7251 08 426 Pipeconnections Into Trapezoidalconcrete - 0 - 1

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

REV

CONCRETE APRON REQUIRED


IF REQUIRED, PIPE BRIDGING SLAB TO BE
MWC DRAWING NUMBER
7251/08/426

DESIGNED BY A STRUCTURAL ENGINEER TO

COVER TO PIPE
300 MINIMUM
SUIT SITE GEOTECHNICAL AND WHEEL LOAD
CONDITIONS

CONCRETE
BANDAGE BEHIND 20mm DRAINAGE
AGGREGATE OR NO

INTO SOLID GROUND


FINES CONCRETE

COVER (MIN)
CAST IN BLACK OXIDE CONCRETE
AROUND ANNULUS TO NEXT FULL

400
CODE

300
300 300 300 300 COURSE
(MIN) (MIN)

C
2100 (MAX)

-
NEATLY ROUND

50
NEATLY ROUND
CORNERS CORNERS
100

PIPE TRENCH
MASS CONCRETE
4 METRE (MIN)
NO FINES CONCRETE GEOFABRIC HAUNCH SUPPORT
HAUNCH SUPPORT TO SPRING LINE
& POSITION INSIDE NO FINES CONCRETE
NO FINES TO FULL LENGTH OF BLUESTONE
CONCRETE
(MIN)
250

A SECTION HAUNCH
SUPPORT
D SECTION
- B -
- 100 100
SUBSOIL PIPE

B SECTION
-

100
REINSTATE MINIMUM 150mm THK
CONCRETE CHANNEL TO MATCH
EXISTING PROVIDE MINIMUM SL
81 MESH WITH 40mm COVER TOP

N
FLOW

IO
E CT

FLOW
N
ON
100

PC
RC

FLOW
"X"
LENGTH REQUIRED TO PROVIDE
400mm EARTH COVER TO PIPE N
EXISTING CHANNEL C TIO 2 SECTION FABRIC REPLACE BLUESTONE
50 N E SL81, LAP AS
SAW CUT BREAKOUT OF CONCRETE APPLY REINFORCEMENT C ON BLOCKS
P SHOWN. 50mm
PROTECTIVE COATING TO ALL CUT RC
COVER TO PIPE AND
REINFORCEMENT, REFER NOTE (6) TO EARTH
NEATLY ROUND
CORNERS D
A -

TYP
300
OUTLET 150 ABOVE REMOVE BLUESTONE
- APPLY PROTECTIVE
INVERT OF CHANNEL UNITS CAREFULLY
NOTES: COATING IF
PLAN - CONCRETE CHANNEL REINFORCEMENT AROUND PIPE

1. DETAILS ARE RELEVANT FOR TRAPEZOIDAL OPEN CHANNELS ONLY. FOUND, REFER
NOTE (6) 230

2. SUITABLE FOR PIPE CONNECTIONS WHERE CHANNEL DEPTH IS (MIN) 3 TIMES PIPE DIAMETER. CONCRETE BANDAGE
FOR CONNECTIONS WHERE PIPE DIAMETER IS MORE THAN 1/3 OF CHANNEL DEPTH SIZE AROUND UPPER HALF
SPECIFIC CONNECTION DRAWING TO BE FORWARDED TO MWC FOR APPROVAL. OF PIPE PLAN - BLUESTONE CHANNEL
3. CONCRETE SHALL NOT BE LESS THAN N32. TO BE DIRECTED BY THE PROJECT ENGINEER. C SECTION
-
4. BACKFILL OVER PIPE TO BE COMPACTED UNTIL THE DRY DENSITY IS IN EXCESS OF 95% OFTHE
MAXIMUM DRY DENSITY OBTAINED FROM THE STANDARD COMPACTION TEST AS PER A.S. 1239.

5. ALL PIPES WITHIN THE WATERWAY OR DRAINAGE RESERVE TO BE RUBBER RING JOINTED.

6. APPLY PARCHEM NITOCOTE EP 410 EPOXY COATING (OR EQUIVALENT) TO A MINIMUM THICKNESS
OF 450 MICRON TO ALL SAW CUT SURFACES ON EXISTING PIPELINE / CONCRETE SURFACES.

7. IT IS THE DESIGNER'S RESPONSIBILITY TO ENSURE THAT THE NOMINATED MELBOURNE WATER


STANDARD DRAWINGS ARE SUITABLE FOR PROJECT USE.

COPYRIGHT TITLE
PIPE CONNECTIONS INTO TRAPEZOIDAL CONCRETE
Copyright - This document
is the property of Melbourne AND BLUESTONE OPEN CHANNELS
Water. Use or copying of the DRAINAGE STANDARD DRAWINGS
document in whole or in part,
for other than Melbourne DRAFTER DESIGNER DESIGN MANAGER PROJECT MANAGER
APPROVAL APPROVAL
Water purposes, without the RD JB PROJECT DATUM
Original
MELBOURNE WATER CORPORATION
A FIRST REVISION RD RM RM 25.11.15 written permission of RM VY Size

PROJECT OR ENG. PR. MAN.


Melbourne Water constitutes
DRAFTING CHECK ENGINEERING REVIEW
SCALE
A1 7251/08/426 A
REV DESCRIPTION COMPANY
WO NUMBER
DRAWN
CHECK APP'D
DATE
an infringement of copyright. BS RM NTS CODE MWC DRAWING NUMBER REV