FACTORY ACCEPTANCE TEST REPORT

UPS
160 KVA UPS
30 KVA UPS
KEOR-T EVO UPS FINAL TEST REPORT

Document Number : INF511-Y01-U749-1-04 OUTPUT VOLTAGE

Serial Number : 2208P1527006 400V 50Hz


Output Power : 30kVA
Legrand Ref. : 311035
Type : UPS KEOR T EVO 30 KVA 1650H P3;30 kW
Input : 400V max.54A 45-65Hz 3Ph+N
Output : 400V 43A 50Hz 3Ph+N

Testing Procedure : INF511-Y01-U737-1-13 Test Engineer : E.Kadız


Test Date : 19.08.2022

Leakage current <.............mA : < 85mA


Touch current : 0,7mA

INPUT OUTPUT Load


R S T
Nominal Voltage (Ph-N) : 3*230V Nominal Voltage : 10% 230,6V 230,4V 230,5V
Minimum Voltage (Ph-N) : 3*140V : 100% 229,7V 229,6V 229,4V
Minimum Voltage (by full load) (Ph-N) : 3*195V Frequency : 50Hz 50Hz 50Hz
Maximum Voltage (Ph-N) : 3*265 Voltage Regulation (dynamic) : <20 ms
Frequency : 45-65Hz Voltage Regulation (Static) : <1%
Maximum Current : 3*54A Crest Factor : 3
Power Factor : >0,99 Nominal Power(VA) : 3*10000
DC Bus Voltage (VDC1 ) : +405V Nominal Power(W) : 3*10000
DC Bus Voltage (VDC2 ) : -405V Over Load (by Mains Operation) : 60s (by %150 Load)
Battery charge : 405V-418 V
Running Test : Ok

PCB Assembly : List of Materials : Serial Number : Firmware Ver :

INVERTER CONTROL BOARD INF518-Y59-L774-1-00 2205E16830126


INVERTER UPCCM76 MODEL-0 INF518-Y59-L574-1-00 2205E16780044 v3.7.8
PARALLELING BOARD INF516-Y59-L814-1-01 2205E16460086
INVERTER IGBT DRIVER BOARD INF517-Y59-L564-1-04 2101E02440036
INVERTER CURRENT SENSE BOARD INF515-Y59-L564-1-02 2204E13310009
BYPASS SNUBBER BOARD INF516-Y59-L214-1-00 2205E16360029

RECTIFIER CONTROL BOARD INF517-Y59-L644-1-02 2206E18390059


RECTIFIER UPCCM76 INF518-Y59-L594-1-00 2205E16800077 v3.5.7
RECTIFIER IGBT DRIVER BOARD INF517-Y59-L564-1-04 2205E13880016
BATTERY CURRENT BOARD INF517-Y59-L544-1-01 2206E18470010
RECTIFIER POWER SUPPLY INF518-Y59-L354-1-03 2205E16560094
RECTIFIER CURRENT SENSE BOARD INF515-Y59-L564-1-02 2204E13310010

FRONT PANEL BOARD INF516-Y59-L954-1-08 2206E18570061 v3,5,8 v3,6,5


INTERFACE BOARD WITH RELAY INF517-Y59-L514-1-01 2205E16430138

OUTPUT CURRENT TRANSFORMER BOARD INF512-Y59-L244-1-08 2205E16200109


TEMPERATURE SENSOR BOARD INF511-Y59-L244-1-05 2205E15330105

Fill non-confirmity report for the faults determined during test.


N.C.R. Number (H.U.B.F.) :

INF511-Y01-U749-1-04

1/1
10 KVA UPS
The following mentioned Products have been tested in typical configuration by
PSC and were found to comply with the essential requirements of
“Council Directive on the Approximation of the Laws of the Member States to
Low Voltage Directive (2014/35/EU)”
Equipment:
Type of Product : Uninterruptible Power Systems
Model Number :

Trade Name :
Produced by:
Manufacture’s Name : LEGRAND FRANCE
Manufacture’s Address : BP 30076-87002 LIMOGES CEDEX FRANCE
Applied Standards:

EN62040-1:2008/A1:2013
Uninterruptible Power Systems (UPS)- Part1:General and safety requirements for UPS .

Manufacture or his authorized representative within EC shall affix the CE


Marking to the products if he ensures the product complies with the
relevant harmonized standards and draws up a declaration of conformity.
The technical report issued by PSC will support you Affix the CE Marking.

