DRYING TIME 73ºF (23ºC) 50% RH: Sealfas® Coating meets the requirements of Military
Set to Touch: 2 Hours Specification MIL-A-3316C Class 1, Grade A, and is listed on
Dry Through: 15 Hours the QPL.
Sealfas® Coating is approved by the U.S. Coast Guard under
SERVICE TEMPERATURE LIMITS: 164.012.
Temperature at coated surface
0ºF to 180ºF (-18ºC to 82ºC) Sealfas® Coating is produced under the classification and
follow-up service of Underwriter’s Laboratories, Inc. and meets
WATER VAPOR PERMEANCE (TYPICAL AVERAGE): NFPA 90A and 90B 25/50 requirements.
ASTM F1249: 0.5 - 1.5 perms (0.9 metric perms) at 31 mils
dry film thickness (0.8 mm) Sealfas® Coating contains no asbestos, lead, mercury or
mercury compounds.
WET FLAMMABILITY: Sealfas® Coating 30-36™ meets the requirements of:
No flash to boiling, 212ºF (100ºC) MAS Certified Green®
California Dept. of Public Health Standard Method v1.2
SURFACE BURNING CHARACTERISTICS (ASTM E84):
VOC Emissions and Content requirements to
Flame Spread: 10
Smoke Developed: 5 contribute to LEED v4 EQ Credit: Low Emitting
Tested at coverage rate of 40 sq. ft./gal. (1.0 m2/l). Applied to Materials – Paints and Coatings
1/4 inch (6.4 mm) inorganic reinforced cement board. The Collaborative for High Performance Schools EQ 7.1
flame spread may vary at different product thicknesses
and/or when applied over other surfaces. VOC Content: 15 g/l, less water and exempt solvents.
LIMITATIONS
Store and apply between 40ºF (4ºC) and 100ºF (38ºC),
protect from freezing until dry.
Always test foil and paper facings for acceptable adhesion
before using.
™ Trademark of H.B. Fuller Construction Products Inc.
30-36™
MATERIAL PREPARATION
DO NOT THIN. Apply only to clean, dry, oil-free surfaces. Keep container closed when not in use.
APPLICATION
1. Apply a tack coat of Foster® Sealfas® Coating at 60 – 70 sq. ft. per gal. (1.5 – 1.7 m2/l).
2. Immediately imbed the selected lagging fabric into the wet coating. Smooth to avoid wrinkles and overlap seams by at least 2
inches (5 cm).
3. Immediately apply a finish coat at 60 – 70 sq. ft. per gal. (1.5 – 1.7 m2/l). The dry film thickness of this application will vary with
the fabric selected.
For air conditioning ducts, increase the coverage rate to 40 – 50 sq. ft. per gal. (1.0 – 1.2 m2/l) for each coat.
BRUSH
Use clean paint brushes (suitable for water-based paints). Apply with full brush and spread out evenly.
SPRAY
Sealfas® Coating may be airless spray applied. For spray equipment information please consult Airless Spray Recommendations or
contact your airless spray equipment supplier. Average viscosity range: 55,000 – 75,000 cps. Corrosion resistant pumps and fittings
are suggested.
TOP COATING
If Sealfas® Coating 30-36™ is to be top coated with anything other than an alkyd enamel conforming to DOD-E-24607 as specified in
MIL-A-3316C, the user must confirm by his own tests that the products are compatible and that the final results are satisfactory.
CLEAN UP
Use clean fresh water for cleaning brushes and equipment before product dries. Dry product may be removed with hot soapy water or
strong solvents such as chlorinated solvent (non-flammable) or mineral spirits (flammable).
ADEQUATE TESTS: The information contained herein we believe is correct to the best of our knowledge and tests. The recommendations and suggestions herein are made
without guarantee or representation as to results. We recommend that adequate tests be performed by you to determine if this product meets all of your requirements. The
warranted shelf life of our products is twelve months from date of shipment to the original purchaser or as otherwise provided on the certificate of analysis.
