GENSET PER ELECTRICAL

DRAWINGS

9'-0" MIN, SEE NOTE 1


CONCRETE SLAB ON GRADE-
18" THICK W/#4 AT 12" EACH
WAY TOP AND BOTTOM

STANDBY GENSET WITH


SOUND INCLOSURE

SLAB PER PLAN


10" MIN,
TYP
EPOXY DOWEL SEE NOTE 1
A
CLR
2"

TYP
FINISH GRADE
TYP
6",
1'-0", TYP

1'-0"
TYP

STANDARD HOOK, TYPICAL


TYP UNO
3" CLR,

4'-0" MIN, SEE NOTE 1

NOTES: NOTES:

1. INSTALL 12"Ø THREADED ROD, ASTM F593, W/4" MIN EMBED INTO SLAB 1. MINIMUM DIMENSIONS INDICATED FOR BID PURPOSES,
USING HILTI HIT-RE 500-SD EPOXY ANCHORING SYSTEM, INSTALL CONTRACTOR TO VERIFY ACTUAL EQUIPMENT DIMENSIONS
ANCHOR AT EACH MOUNTING HOLE PROVIDED IN EQUIPMENT. WITH EQUIPMENT MANUFACTURER AND INCREASE SIZES AS
NEEDED.
2. SEE 3
S-502

A GENSET PAD SECTION 1 GENSET PAD PLAN


- 0 1/2' 1' 2' - 0 1/2' 1' 2'
1"=1'-0" 1"=1'-0"

Reuse of Documents Client


Drawn SEB Designer CSC
This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the Project
property of GHD Inc. and shall not be reused in whole or Drafting CAR Design
in part for any other project without GHD Inc.'s written Check Check CSC
Title
authorization. © GHD Inc. 2012
Approved
GHD Inc. (Project Director)
718 Third Street Eureka California 95501 USA Date Contract No. 7437A-1
T 1 707 443 8326 F 1 707 444 8330 This Drawing shall not be used Original Size
5 12
S-501
Sht of
Job Project W www.ghd.com Scale AS INDICATED for Construction unless Signed
No Revision Note: * indicates signatures on original issue of drawing or last revision of drawing Drawn Manager Director Date and Sealed For Construction -
Plot Date: 31 December 2012 - 3:03 PM Plotted by: Chris Richards Cad File No: N:\US\san francisco\Projects\10344 sf dpw\8410177 sfdpw firestation 6 egu replacement\06-CAD\Sheets\103448410177 S501.dwg
SHEET GENERAL NOTES

1. SEE SHEET E-101 FOR ADDITIONAL INFORMATION ON CONDUIT ROUTING.


1 2 3
2. SEE SHEET E-501 FOR DETAILS.

3. SEE SHEET E-601 FOR SINGLE LINE DIAGRAM.


(N) JUNCTION BOX (E) POWER PANEL 16
(BELOW (E) MCB) 2 15
4. MAINTAIN 5-FOOT MINIMUM CLEAR SPACE BETWEEN GENERATOR FUEL TANK AND
6" BUILDING IN ACCORDANCE WITH NFPA 30 T22.4.1.1(B).
14
FROM EDGE
A 5. PAINT EXPOSED CONDUIT TO MATCH ADJACENT SURFACES.
5 6. PATCH UNUSED OPENINGS AND REPAIR DAMAGE PER SPECIFICATIONS.
(E) EGU CONTROL PANEL
(E) JUNCTION
AND METERING
N(ATS) BOX
6 15
(E) METER MAIN
LB TO CELL TOWER
4
ON ROOF, N.I.C.
4 LB (N) WIRE GUTTER 3 (N) AUTOMATIC
TRANSFER SWITCH

MIN 4" AFF


J-BOX (BEHIND (E) MAIN CIRCUIT BREAKER
2 1
GUTTER)

24" AFF
(E) SERVICE METER

(E) MAIN PANELBOARD 14 KEYNOTES


EDGE OF WALL (APPROX)
15 1. PROVIDE (N) AUTOMATIC TRANSFER SWITCH ON WALL AS INDICATED. SEE SINGLE LINE
DIAGRAM AND SPECIFICATIONS FOR EQUIPMENT RATINGS. MOUNT BOTTOM OF ATS AT
REMOVE TILE BEHIND GUTTER AS REQUIRED +24" AFF.

(N) WIRE GUTTER FOR INSTALLATION. CLEAN, PATCH, AND 16


3 2. PROVIDE (N) 6"x6"x6"-DEEP JUNCTION BOX IN WALL BELOW (E) PULLING COMPARTMENT
PAINT REMAINING EXPOSED SURFACE.
(BELOW (E) MAIN CIRCUIT BREAKER).