Date : December 4, 2020


Report No : 20CE11L107 Venson Huang / Engineering Manager
QUALITY UPS CHECK LIST

Rev.1 Doc. date: 2021.01.15

UPS TEST SAMPLES

N°1 sample test for production lot between 1 and 20 pieces


N°2 pieces for production lot between 21 and 200 pieces
1% for production lot between 201 to 1000 pieces.
0.7% for production lot over 1001 pieces.

TESTED PRODUCT IDENTIFICATION

UPS Code: 311101 UPS S.N. V43KN00001

Lot. Number:______________________________ Lot Quantity: 18

CHECK LIST:

Mechanical verify
Activity description OK KO Notes
Check the material included into the box.
(See Annex 1) √
Check the material included into the accessories bags
(See Annex 1) √
Verify the battery dat a code
(max 8 mont h since production) (if bet ween 8-12 month 210902NV23C/12
is necessary to communicate to Legrand order number √
and UPS s.n. list)

Aesthetichal verify
Activity description OK KO Notes
Quality and color of the UPS gift box
(Ref folder LABE L AND BOX DESIGN) √
External box, Legrand logo
(Ref folder LABE L AND BOX DESIGN) √
Data on different boxes Labels.
(Ref folder LABE L AND BOX DESIGN) √
Labels on the product
(Ref folder LABE L AND BOX DESIGN) √
!! CHE CK THA T ALL BA R CODES ARE CORRECTLY
RED BY BAR CODE REA DER !! √

1
QUALITY UPS CHECK LIST

Technical test & runtime test


Activity description OK KO Notes
Assure batteries are recharged for at least 4 hours after
UPS production . √
Apply a resistive load of 70% UPS active power (W, not
VA) and perform a complete battery discharge. 83%
(See Annex 1) √
Test result is OK if recorded runtime is greater than the
minimum accept able value for the UPS model 7min31sec
(See Annex 1) √
!! Recharge batteries for at least 12 hours !!

!! Check absence of battery voltage in the external
battery terminals when battery breaker is open !!
(only products with internal battery ) √

Final functional test


Test the UPS to verify it performs correctly after Electrical safety tests and battery
recharge before re-packing the unit.
Activity description OK KO Notes
UPS on mains

UPS on battery

Visual control Output waveform visualization with
oscilloscope without load connected √
User interface operation. (USB & RS232)
(Verify the connection between UPS and diagnostic
program trough PC) √

2
QUALITY UPS CHECK LIST

Rev.1 Doc. date: 2021.01.15

UPS TEST SAMPLES

N°1 sample test for production lot between 1 and 20 pieces


N°2 pieces for production lot between 21 and 200 pieces
1% for production lot between 201 to 1000 pieces.
0.7% for production lot over 1001 pieces.

TESTED PRODUCT IDENTIFICATION

UPS Code: 311101 UPS S.N. V46KN00006

Lot. Number:______________________________ Lot Quantity: 9

CHECK LIST:

Mechanical verify
Activity description OK KO Notes
Check the material included into the box.
(See Annex 1) √
Check the material included into the accessories bags
(See Annex 1) √
Verify the battery dat a code
(max 8 mont h since production) (if bet ween 8-12 month 210902NV23C/12
is necessary to communicate to Legrand order number √
and UPS s.n. list)

Aesthetichal verify
Activity description OK KO Notes
Quality and color of the UPS gift box
(Ref folder LABE L AND BOX DESIGN) √
External box, Legrand logo
(Ref folder LABE L AND BOX DESIGN) √
Data on different boxes Labels.
(Ref folder LABE L AND BOX DESIGN) √
Labels on the product
(Ref folder LABE L AND BOX DESIGN) √
!! CHE CK THA T ALL BA R CODES ARE CORRECTLY
RED BY BAR CODE REA DER !! √

1
QUALITY UPS CHECK LIST

Technical test & runtime test


Activity description OK KO Notes
Assure batteries are recharged for at least 4 hours after
UPS production . √
Apply a resistive load of 70% UPS active power (W, not
VA) and perform a complete battery discharge. 83%
(See Annex 1) √
Test result is OK if recorded runtime is greater than the
minimum accept able value for the UPS model 7min40sec
(See Annex 1) √
!! Recharge batteries for at least 12 hours !!

!! Check absence of battery voltage in the external
battery terminals when battery breaker is open !!
(only products with internal battery ) √

Final functional test


Test the UPS to verify it performs correctly after Electrical safety tests and battery
recharge before re-packing the unit.
Activity description OK KO Notes
UPS on mains

UPS on battery

Visual control Output waveform visualization with
oscilloscope without load connected √
User interface operation. (USB & RS232)
(Verify the connection between UPS and diagnostic
program trough PC) √

2
QUALITY UPS CHECK LIST

Rev.1 Doc. date: 2021.01.15

UPS TEST SAMPLES

N°1 sample test for production lot between 1 and 20 pieces


N°2 pieces for production lot between 21 and 200 pieces
1% for production lot between 201 to 1000 pieces.
0.7% for production lot over 1001 pieces.