APPLICATION CONSISTENCY:
Spray, brush or roller. Foster® S.M. Adhesive is a low cost, quick-setting synthetic
elastomer adhesive for use with fibrous glass insulation (up
AVERAGE WEIGHT / U.S. GALLON (FSTM 3): to 3 lbs./cu.ft.) duct wrap and acoustical linings for air
6.2 lbs. (0.74 kg/l) handling ducts.
AVERAGE NON-VOLATILE (FSTM 9A): S.M. Adhesive is designed for use in applications where
17-19% by volume (27-30% by weight) fibrous glass insulation is bonded to the interior or exterior of
sheet metal air-conditioning ducts.
COVERAGE RANGE (FSTM 72):
(Subject to type of surface and nature of material being S.M. Adhesive meets ASTM C916, Type IV (ASC-A-7001-
bonded.) 200 to 400 sq. ft. per gallon (4.9 to 9.8 m2/l) A, Type IV) and NFPA 90A and 90B 25/50 requirements.
0.008 in. to 0.004 in. wet film thickness (0.2 to 0.1 mm)
S.M. Adhesive is produced under the classification and
BOND TIME RANGE (FSTM 66): follow-up service of Underwriter’s Laboratories, Inc.
0 to 15 minutes
S.M. Adhesive contains no asbestos, lead, mercury, or
SERVICE TEMPERATURE LIMITS (FSTM 70): mercury compounds.
(Temperature at coated surface)
-20ºF to 200ºF (-29ºC to 93ºC) LIMITATIONS
Store and apply between 40ºF (4ºC) and 100ºF (38ºC).
WET FLAMMABILITY (ASTM D 93):
Flash point -7ºF (-22ºC) Always test plastic materials for compatibility when using
solvent base products.
SURFACE BURNING CHARACTERISTICS (ASTM 84):
Flame Spread: 10 Make certain this product is completely dry and the area free
Smoke Developed: 25 from solvent odor if food is involved.
Tested at coverage rate of 200 sq. ft./gal. (4.9 m2/l).
Applied to 1/4 inch (6.4 mm) inorganic reinforced cement Not suggested for sealing vapor barrier jackets.
board. The flame spread may vary at different product
thicknesses and/or when applied over other surfaces. Allow to dry to a solvent-free condition before installing weld
pins.
™ Trademark of H.B. Fuller Construction Products Inc. Overhead applications may require mechanical fasteners.
Visit us on the web at www.fosterproducts.com
05/14
No need to prime aluminum or galvanized metal. Apply only to clean, dry surfaces. Keep container closed when not in use to prevent
solvent evaporation.
APPLICATION
Brush:
Use a clean paintbrush. Apply uniformly to metal surface at 200-400 sq. ft./gal. (4.9-9.8 m2/l). Press insulation into place, making
sure complete contact is made with applied adhesive. Bond may be made within 0 to 15 minutes.
Spray:
May be spray applied with conventional air atomizing equipment or airless spray equipment. For spray equipment information, please
consult Spray Recommendations or contact your spray equipment supplier. Average viscosity range: 200-500 cps.
CLEAN-UP
Use solvents such as chlorinated solvent (non-flammable) or mineral spirits (flammable) for cleaning brushes and equipment.
ADHESIVES
SURFACE BURNING CHARACTERISTICS
CUSTOMER SERVICE—800-832-9002
IMPORTANT: H.B. Fuller Construction Products Inc. warrants that each of its products will be manufactured in accordance with the specifications in effect on the date of
manufacture. WE MAKE NO OTHER WARRANTIES AND EXPRESSLY DISCLAIM ANY WARRANTIES OF MERCHANTIBILITY OR FITNESS FOR A PARTICULAR
PURPOSE. If a product fails to meet this limited warranty, purchaser’s sole and exclusive remedy is replacement of the product or, at our option, refund of the purchase
price. OUR ACCEPTANCE OF ANY ORDERS FOR THE PRODUCT IS EXPRESSLY CONDITIONAL UPON PURCHASER’S ASSENT TO THE TERMS ON THE
APPLICABLE INVOICE.
ADEQUATE TESTS: The information contained herein we believe is correct to the best of our knowledge and tests. The recommendations and suggestions herein are
made without guarantee or representation as to results. We recommend that adequate tests be performed by you to determine if this product meets all of your
requirements. The warranted shelf life of our products is six months from date of shipment to the original purchaser.
