Professional Documents
Culture Documents
Enclosure B158 Installation Procedure - MOP
Enclosure B158 Installation Procedure - MOP
Unpack and
check the material
Prepare ground
attachments
Connect incoming
alarm cables
Verify enclosure
installation on site
Perform
concluding routines
Ge15058A
Note: The enclosure must not be left in an outdoor environment more than one
week before taking it into service. If high humidity or cold temperatures
applies, the enclosure must be taken into service within 48 hours.
Steps
Ge7236C
Ge6678E
3. Check that the items delivered
correspond to the packing list.
Ge7263C
Ge8582A
3 Prepare Ground Attachments
Prerequisites
Figure 7 shows the minimum distances recommended to provide adequate
working space.
200
680
200
Steps
1. Check the Customer Site Documentation for what material to install on.
Check that the leveling of the concrete base is made according to the
specified tolerances.
Front
16 mm
70 mm
Ge14801A
4. Remove the nuts and washers of the expansion screws and insert the screws
into the mounting holes.
When the expansion screws are in place, make sure that the exposed part
outside the ground is about 30 mm.
Note: All the installation alternatives described in this section require at least
two people.
Note: Make sure not to scratch or damage the surface of the cabinet. A
damaged surface decreases the resistance to external factors, such as
weather and wind and can, for example, lead to rust formation. When
moving the cabinet, place a soft material under the cabinet not to
damage it.
4.1 Use a Pallet Truck to Move the Enclosure
To move the enclosure using a pallet truck:
Steps
Ge1692A
Ge1693A
Steps
Ge1693A
Ge1695A
Ge15063A
Steps
200mm
600mm Ge15064A
640mm
Ge15065A
850mm
Ge15066A
Ge15067A
5 Mount the Enclosure
Steps
Ge14803A
Ge15067A
4×
Ge14805A
6 Ground the Enclosure
The enclosure is equipped with a MET on the bottom right hand side in front of
the battery space. The enclosure ground cable must be a 35-mm2 green and
yellow cable.
Steps
A F
B G
C H
D I
E J
Ge14797B
Ge14806A
3. Pierce the rubber cover.
Ge14807A
Ge14808A
11 Nm
Ge14809A
Ge15018A
7. Connect the other end of the ground cable to a site grounding terminal.
7 Install the Kit for Additional Battery Strings
To support four battery strings, a kit for additional batteries must be installed.
The kit consists of two −48 V DC internal battery cables, two 0 V DC internal
battery cables, and two battery shelves.
The shelves are installed in positions 2 and 4 starting from the bottom of the
cabinet.
Steps
Horizontal alignment
PH 2
8×
3.2 Nm
Ge15044A
3. Place the second additional
battery shelf in the wanted
location and attach it to place.
PH 2
8×
3.2 Nm
Ge15044A
4×
PH 2
1.2 Nm
Ge15071A
5. PH 2
Attach the 900 mm −48 V DC
internal battery cable to terminal 2
and the 1100 mm −48 V DC
internal battery cable to terminal 4
Terminal 4
4 Nm
on the left side of the enclosure.
Terminal 2
6. PH 2
Attach the 900 mm 0 V DC
internal battery cable to terminal 2
and the 1400 mm 0 V DC internal
battery cable to terminal 4 on the
4 Nm
Terminal 4
right side of the enclosure.
Terminal 2
Four battery blocks must be installed on each shelf. The four battery blocks to be
installed are referred to as battery block 1, 2, 3, and 4. The numbers refer to the
battery block positions on the battery shelves from left to right.
1 2 3 4
Battery string 4
(optional)
1 2 3 4
Battery string 3
(optional)
1234 4321
1 2 3 4
Battery string 1
Ge15591A
Figure 9
— Only install the battery blocks of the same type or a corresponding type that
the manufacturer recommends.
— Do not mix different battery types or mix new and old batteries together.
— The circuit breaker (CB) for the actual battery string must be switched off at
the DC Distribution.
Depending on the size of the batteries, remove the battery shelf side bars and
adjust the back bar position, as follows:
— PH 2
1.2 Nm
2
Ge15075A
PH 2
1.2 Nm Ge15074A
Steps
4×
PH 2
Ge14815A
Ge614047
Ge14635A
4. Put the pole protection caps on all the battery blocks. Remove the knock-
outs in the pole protection caps. Put the top part on the battery blocks.