TESTED PRODUCT IDENTIFICATION

UPS Code: 311101 UPS S.N. V50KN00001

Lot. Number:______________________________ Lot Quantity: 18

CHECK LIST:

Mechanical verify
Activity description OK KO Notes
Check the material included into the box.
(See Annex 1) √
Check the material included into the accessories bags
(See Annex 1) √
Verify the battery dat a code
(max 8 mont h since production) (if bet ween 8-12 month 211006NV23C
is necessary to communicate to Legrand order number √
and UPS s.n. list)

Aesthetichal verify
Activity description OK KO Notes
Quality and color of the UPS gift box
(Ref folder LABE L AND BOX DESIGN) √
External box, Legrand logo
(Ref folder LABE L AND BOX DESIGN) √
Data on different boxes Labels.
(Ref folder LABE L AND BOX DESIGN) √
Labels on the product
(Ref folder LABE L AND BOX DESIGN) √
!! CHE CK THA T ALL BA R CODES ARE CORRECTLY
RED BY BAR CODE REA DER !! √

1
QUALITY UPS CHECK LIST

Technical test & runtime test


Activity description OK KO Notes
Assure batteries are recharged for at least 4 hours after
UPS production . √
Apply a resistive load of 70% UPS active power (W, not
VA) and perform a complete battery discharge. 83%
(See Annex 1) √
Test result is OK if recorded runtime is greater than the
minimum accept able value for the UPS model 7min33sec
(See Annex 1) √
!! Recharge batteries for at least 12 hours !!

!! Check absence of battery voltage in the external
battery terminals when battery breaker is open !!
(only products with internal battery ) √

Final functional test


Test the UPS to verify it performs correctly after Electrical safety tests and battery
recharge before re-packing the unit.
Activity description OK KO Notes
UPS on mains

UPS on battery

Visual control Output waveform visualization with
oscilloscope without load connected √
User interface operation. (USB & RS232)
(Verify the connection between UPS and diagnostic
program trough PC) √

2
QUALITY UPS CHECK LIST

Rev.1 Doc. date: 2021.01.15

UPS TEST SAMPLES

N°1 sample test for production lot between 1 and 20 pieces


N°2 pieces for production lot between 21 and 200 pieces
1% for production lot between 201 to 1000 pieces.
0.7% for production lot over 1001 pieces.

TESTED PRODUCT IDENTIFICATION

UPS Code: 311101 UPS S.N. V50KN00019

Lot. Number:______________________________ Lot Quantity: 6

CHECK LIST:

Mechanical verify
Activity description OK KO Notes
Check the material included into the box.
(See Annex 1) √
Check the material included into the accessories bags
(See Annex 1) √
Verify the battery dat a code
(max 8 mont h since production) (if bet ween 8-12 month 211006NV23C
is necessary to communicate to Legrand order number √
and UPS s.n. list)

Aesthetichal verify
Activity description OK KO Notes
Quality and color of the UPS gift box
(Ref folder LABE L AND BOX DESIGN) √
External box, Legrand logo
(Ref folder LABE L AND BOX DESIGN) √
Data on different boxes Labels.
(Ref folder LABE L AND BOX DESIGN) √
Labels on the product
(Ref folder LABE L AND BOX DESIGN) √
!! CHE CK THA T ALL BA R CODES ARE CORRECTLY
RED BY BAR CODE REA DER !! √

1
QUALITY UPS CHECK LIST

Technical test & runtime test


Activity description OK KO Notes
Assure batteries are recharged for at least 4 hours after
UPS production . √
Apply a resistive load of 70% UPS active power (W, not
VA) and perform a complete battery discharge. 83%
(See Annex 1) √
Test result is OK if recorded runtime is greater than the
minimum accept able value for the UPS model 7min39sec
(See Annex 1) √
!! Recharge batteries for at least 12 hours !!

!! Check absence of battery voltage in the external
battery terminals when battery breaker is open !!
(only products with internal battery ) √

Final functional test


Test the UPS to verify it performs correctly after Electrical safety tests and battery
recharge before re-packing the unit.
Activity description OK KO Notes
UPS on mains

UPS on battery

Visual control Output waveform visualization with
oscilloscope without load connected √
User interface operation. (USB & RS232)
(Verify the connection between UPS and diagnostic
program trough PC) √