Application
  Outdoor Unit

Function
  Long refrigerant pipe, the longest connection pipe of certain units can be 150m,
the largest height difference between indoor and outdoor unit can be 50m
  Wide outdoor units lineup, including digital compressor series, DC inverter
compressor series
  Heat recovery and ultra-low temperature heat-pump series with digital
compressor are available
  Precise temperature control with only ±0.5'C temperature fluctuation
  Powerful and advanced new controller for optional

Refrigerant
  R410A

Features
  High COP value
  Unique oil return patent design
  Real time intelligent defrost technology
  Accurate refrigerate distributing technology
  Wide capacity range from 10kW to 16kW
  Space saving outdoor unit
  Low noise
  Components optimum designed for R410a

J.02 GMV-PD 1/2 - 2012/4/27 - AA-EN www.airtradecentre.com


J.02

Air conditioning
and heatpumps

Applicable indoor units


  Wall mounted type GMV-G
  Floor-ceiling type GMV-Z
  Duct type GMV-P
  Cassette type GMV-T
  Console type GMV-C
  Floor-standing type GMV-L

Applicable controller
Centralized controller ZJ7011 - controlling up to 64 groups (64 outdoor unit, 1024 indoor units in max)
  Central control
  Single control or select control
  Weely schedule
  Malfunction code display
  Expanded timer function
  Maximum wiring length of 1000m
 
Mini centralized controller ZJA011 - controlling up to 1 group (16 indoor units in max)
  Control 1 groups (16 indoor units in max)
  Group centralized control
  Memory restart
  Malfunction code display
  Key lock function

Specifications
Model heat pump GMV-Pd100W/NaB-K GMV-Pd120W/NaB-K GMV-Pd140W/NaB-K GMV-Pd160W/NaB-K
Cooling kW 10 12 14 16
Capacity
Heating kW 11 14 15.4 17.6
Power supply 220-240-1Ph-50Hz
Power Cooling kW 2.86 3.50 4.36 4.98
input Heating kW 2.60 3.40 4.05 4.85
IPLV Cooling 3.8 3.8 4.4 4.2
Refrigerant charge volume kg 7.5 7.5 7.5 7.5
Compressor quantity 1
Sound pressure level dB(A) 58 58 58 60
Dimensions (W   D   H) mm 950 x 340 x 1250
Net / gross weight kg 111 / 122 111 / 122 111 / 122 115 / 122
Connecting Gas mm Ø15.9 Ø15.9 Ø15.9 Ø19.05
pipe diameter Liquid mm Ø9.52 Ø9.52 Ø9.52 Ø9.52
Maximum drive IDU number 6 7 8 9
Maximal total length (actual length) of fitting pipe m 150
1250

1100
378

340 590 201

Operating conditions
Nominal operating conditions
Outdoor conditions Indoor conditions
DB Temperature (°C) WB Temperature (°C) DB Temperature (°C) WB Temperature (°C)
Cooling 35 24 27 19
Heating 7 6 20 15
Outdoor conditions (DB °C)
Operation range Cooling (°C) +10 ~ +48
Heating (°C) -27 ~ +27