Ge614055
Ge14626A
Ge14652A
D I
E J
Ge14797B
Ge14653A
8.1.4 Connect the Battery Blocks
This section describes how to connect interblock connectors and cables to the
battery blocks.
Steps
1. Connect the end of the −48 V DC battery cable to the negative (−) pole of the
leftmost battery block. Tighten the bolt to the torque given on the battery
front label.
- 48 V
13 mm
Ge614049
13 mm
-48 V
G110761A
2. Attach the interblock connectors between the battery blocks. Tighten the
bolts to the torque given on the battery front label.
- 48 V
13 mm
Ge614051
13 mm
- 48 V
G110810A
3. Connect the end of the 0 V DC battery cable to the positive (+) pole of the
rightmost battery block. Tighten the bolt to the torque given on the battery
front label.
- 48 V
13 mm
0V
Ge614053
-48 V
0V
G110763A
5. Cable Tie
Use cable ties to secure cables to
Tool
the side frame of the enclosure on
both sides.
Ge15012A
Steps
1. Make sure that the pole protection caps have been placed over the battery
block poles.
Ge614055
G110825A
Ge14626A
4×
PH 2
1.2 Nm
Ge15042A
Ge15076A
Steps
4×
PH 2
Ge14815A
Ge14652A
D I
E J
Ge14797B
Ge14653A
8.2.4 Connect the Battery Blocks
This section describes how to connect interblock connectors and cables to the
battery blocks.
Steps
Ge14632A
G109559B
G109560B
4. Connect the end of the 0 V DC
13 mm
battery cable to the positive (+)
- 48 V pole of the rightmost battery
block. Tighten the bolt to the
torque given on the battery front
label.
0V
G109561B
6. Cable Tie
Use cable ties to secure cables to
Tool
the side frame of the enclosure on
both sides.Use cable ties to secure
cables to the side frame of the
enclosure.
Ge15012A
8.2.5 Secure the Battery Blocks
Steps
G109562B
4×
PH 2
1.2 Nm
Ge15042A
Ge15076A
9 Connect the DC Power Cable
The DC power cable, which powers the air conditioner and the ventilation fan,
must be connected to the DC distribution system of an external Ericsson power
system, for example, an enclosure.
Steps
A F
B G
C H
D I
E J
Ge14797B
Ge14813A
3. Connect the −48 V DC and 0 V DC
wires to the matching terminal
0 V DC
pins.
–48 V DC
4 mm
0.55 Nm
Ge14812A
Enclosure B158 provides a three-way dry alarm contact output. Alarm terminals
are quick-connect terminals, with a wire diameter of up to 1.5 mm2. They are
located on the left side of the cabinet.
To connect the external alarm cables.
Steps
A F
B G
C H
D I
E J
Ge14797B
Ge14813A
3. Strip about 100 mm of the cable
outer jacket and attach the
exposed cable screen to the
grounding point on the DIN rail
1.2 Nm Ge15693A
Alarm
output cable
Ge14814A
Use a twisted pair for each of the three alarms. Mark down which pairs are used
for which alarms.
5. Press the orange pressure contact point with the slotted screwdriver, and
insert the wires into the corresponding sockets.
6. Plug the alarm output terminal back into the alarm board socket after the
alarm cable connection is completed.
7. Cable Tie
Route and secure the cables.
Tool
Ge15011B
Ge15018A
11 Startup Procedure
This section contains information on how to start up the system.
Steps
1. Check that all cables are connected according to the instructions in this
document.
2. Check that the external power cables are correctly connected in the external
power system according to the instructions in the Customer Site
Documentation and the instructions that are applicable for the external
power system.
— Check that the battery temperature sensors are correctly connected to its
external control system.
— Check that the battery temperature reading is within the normal range.
5. Turn on the air conditioner power from the external power system.
7. Turn on the PDU or the battery circuit breaker switches in the external power
systems.
Steps
Ge9550A
Ge12428A
2. Customer Site
Fill in the verification checklist in
Documentation the Customer Site Documentation.
Hand over the Customer Site
Documentation to the person
responsible for the site. Report any
faults according to local
requirements.
Ge7263E
Ge9552A