Professional Documents
Culture Documents
Electric Comment 26 20 00
Electric Comment 26 20 00
d. Motor sheaves that are variable pitch for 20 kW and below. Select
variable pitch sheaves to drive the fan at a speed that produces the
specified capacity when set at the approximate midpoint of the sheave
adjustment. Furnish motors for V-belt drives with adjustable bases,
and with totally enclosed enclosures.
Provide access sections where indicated and furnish with access doors as
shown. Construct access sections and filter/mixing boxes in a manner
identical to the remainder of the unit casing and equip with access
doors. Design mixing boxes to minimize air stratification and to promote
thorough mixing of the air streams.
2.12.1.1 Enclosure
Nickel chromium heating wire element, free from expansion noise and 60 Hz.
Embed element in magnesium-oxide insulating refractory. Seal element in
high-mass steel or corrosion-resisting metallic sheath with fins. Enclose
element ends in terminal box. Provide not more than six fins per 25 mm.
Limit fin surface temperature 285 degrees C at any point during normal
operation.
2.12.1.3 Controls
2.12.1.4 Wiring
2.12.1.5 Thermostats
SECTION 23 00 00 Page 19
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
2.8.2 Relays
Relays must have contacts rated for the intended application, indicator
light, and dust proof enclosure. The indicator light must be lit when the
coil is energized and off when coil is not energized.
Control relay contacts must have utilization category and ratings selected
for the application. Each set of contacts must incorporate a normally
open (NO), normally closed (NC) and common contact. Relays must be rated
for a minimum life of one million operations.
The Current Sensing Relay portion must meet all requirements of the
Current Sensing Relay input device. The Command Switch portion must meet
all requirements of the Relay output device except that it must have at
least one normally-open (NO) contact.
Current Sensing Relays used for Variable Frequency Drives must be rated
for Variable Frequency applications unless installed on the source side of
the drive. If used in this situation, the threshold for showing status
must be set to allow for the VFD's control power when the drive is not
enabled and provide indication of operation when the drive is enabled at
minimum speed.
SECTION 23 09 13 Page 12
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
j. Keys: two provided with each lock, with all locks keyed alike.
UL 489, UL 1699 and NFPA 70. Molded case circuit breakers: rated as
indicated. Provide with "push-to-test" button.
Provide panelboards and breakers for use on 400 Hz systems rated and
labeled "400 Hz."
SECTION 26 20 00 Page 18
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
a. UL 508, NEMA ICS 1, NEMA ICS 2, EN 60079 (for hazardous areas) and EN
61439 (for switchgear and control gear assemblies).
c. Provide controllers for motors rated 1-hp and above with electronic
phase-voltage monitors designed to protect motors from phase-loss,
undervoltage, and overvoltage.
g. Safety control devices, such as low and high pressure cutouts, high
temperature cutouts, and motor overload protective devices: connected
in motor control circuit in "hand" and "automatic" positions.
SECTION 26 20 00 Page 19
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
MTW meeting UL 1063, and passing the VW-1 flame tests included in
those standards.
c. Current transformer secondary leads: not smaller than 6 mm2 (No. 10 AWG
).
e. Power wiring for 380-volt circuits and below: the same type as
control wiring with (No. 12 AWG) minimum size.
a. NEMA ICS 4.
d. Terminals: not less than No. 10 in size with sufficient length and
space for connecting at least two indented terminals for 10 AWG
conductors to each terminal.
f. Modular, pull apart, terminal blocks are acceptable provided they are
of the channel or rail-mounted type.
g. Submit data showing that any proposed alternate will accommodate the
specified number of wires, are of adequate current-carrying capacity,
and are constructed to assure positive contact between
current-carrying parts.
b. Load Type: Load terminal blocks rated not less than 600 volts and of
adequate capacity: provided for the conductors for NEMA Size 3 and
smaller motor controllers and for other power circuits, except those
for feeder tap units. Provide terminals of either the stud type with
contact nuts and locking nuts or of the removable screw type, having
length and space for at least two indented terminals of the size
SECTION 26 20 00 Page 20
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
NEMA ICS 6.
Provide with "start/stop" momentary contacts having one normally open and
one normally closed set of contacts, and red lights to indicate when motor
is running. Stations: heavy duty, oil-tight design.
Single, Double and Three pole designed for surface mounting with overload
protection.
Provide yoke-mounted, seven element LED cluster light module. Color: green.
2.17 BACKBOARDS
SECTION 26 20 00 Page 21
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
2.6.5 Insulation
a. NEC low voltage wires shall be rated 600V, shall have a minimum
temperature rating of 90 deg C dry/75 deg C wet, and shall conform to
UL Standards according to the particular type (e.g. UL 83 for
THHN/THWN and UL 44 for XHHW).
b. SSA 55 type low voltage wires shall be rated 450/750V, shall have a
minimum rating of 85 deg C, and shall meet the flame test of
IEC 60332-3-21.
(2) Power & Lighting (600V and below) 4mm square (12 AWG)
ASTM B1, solid bare copper wire for sizes 10 mm2 (No. 8 AWG) and smaller
diameter; ASTM B8, Class B, stranded bare copper wire for sizes 16 mm2 ( No.
6 AWG) and larger diameter.
SECTION 26 20 00 Page 13
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
3.1.10 Splices
SECTION 26 20 00 Page 31
100% Site and Facility Design Submittal
RSLF Artillery Brigade Al Yamama
Eastern Province, Kingdom of Saudi Arabia
Pipe hangers, inserts, guides, and supports: to MSS SP-58 and MSS SP-69.
2.5.8 Escutcheons
Provide one piece or split hinge metal plates for piping entering floors,
walls, and ceilings in exposed spaces. Secure plates in place by internal
spring tension or set screws. Provide polished stainless steel plates or
chromium-plated finish on copper alloy plates in finished spaces. Provide
paint finish on metal plates in unfinished spaces.
2.6 PUMPS
2.6.1 Construction
SECTION 23 64 26 Page 13
100% Site and Facility Design Submittal