3. PROVIDE (N) 6"x6"x48", MIN. 10 GAUGE SHEET METAL WIRE GUTTER ON WALL BELOW (E)
METER, (E) MAIN CIRCUIT BREAKER AND (E) MAIN PANELBOARD. ALIGN IN FRONT OF (N)
RECESSED JUNCTION BOX.

4. PROVIDE LB AND CONDUIT BETWEEN (N) GUTTER AND (N) ATS. SEE SINGLE LINE
ENLARGED PLAN 0 1' 2' 4'
DIAGRAM FOR CONDUCTOR AND CONDUIT SIZES. ROUTE CONDUIT/FITTING TIGHT TO
WALL.
SERVICE AREA ELEVATION SERVICE AREA 1/2"=1'-0"
1 2 2
5. PROVIDE CONDUIT BETWEEN (N) ATS AND (E) MAIN PANELBOARD. SEE SINGLE LINE
DIAGRAM FOR CONDUCTOR AND CONDUIT SIZES.

6. PROVIDE (N) SURFACE MOUNT EGU ANNUNCIATOR PANEL ON WALL. MOUNT CENTER OF
(N) EGU ANNUNCIATOR PANEL AT +44" AFF.

7. PROVIDE CONCRETE PAD FOR (N) EGU. COORDINATE EXACT DIMENSIONS AND
PENETRATIONS WITH EGU VENDOR. CONCRETE PAD DIMENSIONS SHALL BE 12" WIDER
AND LONGER THAN EGU (6" EACH SIDE).
ROUTE INTERIOR CONDUIT
ALONG ORIGINAL PATH. 3 8. PROVIDE GROUND ROD TEST WELL ADJACENT TO CONCRETE PAD. SEE DETAILS SHEET
E-501.

(N) JUNCTION BOX 13


6 (E) DOOR 9. COORDINATE EXACT LOCATIONS OF CONDUIT STUB-UPS WITH MANUFACTURER SHOP
E-501
12 (E) WINDOW DRAWINGS.
E (N) JUNCTION BOX 12 10. PROVIDE (N) EMERGENCY GENERATOR UNIT, SUB BASE TANK, AND MOUNTING
ACCESSORIES AND MOUNT ON CONCRETE PAD. SEE SINGLE LINE DIAGRAM AND
SPECIFICATIONS FOR EQUIPMENT RATINGS.

TURN CONDUIT UP WALL TO +96" (E) WALL-MOUNTED LIGHT 11. PROVIDE GENERATOR FRAME GROUND. SEE DETAIL 1/E501 FOR CONNECTION
AFG APPROX. (ABOVE WINDOW) BETWEEN EGU FRAME, REBAR AND CU GND ROD.
F 14
12. PROVIDE (N) NEMA 3R JUNCTION BOX ABOVE WINDOW. ROUTE CONDUIT AROUND

HATCHED AREA INDICATES

BUILDING AND FUEL TANK


WINDOW. AVOID CONFLICT WITH (E) WALL-MOUNTED LIGHT.

5'-0" MINIMUM CLEAR


SPACE BETWEEN
INSTALL CONDUIT 15
13. PROVIDE (N) JUNCTION BOX MOUNTED TO CEILING IN OFFICE.
BELOW GRADE
14. PROVIDE 1-1/2" CONDUIT FOR EGU EMERGENCY FEEDER BETWEEN (N) EGU AND (N)
16
ATS. SEE SINGLE LINE DIAGRAM FOR CONDUCTOR SIZES.

15. PROVIDE CONTROL WIRING BETWEEN (N) EGU, (N) EGU ANNUNCIATOR PANEL, AND (N)
ATS IN MINIMUM 1-1/4" CONDUIT. COORDINATE WIRE TYPE AND QUANTITY WITH EGU
MINIMUM CLEARANCE PER MANUFACTURER.
GENERATOR MANUFACTURER 6"
RECOMMENDATIONS 16. PROVIDE (2) #12 AWG AND #12 GND IN MINIMUM 1" CONDUIT FROM (N) EGU BACK TO (N)
(TYP.) CIRCUIT BREAKER IN (E) POWER PANEL FOR (N) EGU BATTERY CHARGER AND JACKET
9
HEATER.
SALVAGED BRICK 17
GROUND ROD 17. REUSE (E) BRICK SALVAGED DURING DEMOLITION TO FILL AREA AROUND GENERATOR
8
TEST WELL PAD. FOLLOW EXISTING PATTERN AND RESTORE SURFACE TO ORIGINAL CONDITION.
(N) CONCRETE
6"
7
GENERATOR PAD
4" CURB
8'-0" (N) EGU 10

