Professional Documents
Culture Documents
Test Features
Test Features
GMR35 Software
Description of Test Features
CONTENTS
TEST MODE........................................................................................................................ 2
TEST JACKS..................................................................................................................... 19
TEST MODE
The test mode is a facility to change from shuntfield to a separate supplied excitation type in order to
perform some special generator or protection tests. The power supply might come from a brake or
test transformer or via a temporary test supply from a station service feeder. By selecting this mode
some software interlockings and restrictions for switching the excitation ON and OFF are skipped or
bypassed e.g. speed and generator CB interlockings, thyristor voltage supervision.
The power source of excitation during test condition is usually a temporary supply which probably is
not designed to cover all load requirements. To prevent an overload during test condition the field
current limiter can be used to keep the test-supply within the admissible limits.
Conditions
Prepare a permanent supply to the excitation busbar.
To select this mode the excitation must be switched off.
When using the current limiter option – set the configuration parameter C21=1 (break/test transform-
er installed) and check the setting of current limitation for temporary supply V1942:
Imaxtst
V1942 = --------------------
0,82 * Ifn
Imaxtst .... maximum admissible AC current of test supply in Amps
(consider the inverse time characteristic of the limiter)
Ifn ........ nominal field current in Amps
Variables
I 503 … selection variable for the "Excitation test" mode.
V1942… IPMXTR2 field current limitation second value (if a reduced limiter value is requested).
Test mode selection
When excitation is switched OFF - set I503 to "1" e.g. via ELTERM for all regulator configurations
(also dual channel regulators). Select menu 5 Terminal Mode to access all internal variables.
It is forced by the software when:
1) the "Master" button (I650) is pressed when excitation is OFF, but only when regulator is configured
as single channel (C4=0), *)
2) FB test mode is selected (I246=1) **)
Consequences when I503=1
1) excitation switches to current regulation = MAN mode.
During OFF condition it is forced to MAN. As soon as excitation is ON and the voltage is within the
regulator setting range – usually between 90% and 110% of nominal generator voltage, a transfer
to AUTO mode is possible.
2) the field current start - setpoint is forced to zero after the start command,
3) the field current limiter parameter is switched to the parameter IPMXTR2 (V1942) to prevent an
overloading of the test supply,
4) the excitation OFF command is released even when the generator CB is closed,
5) the excitation ON command is released even when the speed is below 90%,
6) the excitation ON command starts the break/test start sequence by closing the break/test AC cir-
cuit breaker to activate the separate supply,
7) thyristor voltage supervision is blocked, to prevent an excitation trip when missing ***),
8) the alarm "excit. test mode" appears on the alarm table.
Caution
To select or un-select this mode the excitation must be switch OFF.
During test operation an interruption of the AC supply circuit - e.g. by feeder overcurrent pro-
tection - must be absolutely avoided !
This interruption may harm or even destroy devices of the excitation or the feeder by overvoltages.
The discharge circuit of the excitation is the only device designed to interrupt the high inductive rotor
circuit!
When exciting the machine consider that the brushes and sliprings have a significantly reduced cur-
rent capability at standstill of generator. In that case keep the rotor current below 5% of nominal !
Hazard of burn marks on the sliprings !
Switch excitation back to AUTO mode after finishing the tests, it will not return automatically.
DE Input Simulation
For tests it is useful to force or to suppress signals of a digital input card DE of the AVR to skip inter-
lockings or to prevent unintententional trips.
Each physically wired digital input signal used in the AVR – controlling or feedback signal – is con-
nected to one of 32 inputs of one or several digital input cards DE32.
The 32 inputs of the first card (E00 to E31) are assigned in the firmware of the processor card to the
input variables E0 to E31, the 32 inputs of the second card are assigned to E32 to E63 and so on…
In software mailboxes the input variables E00 to E31 and E32 to E63 are assigned to an internal "I"
variable which are constantly used in the standard software.
