Professional Documents
Culture Documents
DNV TecRegNews No 15 2023web
DNV TecRegNews No 15 2023web
15/2023 – TECHNICAL
The MEPC.107(49) requires a sampling point to be installed in a vertical section of the outlet
pipe as close as possible to the 15 ppm bilge separator outlet. There have been several cases
where ships have been detained for not complying with this requirement. This technical news
summarizes this topic.
Vertical section
Horizontal section
An oily water separator (OWS), bilge separator or oil filter- For many OWSs, the effluent pipe is short before the 3-way
ing equipment is required by MARPOL Annex I, Regulation valve and only a small part is vertical, so for many installations
14 to be installed on any ship above 400 GT. The unit shall the sampling point is in the bend of the vertical section and
be of a design approved by the administration and tested extracts the sample from the vertical section (see picture).
and installed according to guidelines in MEPC.107(49) as DNV considers this solution acceptable and in compliance
amended by MEPC.285(70). with the regulations.
DNV AS, Veritasveien 1, 1363 Høvik, Norway, Phone: +47 67 57 99 00, www.dnv.com/maritime DNV Disclaimer of Liability Page 1/1