(E) WALL 48" 48" 48" (N) REMOVABLE BOLLARD


(TYP. OF 3)

ENLARGED PLAN 0 1' 2' 4'


GENERATOR AREA 1/2"=1'-0"
3

Reuse of Documents Client


Drawn SMG Designer CAR
This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the Project
property of GHD Inc. and shall not be reused in whole or Drafting BNB Design
in part for any other project without GHD Inc.'s written Check Check BNB
Title
authorization. © GHD Inc. 2012
Approved
GHD Inc. (Project Director)
718 Third Street Eureka California 95501 USA Date Contract No. 7437A-1
T 1 707 443 8326 F 1 707 444 8330 This Drawing shall not be used Original Size
10 12
E-202
Sht of
Job Project W www.ghd.com Scale 1/4" = 1'-0" for Construction unless Signed
No Revision Note: * indicates signatures on original issue of drawing or last revision of drawing Drawn Manager Director Date and Sealed For Construction -
Plot Date: 31 December 2012 - 3:09 PM Plotted by: Chris Richards Cad File No: N:\US\san francisco\Projects\10344 sf dpw\8410177 sfdpw firestation 6 egu replacement\06-CAD\Sheets\103448410177 E202.dwg
SHEET GENERAL NOTES

1. CONTRACTOR TO COMPLETE PERMIT APPLICATION CHECKLIST FOR


DIESEL GENERATORS, DIESEL FIRE PUMPS, AND FUEL TANKS SERVING
GENERATORS AND FIRE PUMPS, LOCATED ON DRAWINGS E-701 AND
E-702. APPLICATION IS PARTIALLY COMPLETED WITH INFORMATION
AVAILABLE DURING DESIGN. CONTRACTOR TO REVIEW, UPDATE, AND
CORRECT AS NECESSARY FOR BUILDING DEPARTMENT.

Reuse of Documents Client


Drawn SMG Designer CAR
This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the Project
property of GHD Inc. and shall not be reused in whole or Drafting BNB Design
in part for any other project without GHD Inc.'s written Check Check BNB
Title
authorization. © GHD Inc. 2012
Approved
GHD Inc. (Project Director)
718 Third Street Eureka California 95501 USA Date Contract No. 7437A-1
T 1 707 443 8326 F 1 707 444 8330 This Drawing shall not be used Original Size
11 12
E-701
Sht of
Job Project W www.ghd.com Scale NO SCALE for Construction unless Signed
No Revision Note: * indicates signatures on original issue of drawing or last revision of drawing Drawn Manager Director Date and Sealed For Construction -
Plot Date: 31 December 2012 - 2:53 PM Plotted by: Chris Richards Cad File No: N:\US\San Francisco\Projects\10344 SF DPW\8410177 SFDPW Firestation 6 EGU Replacement\06-CAD\Sheets\103448410177 E701.dwg
SHEET GENERAL NOTES

1. CONTRACTOR TO COMPLETE PERMIT APPLICATION CHECKLIST FOR


DIESEL GENERATORS, DIESEL FIRE PUMPS, AND FUEL TANKS SERVING
GENERATORS AND FIRE PUMPS, LOCATED ON DRAWINGS E-701 AND
E-702. APPLICATION IS PARTIALLY COMPLETED WITH INFORMATION
AVAILABLE DURING DESIGN. CONTRACTOR TO REVIEW, UPDATE, AND
CORRECT AS NECESSARY FOR BUILDING DEPARTMENT.

Reuse of Documents Client


Drawn SMG Designer CAR
This document and the ideas and designs incorporated
herein, as an instrument of professional service, is the Project
property of GHD Inc. and shall not be reused in whole or Drafting BNB Design
in part for any other project without GHD Inc.'s written Check Check BNB
Title
authorization. © GHD Inc. 2012
Approved
GHD Inc. (Project Director)
718 Third Street Eureka California 95501 USA Date Contract No. 7437A-1
T 1 707 443 8326 F 1 707 444 8330 This Drawing shall not be used Original Size
12 12
E-702
Sht of
Job Project W www.ghd.com Scale NO SCALE for Construction unless Signed
No Revision Note: * indicates signatures on original issue of drawing or last revision of drawing Drawn Manager Director Date and Sealed For Construction -
Plot Date: 31 December 2012 - 2:51 PM Plotted by: Chris Richards Cad File No: N:\US\San Francisco\Projects\10344 SF DPW\8410177 SFDPW Firestation 6 EGU Replacement\06-CAD\Sheets\103448410177 E702.dwg