053-136 DEEP SEA ELECTRONICS

TYPICAL WIRING DIAGRAM ISSUE 2


DSE335 INSTALLATION INSTRUCTIONS

ACCESSING THE FRONT PANEL EDITOR (FPE)


• Press and hold the the button.
• If a module security PIN has been set, the PIN number request is then shown .
• Press , the first ‘#’ changes to ‘0’. Press (up) or (down) to adjust it to the correct
value.
• Press (right) when the first digit is correctly entered. The digit you have just entered will now
show ‘#’ for security.
• The other digits of the PIN number. You can press (left) if you need to move back to adjust one
of the previous digits.
• When is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is
not correct, you must re-enter the PIN.
• If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is
displayed.

EDITING A PARAMETER
• Press the Press the or buttons to cycle to the section you wish to view/change.
• Press the or buttons to select the next parameter or previous parameter within the current
page.
• When viewing the parameter to be changed, press the button. The value begins to flash.
• When editing the scheduler, press the or button to move between the various parameters of
the scheduler.
• Press the or buttons buttons to adjust the value to the required setting.
• Press the button the save the current value, the value ceases flashing.
• Press and hold the button to exit the editor.

DIMENSIONS AND MOUNTING


For flat surface mounting in a type 1 enclosure and use in a pollution degree 2 environment.

DIMENSIONS PANEL CUTOUT WEIGHT


240 mm x 181 mm x 41 mm 220 mm x 160 mm 680 g
(9.4” x 7.1” x 1.6”) (8.7” x 6.3”) (0.68 kg)

Deep Sea Electronics Plc. Deep Sea Electronics inc.


Tel: +44 (0)1723 890099 Phone: +1 (815) 316-8706
Fax: +44 (0)1723 893303 Fax: +1 (815) 316- 8708
Email: support@deepseaplc.com TOLL FREE (USA only)
Web: www.deepseaplc.com Tel: +1 866 636 9703
Email: support@deepseausa.com
Web: www.deepseausa.com
FRONT PANEL CONFIGURATION EDITOR Page Parameter Values
SCHEDULER Bank 1 Event 4 Duration hh:mm
Page Parameter Values Bank 1 Event 5 Week 1-4
DISPLAY LCD Contrast 0% Bank 1 Event 5 Day Monday to Sunday
Language English Bank 1 Event 5 Start Time hh:mm
LCD Page Timer hh:mm:ss Bank 1 Event 5 Duration hh:mm
Scroll Delay hh:mm:ss Bank 1 Event 6 Week 1-4
Date and Time dd-mm-yyyy, hh:mm:ss Bank 1 Event 6 Day Monday to Sunday
S2 S2 Option Generator, Mains Bank 1 Event 6 Start Time hh:mm
Immediate S2 Dropout Inactive, Active Bank 1 Event 6 Duration hh:mm
Under Voltage Trip (Generator Option) 0V Bank 1 Event 7 Week 1-4
Over Voltage Trip (Generator Option) 0V Bank 1 Event 7 Day Monday to Sunday
Under Frequency Trip (Generator Option) 0.0 Hz Bank 1 Event 7 Start Time hh:mm
Over Frequency Trip (Generator Option) 0.0 Hz Bank 1 Event 7 Duration hh:mm
Under Voltage Trip (Mains Option) 0V Bank 1 Event 8 Week 1-4
Over Voltage Trip (Mains Option) 0V Bank 1 Event 8 Day Monday to Sunday
Under Frequency Trip (Mains Option) 0.0 Hz Bank 1 Event 8 Start Time hh:mm
Over Frequency Trip (Mains Option) 0.0 Hz Bank 1 Event 8 Duration hh:mm
S1 S1 Option Generator, Mains Bank 2 Run Mode Off Load, On Load, Do Not Transfer
Immediate S1 Dropout Inactive, Active Bank 2 Period Weekly, Monthly
Under Voltage Trip 0V Bank 2 Event 1 Week 1-4
Over Voltage Trip 0V Bank 2 Event 1 Day Monday to Sunday
Under Frequency Trip 0 Hz Bank 2 Event 1 Start Time hh:mm
Over Frequency Trip 0 Hz Bank 2 Event 1 Duration hh:mm
TIMERS S1 Transient Delay mm:ss Bank 2 Event 2 Week 1-4
Start Delay hh:mm:ss Bank 2 Event 2 Day Monday to Sunday
Warming Up Time hh:mm:ss Bank 2 Event 2 Start Time hh:mm
S2 Fail Delay mm:ss Bank 2 Event 2 Duration hh:mm
Elevator Delay mm:ss Bank 2 Event 3 Week 1-4
Non-sync Transfer Time mm:ss.s Bank 2 Event 3 Day Monday to Sunday
Check-Sync Transfer time mm:ss.s Bank 2 Event 3 Start Time hh:mm
Return Delay hh:mm:ss Bank 2 Event 3 Duration hh:mm
Cooling Time hh:mm:ss Bank 2 Event 4 Week 1-4
Fail to Stop Enable Inactive, Active Bank 2 Event 4 Day Monday to Sunday
Fail to Stop Delay mm:ss Bank 2 Event 4 Start Time hh:mm
S2 Transient Delay s.s Bank 2 Event 4 Duration hh:mm
SCHEDULER Scheduler Enable Inactive, Active Bank 2 Event 5 Week 1-4
Bank 1 Run Mode Off Load, On Load, Do Not Transfer Bank 2 Event 5 Day Monday to Sunday
Bank 1 Period Weekly, Monthly Bank 2 Event 5 Start Time hh:mm
Bank 1 Event 1 Week 1-4 Bank 2 Event 5 Duration hh:mm
Bank 1 Event 1 Day Monday to Sunday Bank 2 Event 6 Week 1-4
Bank 1 Event 1 Start Time hh:mm Bank 2 Event 6 Day Monday to Sunday
Bank 1 Event 1 Duration hh:mm Bank 2 Event 6 Start Time hh:mm
Bank 1 Event 2 Week 1-4 Bank 2 Event 6 Duration hh:mm
Bank 1 Event 2 Day Monday to Sunday Bank 2 Event 7 Week 1-4
Bank 1 Event 2 Start Time hh:mm Bank 2 Event 7 Day Monday to Sunday
Bank 1 Event 2 Duration hh:mm Bank 2 Event 7 Start Time hh:mm
Bank 1 Event 3 Week 1-4 Bank 2 Event 7 Duration hh:mm
Bank 1 Event 3 Day Monday to Sunday Bank 2 Event 8 Week 1-4
Bank 1 Event 3 Start Time hh:mm Bank 2 Event 8 Day Monday to Sunday
Bank 1 Event 3 Duration hh:mm Bank 2 Event 8 Start Time hh:mm
Bank 1 Event 4 Week 1-4 Bank 2 Event 8 Duration hh:mm
Bank 1 Event 4 Day Monday to Sunday
Bank 1 Event 4 Start Time hh:mm