Genset Pad Plan Genset Pad Section: Client Designer Drawn Reuse of Documents SEB CSC
Genset Pad Plan Genset Pad Section: Client Designer Drawn Reuse of Documents SEB CSC
DRAWINGS
TYP
FINISH GRADE
TYP
6",
1'-0", TYP
1'-0"
TYP
NOTES: NOTES:
1. INSTALL 12"Ø THREADED ROD, ASTM F593, W/4" MIN EMBED INTO SLAB 1. MINIMUM DIMENSIONS INDICATED FOR BID PURPOSES,
USING HILTI HIT-RE 500-SD EPOXY ANCHORING SYSTEM, INSTALL CONTRACTOR TO VERIFY ACTUAL EQUIPMENT DIMENSIONS
ANCHOR AT EACH MOUNTING HOLE PROVIDED IN EQUIPMENT. WITH EQUIPMENT MANUFACTURER AND INCREASE SIZES AS
NEEDED.
2. SEE 3
S-502
24" AFF
(E) SERVICE METER
3. PROVIDE (N) 6"x6"x48", MIN. 10 GAUGE SHEET METAL WIRE GUTTER ON WALL BELOW (E)
METER, (E) MAIN CIRCUIT BREAKER AND (E) MAIN PANELBOARD. ALIGN IN FRONT OF (N)
RECESSED JUNCTION BOX.
4. PROVIDE LB AND CONDUIT BETWEEN (N) GUTTER AND (N) ATS. SEE SINGLE LINE
ENLARGED PLAN 0 1' 2' 4'
DIAGRAM FOR CONDUCTOR AND CONDUIT SIZES. ROUTE CONDUIT/FITTING TIGHT TO
WALL.
SERVICE AREA ELEVATION SERVICE AREA 1/2"=1'-0"
1 2 2
5. PROVIDE CONDUIT BETWEEN (N) ATS AND (E) MAIN PANELBOARD. SEE SINGLE LINE
DIAGRAM FOR CONDUCTOR AND CONDUIT SIZES.
6. PROVIDE (N) SURFACE MOUNT EGU ANNUNCIATOR PANEL ON WALL. MOUNT CENTER OF
(N) EGU ANNUNCIATOR PANEL AT +44" AFF.
7. PROVIDE CONCRETE PAD FOR (N) EGU. COORDINATE EXACT DIMENSIONS AND
PENETRATIONS WITH EGU VENDOR. CONCRETE PAD DIMENSIONS SHALL BE 12" WIDER
AND LONGER THAN EGU (6" EACH SIDE).
ROUTE INTERIOR CONDUIT
ALONG ORIGINAL PATH. 3 8. PROVIDE GROUND ROD TEST WELL ADJACENT TO CONCRETE PAD. SEE DETAILS SHEET
E-501.
TURN CONDUIT UP WALL TO +96" (E) WALL-MOUNTED LIGHT 11. PROVIDE GENERATOR FRAME GROUND. SEE DETAIL 1/E501 FOR CONNECTION
AFG APPROX. (ABOVE WINDOW) BETWEEN EGU FRAME, REBAR AND CU GND ROD.
F 14
12. PROVIDE (N) NEMA 3R JUNCTION BOX ABOVE WINDOW. ROUTE CONDUIT AROUND
15. PROVIDE CONTROL WIRING BETWEEN (N) EGU, (N) EGU ANNUNCIATOR PANEL, AND (N)
ATS IN MINIMUM 1-1/4" CONDUIT. COORDINATE WIRE TYPE AND QUANTITY WITH EGU
MINIMUM CLEARANCE PER MANUFACTURER.
GENERATOR MANUFACTURER 6"
RECOMMENDATIONS 16. PROVIDE (2) #12 AWG AND #12 GND IN MINIMUM 1" CONDUIT FROM (N) EGU BACK TO (N)
(TYP.) CIRCUIT BREAKER IN (E) POWER PANEL FOR (N) EGU BATTERY CHARGER AND JACKET
9
HEATER.
SALVAGED BRICK 17
GROUND ROD 17. REUSE (E) BRICK SALVAGED DURING DEMOLITION TO FILL AREA AROUND GENERATOR
8
TEST WELL PAD. FOLLOW EXISTING PATTERN AND RESTORE SURFACE TO ORIGINAL CONDITION.
(N) CONCRETE
6"
7
GENERATOR PAD
4" CURB
8'-0" (N) EGU 10