To verify the assigned internal variable number please refer to the interface list or logic diagram.
Each digital input which have an assigned internal variable numbers between I200 and I231 is pre-
pared for a simulation mode and its logical status can be forced to HIGH = "1" or LOW = "0" via the
local ELTERM terminal when the simulation mode is activated.
Activation
Select menu 5 Terminal Mode to access all internal variables.
Set variable I700 = 1 to activate the signal simulation mode.
The internal variables I200 … I231 can now be forced.
To change the logical status of the variable I2xy (xy = 00 … 31) you have to select the corresponding
simulation variable V7xy.
Setting the "V7xy" variable to "1" forces the corresponding I2xy to "1" = HIGH,
setting the "V7xy" variable to "-1" forces the corresponding I2xy to "0" = LOW,
setting the "V7xy" variable to "0" leaves I2xy unchanged according status of the assigned input varia-
ble (E...).
De-activation
Setting variable I700 back to zero will de-activate the signal simulation mode.
By this all V7xy variables are forced back to "0" and all simulated inputs will return to their input sta-
tus.
16 digital signals are summarized to one analogue "word" which is transmitted to via bus.
Totally 10 words are available for the LAN covering 10x16=160 digital signals.
The Variables in detail are:
Feedback and status indication: V799, 798, 797, 768,
Alarm indication: V791, 792, 793, 794, 795, 796
For each variable V7xy one simulation variable V3xy is provided.
When activating the simulation mode (I900=>1) all LAN signals remain unchanged but are frozen
means any input signal change during activated simulation (I900=1) will not be recognized.
Activation
Select menu 5 Terminal Mode to access all internal variables.
Set variable I900 = 1 to activate the signal simulation mode.
Each input signal of the LAN variables V799, 798, 797, 768, 791, 792, 793, 794, 795, 796 can now be
forced.
Simulate each input signal of V7xy to "1" by setting variable V3xy to the following value:
Bit 0 = 1 when V3xy = 1 (decimal) = 0.0005 (pu)
Bit 1 = 1 when V3xy = 2 (decimal) = 0.0010 (pu)
Bit 2 = 1 when V3xy = 4 (decimal) = 0.0020 (pu)
Bit 3 = 1 when V3xy = 8 (decimal) = 0.0039 (pu)
Bit 4 = 1 when V3xy = 16 (decimal) = 0.0078 (pu)
Bit 5 = 1 when V3xy = 32 (decimal) = 0.0156 (pu)
Bit 6 = 1 when V3xy = 64 (decimal) = 0.0313 (pu)
Bit 7 = 1 when V3xy = 128 (decimal) = 0.0625 (pu)
Bit 8 = 1 when V3xy = 256 (decimal) = 0.1250 (pu)
Bit 9 = 1 when V3xy = 512 (decimal) = 0.2500 (pu)
Bit 10 = 1 when V3xy = 1024 (decimal) = 0.5000 (pu)
Bit 11 = 1 when V3xy = 2048 (decimal) = 1.0000 (pu)
Bit 12 = 1 when V3xy = 4096 (decimal) = 2.0000 (pu)
Bit 13 = 1 when V3xy = 8192 (decimal) = 4.0000 (pu)
Bit 14 = 1 when V3xy = 16384 (decimal) = 8.0000 (pu)
Bit 15 = 1 when V3xy = 32768 (decimal) = -16.0000 (pu)
De-activation
Setting variable I900 back to zero will de-activate the signal simulation mode.
By this all V7xy and V3xy variables will return to their input status.
@ version
GMR35_20111215 or later
Software details
Default values after restart of regulator: V250 = 0, T37 = 10 = 1s, T46 = 30 = 3s, I460 = 0
Routine implemented in Task 7 (cycle time 100ms)
Test run
1) Select menu 5 Terminal Mode on the local operation terminal to access all internal variables.
