Professional Documents
Culture Documents
Torre Di Raffreddamento Serie TVA - 11.2016 EN - Rev 01 - 31
Torre Di Raffreddamento Serie TVA - 11.2016 EN - Rev 01 - 31
INSTRUCTION MANUAL
- translation of the original instructions -
SERIAL No.:
DECSA S.r.l.
Via Cappelletta, 1 -27058, Voghera (PV) Italia
2 TECHNICAL DESCRIPTION................................................................................................................... 16
2.1 General information .......................................................................................................................... 16
2.2 Directives and Harmonised Standards ............................................................................................. 17
2.3 Definitions and main theoretical principles ....................................................................................... 18
2.4 General description of DECSA TVA series Cooling Towers ............................................................ 21
2.5 Technical features of TVA Cooling Towers ...................................................................................... 22
2.5.1 Containment casing .......................................................................................................... 24
2.5.2 Water collection basin ....................................................................................................... 27
2.5.3 Fan protection grids .......................................................................................................... 28
2.5.4 Axial fans .......................................................................................................................... 29
2.5.5 Evaporative wet deck fill ................................................................................................... 30
2.5.6 Water distribution system and spraying nozzles .............................................................. 31
2.5.7 Drift eliminators ................................................................................................................. 32
2.6 Operating principle ........................................................................................................................... 33
2.7 Overall dimensions per model .......................................................................................................... 35
2.8 Technical data per model ................................................................................................................. 44
3 SAFETY ................................................................................................................................................... 54
3.1 Introduction ....................................................................................................................................... 54
3.2 Duties of the Safety Officer .............................................................................................................. 55
3.3 Duties of personnel that interact with the Cooling Tower................................................................. 55
3.4 Safety solutions adopted: general remarks ...................................................................................... 56
3.5 Nature of potential hazards .............................................................................................................. 58
3.5.1 Potential shock hazard...................................................................................................... 59
3.5.2 Potential risk deriving from interference with other electric devices ................................. 59
3.5.3 Potential exposure to lightning hazard.............................................................................. 60
3.5.4 Potential risk of crushing and shearing of the upper limbs ............................................... 60
3.5.5 Potential risk of dragging .................................................................................................. 60
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 3 of 138
5 INSTALLATION ....................................................................................................................................... 77
5.1 Localisation: general guidelines ....................................................................................................... 77
5.2 Free air circulation ............................................................................................................................ 79
5.3 Mist formation ................................................................................................................................... 82
5.4 Resting surface ................................................................................................................................ 84
5.5 Unloading from the transportation vehicle........................................................................................ 86
5.6 Assembly of the modules ................................................................................................................. 87
5.6.1 Fixing of the upper module to the lower module ............................................................... 87
5.6.2 Assembling ladders and walkways (optional group) ......................................................... 92
5.6.3 Electric and water connections ......................................................................................... 93
5.7 Sealing leaks .................................................................................................................................... 94
5.8 Water connection ............................................................................................................................. 95
5.9 Electric power supply line ................................................................................................................. 96
5.10 Connecting the motors ..................................................................................................................... 98
Before carrying out any operation on or with the Cooling Tower, all the instructions, procedures and
warnings described in this Instruction Manual must be read and understood.
PRELIMINARY REMARKS
The Cooling Tower of the TVA series is partly completed machinery because it is supplied without an electric
power supply circuit and without electrical control and safety devices.
Therefore, this assembly and maintenance manual does not include the instructions for use (description of
machinery controls); it includes exclusively the directions for a proper installation and use.
The realization of the electrical and water systems in compliance with the standards in force in the country of
installation are to be accomplished by the Purchaser, as well as the connection of the partly completed
machinery itself to the power sources by equipping it with suitable control and safety devices.
The use of the Cooling Tower before its incorporation into the plant of destination and consequent
CE certification is forbidden.
