ωn , Td = 1 / ω0 , so just show the simulation results.
kp2 needs to be designed, which greatly simplifies the Fig.8. shows the steady-state waveforms of grid
controller design. When kp2 is set at different values (such voltage and current. As shown, without decoupling
as 0.03,0.06 and 0.09), the bode plot of Gcsi(s) is shown compensation, the system can realize unit power factor of
in Fig. 6. grid-connected current control. Fig. 8(b) shows the THD
80
Bode Diagram of the grid-connected current is 1.54% and the amplitude
k p2=0.03 of each harmonics is less than 1%, so the CSI can meet
k p2=0.06
60
grid code completely. By comparing the grid-connected
Magnitude (dB)
k p2=0.09
-20 e
Voltage(125V/div)
Current(25A/div)
90 a
0
Phase (deg)
-90 0 i
a
-180
-270
-360
0 1 2 3
10 10 10 10
Frequency (Hz) 0.04 0.06 0.08 0.1 0.12
Fig. 6. Bode plot of Gcsi. time(s)
It can be seen from Fig. 6 that with the increase of kp2, (a)
489
3rd IEEE International Symposium on Power Electronics for Distributed Generation Systems (PEDG) 2012
ea
iref
0
ia
es
C u rre nt(2 5A /d iv)
0
is
-50
-100
0.02 0.04 0.06 0.08
time(s)
(c)
Fig. 9. Grid voltage and current. (a) Step response. (b) Disturbance
rejection response. (c) Grid current at different control strategy.
Fig. 9(a) shows the dynamic response when the
reference current is changed abruptly from 12.5A to 23A,
the output current of the CSI can track the set reference
(a)
values in less than 1ms. Therefore, fast dynamic response
is obtained with the proposed controller. Fig. 9(b) shows
with distorted grid voltage (containing 5% of the
harmonics at natural frequency) the sinusoidal
grid-connected current remains unaffected, which
indicates that the CSI is capable of suppressing LC
resonances either from the inverter or from the utility
supply. Fig. 9(c) shows when PRD controller is replaced
by PR controller (as shown in (3)), the CSI will be
unstable. This indirectly proves that the proposed PRD
control method can enhance the stability of the system.
In order to verify the proposed PRD control method a (b)
rectifier prototype system using Insulated Gate Bipolar Fig. 11. Experiment result with PRD controller.
(a)Grid current. (b) FFT of grid current.
490
3rd IEEE International Symposium on Power Electronics for Distributed Generation Systems (PEDG) 2012
It can be seen from Fig. 10 that when using PR [10] M.Salo.H.Tuusa, “A Vector Controlled Current-Source
control method grid current contains a lot of 11th PWM Rectifier with a Novel Current Damping Method,”
harmonic (natural frequency). But it can also be seen IEEE Transactions on power electronicsˈvol.15ˈno.3ˈ
from Fig. 11 that the current component nearby 11th pp.464-450ˈMay.2000.
harmonic greatly reduced with PRD control method. [11] Xiaoqiang Guo ˈ Weiyang Wu ˈ Qinglin Zhao.
Thus proved the proposed PRD control method can damp “Comparative Analysis and Digital Implementation of
LC resonance effectively. Novel Control Strategies for Grid-Connected Inverters,”
V. CONCLUSION Transactions of CHIAN Electrotechnical Societyˈ22(5)˖
A novel PRD control method has been proposed for 111-115ˈMay, 2007ˊ
the grid-connected current source inverters to damp the [12] Y. W. Li, D. M. Vilathgamuwa, P. C. Loh, “Robust
LC resonances. Its design is so simple that only the Control Scheme for a Microgrid With PFC Capacitor
Connected,” IEEE Transactions on industry applications,
grid-connected current needs to be sensed and fed back.
vol.43, no.5, pp.1172-1182, Sep.2007.
The results of the simulations and experiments
demonstrate that the proposed control method is capable
to achieve high-quality dynamic and steady-state
performances, and can effectively damp the parallel
resonance excited by the inverter and the series resonance
caused by the utility voltage.
ACKNOWLEDGMENT
The authors would like to acknowledge the partial
support from Grant International Cooperation Project
of MOST ( 2007DFA71340 ).
REFERENCES
[1] Qinglin ZhaoˈXiaoqiang GuoˈWeiyang Wu. “Research
on Control Strategy for Single Phase Grid connected
Inverter,” Proceedings of the CSEEˈ2007ˈ27(16)˖60-64ˊ
[2] Qin LeiˈFang Zheng PengˈShuitao Yang. “Multiloop
control method for High-preformance microgrid inverter
through laod voltage and current decoupling with only
output voltage feedback,” IEEE Transactions on power
electronicsˈvol.26ˈno.3ˈpp.953-960ˈMar. 2011.
[3] Benjamin SahanˈSamuel V. AratjoˈChristian Nödingˈ
Peter Zacharias. “Comparative evaluation of three-phase
current source inverter for grid interfacing of distributed
and renewable energy systems,” IEEE Transactions on
power electronicsˈvol.26ˈno.8ˈpp.2304-2318ˈAug. 2011.
[4] Sorrell Alistair Shield Grogan, Donald Grahame Holmes,
Brendan Peter McGrath, “High Performance Voltage
Regulation of Current Source Inverters,” IEEE
Transactions on power electronics ˈ vol.26 ˈ no.9 ˈ
pp.2439-2448ˈSep. 2011.
[5] Yun Wei Li, “Control and Resonance Damping of
Voltage-Source and Current-Source Converters With LC
Filters,” IEEE Transactions on industry applicationsˈ
vol.56ˈno.5ˈpp.1511-1521ˈJun.2009.
[6] Yukihiko Sato, Teruo Kataoka, “A Current Type PWM
Rectifier with Active Damping Function,” IEEE
Transactions on industry applicationsˈvol.32ˈno.3ˈ
pp.533-541ˈMar.1996.
[7] A.Nabae, H.Nakano,Y.Okamura, “A Novel Control
Strategy of the Inverter with Sinusoidal Voltage and
Current Outputs,” Power Electronics Specialists
ConferenceˈPESCÿ94,25TH Annual IEEEˈJun.1994,
vol.1,pp.154-159.
[8] J.C.Wiseman, B.Wu, “Active Damping Control of a
High-Power PWM Current-Source Rectifier for
Line-Current THD Reduction,” IEEE Transactions on
industry applicationsˈvol.52ˈno.3ˈpp.758-764ˈJun.2005.
[9] B. Wu, “High-Power Converters and AC Drives,”
Piscataway, NJ: IEEE Press, 2006.
491