2) Determine the value and the direction of the injection signal in p.u.
a negative value => step down, a positive value => step up
e.g. V250 = -0.05 will step down the setpoint by 5%.
3) Determine the duration of the step in 1/10 sec:
e.g. T37 = 50 will apply the disturbance signal V250 for 5 seconds.
4) Determine the pre-/post history time for the trace record in 1/10 sec
5) Start the step injection by setting I460 to "1".
The trace record starts instantly, *)
after T46/10 seconds the setpoint step starts, *)
after T37/10 seconds the setpoint step stops,
after T46/10 seconds the trace record stops *).
(When I460 is set to "0" during injection – the injection will stop immediately).
*) The auto trace feature is available in the standard software GMR35_20121111 or later.
Caution
This software facility serves for test purposes and is therefore UNLIMITED.
Any wrong typed value may bring the generator out of its capabilities (overvoltage, overcurrent). Be-
fore activating the injection please check the values if they are typed correctly, in per unit, the correct
sign, comma on proper place, etc.
Caution
This software facility serves for test purposes and is therefore UNLIMITED.
Any wrong value may bring the generator out of its capabilities (overvoltage, overcurrent).
Before activating the injection please check if the value corresponds to the required interference.
Increase injection signal slowly and check its influence and effect to generator and grid.
Caution
This software function serves only field breaker test purposes when the unit is shut down and must
not be activated when the unit is still turning or starting. When test mode is selected the ON/OFF
command will only switch the field breaker but not activate the bridge, field flashing or any other
breaker in the excitation system.
Any internal or external trip signal will block only the ON command to the field breaker or trip it when
it is ON. It will not alter the selection of this test mode.
When one of the pre-conditions vanishes during the test (speed, voltage) the FB will be tripped in-
stantly and the test mode will be de-selected. In this case please restore the correct pre-conditions
and re-select this mode.
A de-selection of this mode when FB is still closed will instantly trip the breaker and restore normal
operating conditions.
The regulator card PGS3 contains the gate firing unit. On its front plate there is located a HST switch
to activates this mode. Below the switch is a second ± switch to raise / lower the output at this mode.
Test run
When excitation is switched OFF and supplied separately (no shuntfield connection) – push the HST
switch on the front of PGS card to the upper position "1". The gate pulses will be enabled, an alarm
appears and indicates that the device is not ready for automatic operation.
The mode can also be activated during operation, the actual firing angle will not be changed, i.e. the
change-over is bumpless.
Set the output to the requested value by using the ± button. Pushing upwards will move the firing an-
gle to raise the exciter output voltage, pushing the button downwards moves the firing angle to lower
the output voltage.
The firing angle can be checked on the ELTERM by selecting in main menu 2 Actual Values – move
the cursor down to parameter "V509 Firing Angle".
Measuring jack "U" on the front of card PGS allows the measurement of the adjusted firing angle by a
meter or scope, (0...5V corresponds to 0...180°). Please refer to chapter "Test Jacks"
Variables:
V509 … Firing Angle (alpha)
P200 … minimum firing angle = positive ceiling, default value GR = 0.4444 = 5°
P201 … maximum firing angle = negative ceiling, default value WR = 13.3335 = 150°
I 520 … manual gate control selected => Alarm: "PIM0 man.gate contr"
The setting range 0 … 8 on the display corresponds to rectifier operation (firing angle 0° to 90°) and
the range 8 … 16 corresponds to inverter operation (firing angle 90° to 180°).
Therefore the field voltage starts increasing with a setting of 8 (firing angle 90°).
The relation is:
180
Firing angle Alpha = N * ---------
16
N … value of V509, P200, P201
Caution:
Use this mode only with external (separate) supply.
When using this HST mode with excitation in shunt-field connection the field voltage can hardly be
controlled in open loop mode (exciter output drifts permanently towards one ceiling).
A bumpless de-activation of switch HST is not possible.
De-activate the HST switch at PGS card to its normal operating position after completing the tests.
