I614e V109 N3000-PLC-SpecialChannels
I614e V109 N3000-PLC-SpecialChannels
NORIMOS 3000
V109-N3_ALA
PLC – Special Channels Page 1 / 7
NORIMOS 3000
PLC Special Cannels
NORIS Marine Systems GmbH & Co. KG • Muggenhofer Strasse 95 • D - 90429 Nürnberg
Fon +49 (0) 911 32 01 - 0 • Fax +49 (0) 911 32 01 - 150 • info@noris-automation.com • http: // www.noris-automation.com
Info 614e
NORIMOS 3000
V109-N3_ALA
PLC – Special Channels Page 2 / 7
Change log
Document: I614e_V109_N3000-PLC-Special-Channels.doc
Content
1 P Channels ......................................................................................................................... 3
2 D Channels ......................................................................................................................... 6
NORIS Marine Systems GmbH & Co. KG • Muggenhofer Strasse 95 • D - 90429 Nürnberg
Fon +49 (0) 911 32 01 - 0 • Fax +49 (0) 911 32 01 - 150 • info@noris-automation.com • http: // www.noris-automation.com
Info 614e
NORIMOS 3000
V109-N3_ALA
PLC – Special Channels Page 3 / 7
1 P Channels
P Channels are data, that are delivered from the firmware to the PLC.
P2: statically Horn 1 is necessary. That is the result out of the alarm state of the known
channels, not depending of the duty state of the node.
from: N3-ALA-1.12q: Horn groups, that are necessary, according to alarm state.
statically P2-1: Horn group 0 is necessary ( channel spec: 0x00 )
P2-2: Horn group 1 is necessary ( channel spec: 0x20 )
…
P2-8: Horn group 7 is necessary ( channel spec: 0xE0 )
P3: Free
P5: Pulse P5-1: Acoustical acknowledgement came from keyboard or channel input
from N3-ALA-1.14ja and N3-ALA-1.24ja:
Pulse P5-7: Acoustical acknowledgement came from keyboard.
Pulse P5-8: Acoustical acknowledgement came from channel input
P8: statically P8-1: Engineer call is active, single or all engineer call
statically P8-2: All engineer call is active
P9: Free
from N3-ALA-1.12ra:
statically P9-1: Display buzzer has to be switched on, resulting bit of:
statically P9-2: Engineer alarm came from CANbus
statically P9-3: NO DUTY alarm came from CANbus
statically P9-4: Engineer call is active
statically P9-5: An alarm is active, acoustically not accepted
NORIS Marine Systems GmbH & Co. KG • Muggenhofer Strasse 95 • D - 90429 Nürnberg
Fon +49 (0) 911 32 01 - 0 • Fax +49 (0) 911 32 01 - 150 • info@noris-automation.com • http: // www.noris-automation.com
Info 614e
NORIMOS 3000
V109-N3_ALA
PLC – Special Channels Page 4 / 7
P11: statically P11-1: All engineer call was broadcasted ( that is an answer after the instruction of
PLC channel D1
P14: Pulse P14-1: Optical acknowledgement came from keyboard or channel input
from N3-ALA-1.14ja and N3-ALA-1.24ja:
Pulse P14-7: Optical acknowledgement came from keyboard.
Pulse P14-8: Optical acknowledgement came from channel input
P17..P20: statically Bitwise declaration for the duty state of all nodes
P17: node 7... 0,
...,
P20: node 31...24
NORIS Marine Systems GmbH & Co. KG • Muggenhofer Strasse 95 • D - 90429 Nürnberg
Fon +49 (0) 911 32 01 - 0 • Fax +49 (0) 911 32 01 - 150 • info@noris-automation.com • http: // www.noris-automation.com
Info 614e
NORIMOS 3000
V109-N3_ALA
PLC – Special Channels Page 5 / 7
NORIS Marine Systems GmbH & Co. KG • Muggenhofer Strasse 95 • D - 90429 Nürnberg
Fon +49 (0) 911 32 01 - 0 • Fax +49 (0) 911 32 01 - 150 • info@noris-automation.com • http: // www.noris-automation.com
Info 614e
NORIMOS 3000
V109-N3_ALA
PLC – Special Channels Page 6 / 7
2 D Channels
D channels are data, that are delivered from the PLC to the firmware.
D1: D1-1: Create engineer call via CANbus. Having done this is messaged via P channel
P11.
D7: D7-1: Do not deliver any acoustical or optical acceptance from bottom, neither to the
operating system nor do broadcast on CANbus
D7-2: Do not broadcast any acoustical acceptance from bottom on CANbus
D7-3: Do not broadcast any optical acceptance from bottom on CANbus
D7-4: Do not deliver any acoustical acceptance from bottom to the operating system
D7-5: Do not deliver any optical acceptance from bottom to the operating system
D7-6: Any optical acceptance may only accept "visible" channels
NORIS Marine Systems GmbH & Co. KG • Muggenhofer Strasse 95 • D - 90429 Nürnberg
Fon +49 (0) 911 32 01 - 0 • Fax +49 (0) 911 32 01 - 150 • info@noris-automation.com • http: // www.noris-automation.com
Info 614e
NORIMOS 3000
V109-N3_ALA
PLC – Special Channels Page 7 / 7
D8: Do deliver any optical acceptance from CANbus only to the PLC channel P15,
not to the operating system
from N3-ALA-111g;
D8-1: Do deliver any optical acceptance from CANbus only to the PLC channel P15,
not to the operating system
D8-2: Do deliver any acoustical acceptance from CANbus only to the PLC channel
P4, not to the operating system
from N3-ALA-113a;
D8-4: Do not display faded out channels on the front plate oft he IO boxes.
from N3-ALA-112ra;
D8-8: Switch OFF dimmer for the LEDs ( LEDs in light state )
D17: from N3-ALA-112s: The limit value for the insulation is defined by 2 bits ( = 4 levels ). This value is
valid for measuring over the whole box. For measuring of single channels there
are other values.
The limit value is defined by the following table:
D17-2 D17-1 Limit value
0 0 7kOhm
0 1 20kOhm
1 0 50kOhm
1 1 90kOhm