FPDS81-10 R0514
32-17
Product Data Sheet
APPLICATION CONSISTENCY:
Brush, trowel, caulking gun or power extrusion
FOSTER® SAFETEE™ DUCT SEALANT is a fire-resistive, fibrated,
AVERAGE WEIGHT / U.S. GALLON (ASTM D1475): water-based, indoor/outdoor vapor barrier sealant for low, medium
11.6 lbs. (1.35 kg/l) and high velocity heating and air conditioning ducts. It performs as a
tough and flexible adhesive and sealant, forming a durable seal
AVERAGE NON-VOLATILE (ASTM D2369): against air leakage when used with or without reinforcing tape or
55% by volume (69% by weight) membrane. Mechanical fasteners of the type and number normally
used for duct assemblies are required to provide rigidity to the duct
COVERAGE RANGE: system.
Brush: 25 – 50 sq. ft./gal. (0.6 – 1.2 m2/l) 0.064 in. – 0.032 in.
(1.6 mm – 0.8 mm) wet film thickness SAFETEE™ DUCT SEALANT has excellent weather resistance, low
water vapor permeance and good water resistance, allowing it to be
Caulking Gun: 125 linear ft. per 10.5 fluid oz. tube, 1/8 in. used outdoors and in high humidity environments. It is U.V. resistant.
bead (38 m per 0.31 liter tube, 3.2 mm bead) When dry, it may be painted with good quality, water-based paint.
30 linear ft. per 10.5 fluid oz. tube, 1/4 in. bead (9 m per 0.31
liter tube, 6.4 mm bead) SAFETEE™ DUCT SEALANT may be pressure tested within 16
hours dry time above 70ºF (21ºC) and below 60% RH. It quickly
SERVICE TEMPERATURE LIMITS: forms a strong bond to galvanized, aluminum or mild steel metal
20ºF to 200ºF (-7ºC to 93ºC) ducts. It has a mild odor when wet.
DRYING TIME 73ºF (23ºC) 50% RH: SAFETEE™ DUCT SEALANT will meet all SMACNA pressure
Set to Touch: 1 hour classes up to 10" w.g. and SMACNA seal classes A, B and C on
Dry Through: 24 hours ducts constructed to SMACNA standards. It has been tested up to
15" w.g. and passed with no sealant blow out.
SHORE HARDNESS (ASTM D2240):
Type A: 80 SAFETEE™ DUCT SEALANT 32-17 meets the requirements of:
MAS Certified Green®
WATER VAPOR PERMEANCE (TYPICAL AVERAGE): California Dept. of Public Health Standard Method v1.2
ASTM E96, PROCEDURE A: 0.45 perms (0.30 metric perms)
VOC Emissions and Content requirements to contribute to
at 35 mils (0.9 mm) dry thickness
LEED v4 EQ Credit: Low Emitting Materials – Paints
WET FLAMMABILITY: and Coatings
No flash to boiling, over 210ºF (99ºC) Collaborative for High Performance Schools EQ 7.1
SURFACE BURNING CHARACTERISTICS (ASTM E84): VOC Content: 45 g/l, less water and exempt solvents.
Flame Spread: 5
Smoke Developed: 0
Tested as applied in two 2 in. wide strips spaced 8 in. on
center at a coverage rate of 25 sq. ft./gal. Applied to 1/4 inch
(6.4 mm) inorganic reinforced cement board. The flame
spread may vary at different product thicknesses and/or when LIMITATIONS
applied over other surfaces. Store and apply between 40ºF (4ºC) and 100ºF (38ºC), protect from
freezing until dry.
SAFETEE™ DUCT SEALANT is produced under the
classification and follow-up service of Underwriter’s To resist rain washoff, allow at least 12-15 hours drying time above
Laboratories, Inc. and meets NFPA 90A and 90B 25/50 40ºF (4ºC), with a relative humidity of 50%. Higher humidity or lower
requirements. It is approved for use in the City of Los temperatures may retard drying.
Angeles, application number M-960081.