Variables:
V1955… duration of freewheel operation
possible range 0 … 15,9995 = 0s … 1638s in steps of 50ms (1=102 sec).
default value of V1955 = 0,4 = 41s,
I 507 … (= Error 69) this digital variable starts the decay test for the defined time.
it returns to "0" when time V1955 is over.
After this time the field breaker trips automatically and the excitation switches off (I365)
Test run:
1) Select menu 5 Terminal Mode on the local operation terminal to access all internal variables.
2) Select variable V1955 and re-adjust the duration of the test when 41s is not sufficient.
3) Adjust the generator voltage to the requested value.
4) Start the stator voltage, field voltage and field current measurement.
5) Start the decay test by setting I507 to "1".
When during the test I507 is set to "0" then the excitation stops instantly by opening the field
breaker without endangering the equipment and machine.
Caution:
This software facility serves only for no-load test purposes and must NOT be started when unit is
parallel to the grid.
Please consider: when the test is started with loaded generator the field current will decay to zero and
the unit remains unexcited on the grid !!
Logics:
Routine implemented in Task 5, cycle time = 50ms
For this test the generator will be excited under no load condition up to a certain voltage level. Then
the generator terminals will suddenly be short circuited. From the course of the stator current after
switching the short circuit the sub-transient and transient parameters of the generator can be deter-
mined.
The sudden short circuit test is also used to verify the toughness of the stator winding at failure condi-
tions.
To get correct curves and measuring results the excitation must be operated without any regula-
tion by setting the firing angle to a fixed value in OPEN LOOP mode.
Please refer to the OPEN LOOP TEST in this description.
Use the HST switch on the front plate of PGS card to activate this mode. Use the ± switch to raise /
lower the output and adjust the requested exciter voltage. Watch the firing angle on the ELTERM by
selecting in main menu 2 Actual Values – move the cursor down to parameter "V509 Firing Angle".
Before switching ON the excitation and after activating this mode (HST=>1) please check if the value
of V509 is greater than 8 (means: exciter output = below zero).
If not press down the button until reaching this condition.
At usual generator design please consider that the adjusted pre-voltage before switching on the sud-
den short circuit should not exceed a level of appr. 50% of nominal voltage. Up to this value the
stress remains usually within the normal operating conditions.
Usually the first test will be started at a low level of 10% and repeated on increasing voltage levels of
20, 30 and finally at 50% of nominal stator voltage.
On values above 50% generator voltage the forces during the test on generator stator-, rotor winding
and shaft torque exceeds the normal stress level.
In any case this test must be discussed with and agreed by the generator and turbine manu-
facturer !
Test run:
1) Prepare a temporary separate supply for the excitation.
2) Prepare a temporary short circuit on the generator busbar behind the main CB.
3) Switch ON HST switch on PGS card (pos.1). Check on local operation terminal ELTERM menu
2 Actual Values that V509 is greater than 8 (firing angle above 90°).
4) Speed up the generator to rated speed.
5) Switch ON the excitation (excitation terminal must indicate "Ready") and adjust the generator volt-
age to the requested value by pressing the ± button on PGS upwards.
6) Start the stator voltage/current and field voltage/current measurement.
7) Short circuit the generator terminals by closing the main CB.
8) After test remove all temporary precautions – restore normal conditions. De-activate HST.
For this test the generator will be excited under short circuit condition up to a certain stator current
level. Then the generator terminals will suddenly be opened. From the course of the stator voltage
after switching off the short circuit the transient parameter of the generator can be determined.
To get correct curves and measuring results the excitation must be operated without any regula-
tion by setting the firing angle to a fixed value in OPEN LOOP mode.
Please refer to the OPEN LOOP TEST in this description.
Use the HST switch on the front plate of PGS card to activate this mode. Use the ± switch to raise /
lower the output and adjust the requested exciter voltage. Watch the firing angle on the ELTERM by
selecting in main menu 2 Actual Values – move the cursor down to parameter "V509 Firing Angle".
