Professional Documents
Culture Documents
Distribution Activity 5
Distribution Activity 5
Distribution Activity 5
DISTRIBUTION SYSTEM
Presented by:
Peter Carlo A. Dabalus
Presented to:
Engr. Alfred G. Vasquez
2023
CHAPTER 5
Substation Design
Substation Load Graphs
1600
1400
1200
1000
800
600
400
200
0
h h h h h h h h h h h h h IN
000 200 400 600 800 000 200 400 600 800 000 200 400 M
0 0 0 0 0 1 1 1 1 1 2 2 2
14000
12000
10000
8000
6000
4000
2000
0
h h h h h h h h h h h h h h h h h h h h h h h h h
000 100 200 300 400 500 600 700 800 900 000 100 200 300 400 500 600 700 800 900 000 100 200 300 400
0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2
10000
8000
6000
4000
2000
0
h h h h h h h h h h h h h h h h h h h h h h h h h
000 100 200 300 400 500 600 700 800 900 000 100 200 300 400 500 600 700 800 900 000 100 200 300 400
0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2
24000
20000
16000
12000
8000
4000
0
h h h h h h h h h h h h h h h h h h h h h h h h h
000 100 200 300 400 500 600 700 800 900 000 100 200 300 400 500 600 700 800 900 000 100 200 300 400
0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2
Maximum Demand
Power Transformer Capacity =
Capacity Factor
26,014.63
Power Transformer Capacity =
0.70
Power Transformer Capacity = 37,163.77 kVA
Use: 40 MVA Power Transformer, 69/13.8 kV, 60 HZ
Power Transformer Specification
The selection of power transformer is a vital part in the design of a substation. This
A. Rating
Three Phase 20/26/33 MVA with OA/FA1/FA2 type suitable for outdoor
installation.
B. Frequency
C. Impedance
8.12 %
67 kV/13.8 kV
350 kV/110 kV
F. Primary Connection
Delta
G. Secondary Connection
I. Insulating Fluid
Mineral Oil. The oil will have the properties specified in CNS 3070 and CNS
J. Sound Level
65°C
65°C
M. Tap-changer
The transformer technical requirements are also specified to assure that the power
transformer will meet the international standard for its quality and performance.
A. Core
The core of the transformer will be constructed of the highest quality, non-aging
high permeability, cold-rolled gain-oriented silicon steel sheet especially suitable
for the purpose. Every care will be taken during slitting and cutting process to
avoid burrs. Both sides of each sheet will be special glass film insulated on to
minimize eddy current losses. The cores will be carefully assembled and rigidly
clamped to ensure adequate mechanical strength to support the windings and also
reduced vibration to minimum under operating conditions.
B. Winding Characteristics
The winding for the transformer shall be made of high tensile strength electrolytic
copper of high conductivity (Class A, in accordance with ANSI) and insulation,
material of high quality shall be free from burrs. The insulation material of windings
and connections shall not shrink, soften or collapse during service. Thermally
upgraded paper shall be used for conductor insulation. The design, construction
and treatment of windings shall give proper consideration to all service factors,
such as high dielectric and mechanical strength of insulation, coil characteristics,
uniform electrostatic flux distribution, prevention of corona formation, and
minimum restriction to oil flow. Adequate barriers shall be provided between
windings and core as well as between high voltage and low voltage windings. All
leads or bars from the windings to the terminal boxes and bushings shall be rigidly
supported.
C. Short Circuit Withstand Capability
The transformer shall withstand the combined effects of thermal, mechanical and
electromagnetic stresses arising under short-circuit conditions based on the
maximum durations of fault:
67 kV: IF= 40 kA
13.8 kV: IF = 25 kA
E. Overload Capability
F. Transformer Tanks
The tank should have sufficient strength to withstand full vacuum and internal
pressure of 1.0 kg/cm2, with cooling equipment & conservator connected. The
tank cover will be clamped with bolts and nuts and will be provided with handhole
or manholes of suitable size. All seams and joints will be oil tight. Guides within the
tank will be furnished to facilitate tanking and untanking, and to prevent movement
of the core and coil assembly during transit. The casing will be provided with
suitable lugs for lifting the completely assembled transformer filled with oil. All
gaskets will be synthetic rubber bonded cork.
G. Bushing Assembly
High Voltage Side – ABB model: GOB 325/800LF123027-K72.5 kV, 800 Amps,
350kV BIL, Creepage Distance: 1980mm, Condenser type with 1 unit bushing for
spare.
Low Voltage Side - 2000 Amps, 15.5 kV, 110 kV BIL with 1 unit bushing for spare,
Creepage Distance: 400mm. Test tap should be provided for each unit.
H. Cooling Systems
The transformer will be provided with sets of radiators for self-cooled (OA)
operation with equal sets on both side of the tank. The radiator will be installed on
the tank via radiator valves, so that each radiator can be detached from the tank
independently of the oil in the main tank. The radiator valves will have the open
and close positions clearly marked. Radiators will be equipped with provisions for
draining. Radiators shall be made of galvanized steel. For future forced-air-cooled
operation, transformer must have cooling-fans mounting provision on the radiators
and its control box.
I. Forced-air-cooling system
J. Gaskets
The gaskets shall be compatible for the insulating fluid in the transformer tank.
Metal surfaces to which gaskets are applied shall be smooth and shall have
sufficient rigidity to assure proper compression of the gaskets.
K. Grounding Provisions
M. Painting
The standard finish will consist of one rust resisting primary coat and two finish
coats of paint. The paint will be applied after the steel surface had been thoroughly
cleaned by shot blasting and treated with rust inhibitor. The color of the final coat
for transformer will be ANSI 70 light gray.
3. Neutral
O. Nameplates
2. Oil temperature indicator and relay type AKM OTI series 34, with alarm & trip
contacts; AKM OTI remote mount thermometers remote output: current loops: 4
to 20mA; Resistive Pt 100
3. Two (2) winding temperature indicators and relays for HV and LV windings, with
three (3) contacts each for alarm, tripping & fan control, AKM type WTI series
35; AKM WTI remote mount thermometers
9. Hand-hole, lifting eye for the tank cover and lifting lug for the completely
assembled unit filled with oil.
10. Steel ladder, jacking pad, anchor bolts and skid base with pulling eye.
The last part of the specifications contains the necessary tests that will be conducted
Test (FAT) will be conducted by a representative of DLPC to witness that the unit
passed all the test required. This should be strictly complied in order to avoid
opportunity loss if the power transformer delivered will be found defective at site. If
this scenario happens, it will affect the reliability of the system thus causing
discomfort to the customers. Lastly, it will entail profit loss for the company because
of the unscheduled downtime.
The following routine tests based on ANSI C57.12.00 and ANSI C57.12.90 must be
performed to the power transformer:
D. Measurement of no-load loss and excitation current at 90%, 100% & 110% of
rated voltage and frequency.
L. Leak test
O. Voltage regulation
R. Short circuit withstand capability type test certification from third party