Always test foil and paper facings for acceptable adhesion.
Outdoor horizontal surfaces must always drain completely. A pitch of
at least 1/2 inch per foot (4 cm/m) is required.
™ Trademark of H.B. Fuller Construction Products Inc. If used between impermeable surfaces, drying time will be extended.
UL 181B-M
MATERIAL PREPARATION
DO NOT THIN. Apply only to clean, dry, oil-free surfaces. Keep container closed when not in use.
APPLICATION
UL 181B MASTIC CLOSURE OF UL 181 FLEXIBLE AIR DUCTS:
Apply to clean, dry, oil-free surfaces by brush, trowel or power extrusion. Uniformly brush out a 2” wide coat over the joint, at the
nominal rate of 2 gal./100 sq. ft. (0.8 l/m2). Total coverage rate to be 45 – 55 sq. ft./gal. (1.1 – 1.4 m2/l). Allow the completed joint to
dry at least 24 hours above 70ºF (21ºC) before pressure testing. High humidities (over 70%) and/or cooler temperatures may retard
drying. Total wet film thickness to be 32 mils +/- 3 mils.
OTHER SEALING APPLICATIONS – NOT UL 181:
Apply a continuous film of FOSTER® SAFETEE™ DUCT SEALANT over all areas of the indoor or outdoor duct system where air
leakage may occur. A brush may be used to work the sealant into joints and remove excess. On spiral ducts, apply a coat to the male
end of the coupling prior to fitting the straight run of spiral duct over it. Brush excess SAFETEE™ DUCT SEALANT over the joint to
complete the seal. Screw holes and flanges should also be sealed with a coat of SAFETEE™ DUCT SEALANT. It may be applied to
the inside or the outside of the duct.
POWER EXTRUSION:
SAFETEE™ DUCT SEALANT may be applied using a wide variety of power (pressure) extrusion equipment suitable for use with
water-based sealants. It is a soft buttery gel with a typical viscosity range of 130,000 – 160,000 cps. Corrosion resistant pumps and
fittings are suggested.
TOP COATING
After it is completely dry, SAFETEE™ DUCT SEALANT may be top coated with good quality water-based paint.
CLEAN UP
Use fresh water to clean brushes and equipment before product dries. Dry product may be removed with hot soapy water or strong
solvent such as chlorinated solvent (non-flammable) or xylol (flammable).
UL 181B-M
6P84
ALSO CLASSIFIED for
Surface Burning Characteristics
312U
ADEQUATE TESTS: The information contained herein we believe is correct to the best of our knowledge and tests. The recommendations and suggestions herein are made
without guarantee or representation as to results. We recommend that adequate tests be performed by you to determine if this product meets all of your requirements. The
warranted shelf life of our products is twelve months from date of shipment to the original purchaser or as otherwise provided on the certificate of analysis.
Accredited
Standards & California Dept. of Public Health Standard Method v1.2 classroom & private office
Test Methods:
Certified Group 4: HVAC Sealants: 32-16, 32-17**, 32-18, 32-19, CP-146, CP-147,
Products: CP-148, CP-181, CP-181-1, FDS-181, G-347.
**Product tested as representative exemplar of product bracket listed above.
Test Date: September 27, 2022 Report No.:2200701 Certificate No.: MAS2200701-R1
1200 WILLOW LAKE BLVD VADNAIS HEIGHTS, MN 55110 651/236-5300 FAX 651/236-5485 www.fosterproducts.com
(lb/gal):
*The VOC information presented here is calculated based on the theoretical VOC contribution of each
ingredient in each formulation. The VOC information for each ingredient is either measured using EPA
Method 24 (40 CFR 60 Appendix A), or per composition data as reported to us by the supplier (40 CFR
63.827(b)).
Sealants:
Architectural: 250 g/l, less water and exempts
Other: 420 g/l, less water and exempts
*The VOC information presented here is calculated based on the theoretical VOC contribution of each ingredient in
each formulation. The VOC information for each ingredient is either measured using EPA Method 24 (40 CFR 60
Appendix A), or per composition data as reported to us by the supplier (40 CFR 63.827(b)).