Before switching ON the excitation and after activating this mode (HST=>1) please check if the value
of V509 is greater than 8 (means: exciter output = below zero).
If not press down the button until reaching this condition.
Test run:
1) Use the preparations for the sudden short circuit test:
a) the temporary separate supply of the excitation and
b) the temporary short circuit on the generator busbar behind the main CB.
2) HST switch on PGS card is ON (pos.1). Check on local operation terminal ELTERM menu
2 Actual Values that V509 is greater than 8 (firing angle above 90°).
3) Generator @ rated speed.
4) Switch ON the excitation (excitation terminal must indicate "Ready")
5) Short circuit the generator terminals by closing the main CB.
6) Adjust the generator current to the requested value by pressing the ± button on PGS.
7) Start the stator voltage/current and field voltage/current measurement.
8) Switch off the short circuit on generator terminals by opening the main CB.
9) After test remove all temporary precautions – restore normal conditions. De-activate HST.
Test run
1) Select menu 5 Terminal Mode on the local operation terminal to access all internal variables.
2) Set variable I503 to "1". The alarm "excit. test mode" and a summary alarm appears instantly. Also
"excitation ready for start" appears.
3) Set variable I508 to "1". Error 70 appears additionally.
4) When I508 becomes "1" a one second ON pulse goes to the short CB.
The pulse only comes when the conditions mentioned above are fulfilled.
When the short CB is not closing due to any missing conditions or interlockings you have to set
the variable I508 to "1" again to create a new ON pulse.
5) Now the excitation can be switched ON and OFF according requirements. It can be switched by
local commands or remotely.
6) De-activation of this mode is only possible when excitation is OFF.
Set I508 back to "0" to switch OFF the short CB and deactivate only this mode and keep the "test
mode" with the brake/test transformer supply.
When I508 becomes "0" a one second OFF pulse goes to the short CB
Setting I503 back to "0" will de-activate both varialbles, (also I508)
Caution
The ON and OFF pulse to the short CB happens only once. When it was not successful you have to
repeat the procedure.
For this reason a software switch is provided to bypass all interlockings, prepare feedback signals,
blocks all digital outputs and also blocks voltage supervisions which probably are not useable under
this test condition.
For details of using SyMaSim please refer to the SyMaSim MANUAL or SyMaSim QUICK GUIDE.
Variables
I 288 … selection variable for "SyMaSim" mode.
I 1318 … CB OFF simulation (signal is forced automatically)
I 1319 … FB OFF simulation (signal is forced automatically)
I 1320 … bridge OFF simulation (signal is forced automatically)
Test run
1) Select menu 5 Terminal Mode on the local operation terminal to access all internal variables.
2) Set variable I288 to "1". The "excitation ready for start" appears.
3) Switch excitation ON and OFF as required by local ON and OFF commands on the terminal (check
that "LOCAL" mode is selected on the terminal).
4) Reset this test mode by setting variable I288 to "0".
Caution:
This software facility serves only for stand still test purposes and must NOT be started when unit is
excited or even parallel to the grid.
TEST JACKS
On the front plate of the PGS card there are 4 test jacks located.
One for ground GND (top right) and one output jack for testing signals of each processor (A, B, C).
Via software it can be selected which signal is represented on the test jacks.
By setting the value of 3 variables – one for each processor – you can select the signal.
The attached list shows the value in decimal format (T) and also the calibration of each signal.
Note: the calibration is not exact, it depends on the input voltage. That means if the input voltage is
e.g. 5,2V then the maximum output voltage is also appr. 5,2V. ?…depends on act.value calibration.
Variables
V544 …selection variable for processor A / jack top left. Default value = 0 => firing angle alpha
V542 …selection variable for processor B / jack bottom left. Default value = 0 => field current
V543 …selection variable for processor C / jack bottom right. Default value = 0 => gen. voltage