The Purchaser shall also arrange the subsequent drawing up of the documentation to be enclosed in the
present Manual in order to provide the assigned staff with the instructions for a correct use of the Cooling
Tower.
INTRODUCTION
Correct installation and subsequent good operation of the TVA series Cooling Tower will depend on the
scrupulous and sensible observation of the instructions laid out in the present document.
DECSA S.r.l. owns all intellectual property rights in the content of this Manual. Any reproduction thereof, in
whole or in part, is prohibited without the prior written permission of DECSA S.r.l.
DECSA S.r.l. reserves the right to modify, with no prior notice, the characteristics of the Cooling Tower
presented in this document.
Before operating the Cooling Tower, read carefully these instructions and strictly follow
them.
It is mandatory for operators and maintenance personnel to read and understand all the
instructions contained within this Manual.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 7 of 138
In this Manual, the word “Purchaser” refers to the natural or juridical person that has possession of one
Cooling Tower of the series TVA and/or has the power to take decisions with regard to its actual utilization.
The upper part of the page includes the information to identify the Instruction Manual.
Warnings and pieces of information have each been inserted within the most appropriate section and
are not repeated elsewhere. For this reason, the manual must be read first entirely and in sequence,
from beginning to end, and all such information must be understood and kept in mind. Afterwards,
only the required paragraphs can be referred to.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 9 of 138
OBLIGATION
It is MANDATORY to carry out the operations and/or comply with the actions marked by this
symbol.
PROHIBITION
It is PROHIBITED to carry out the operations and/or pursue the actions marked by this
symbol.
DANGER
It indicates an action or behaviour likely to cause damage to property or persons.
INFORMATION
This highlights important information which must be read with the utmost attention.
Hereunder is a list of the graphic symbols used in this manual in order to make reading easier, and
understanding of certain significant parts of the text more immediate. Each symbol (ISO 7000) is identified by
its related image, code number and meaning.
ANNEXES
The following enclosures are integral parts of the manual [ Chapter 11 – ANNEXES]:
Layout
Foundation drawing or Bearing Points drawing
Wiring diagram
Water diagram
Documentation concerning the main trade parts
A detailed list of the documentation supplied with the machinery is enclosed with the
“Consignment Letter”. We recommend to sign the appropriate copy as a receipt of
consignment and to send it as soon as possible to DECSA s.r.l. - Documentation
Department.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 11 of 138
1 GENERAL INFORMATION
1.1 Manufacturer’s details
DECSA S.r.l.
e-mail: info@decsa.eu
The identification code of this Manual is featured on the header of each page: this code is required when
purchasing additional copies of the Manual.
A plate fixed by DECSA S.r.l. to each Cooling Tower of the series TVA features the identification data:
The Purchaser of the Cooling Tower must make sure the plate is never removed from the
Cooling Tower and the featured data are always clearly legible.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 12 of 138
DECSA S.r.l.
e-mail: info@decsa.eu
Any inquiry or request for assistance submitted to the After Sales Service must indicate the
data featured on the Cooling Tower identification plate.
( Section 1.3 - Identification data of Cooling Tower)
The parts subject to normal wear and tear require periodic replacement. Whenever ordering spare parts,
make sure they can be clearly identified by submitting the relevant info, such as: code number featured in
the diagrams, ID data featured on the physical label, any reference code mentioned in this Instruction
Manual, etc.
DECSA S.r.l.
Ufficio Ricambi
e-mail: info@decsa.eu
To maintain the safety conditions expected by the Manufacturer, ORIGINAL spare parts
must be purchased at all times.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 13 of 138
The partly completed machinery named “COOLING TOWER” of the series TVA has been designed and
constructed for performing the following function:
Cooling of water by means of air flow from axial fans, according to the data specifically confirmed in
the Purchase Order by the Buyer and included in Section 2.8 – Technical data per model.
The Manufacturer’s intended use is that defined as “Cooling Tower function”, with the performance,
characteristics, and limitation details listed in Chapter 2 - TECHNICAL DESCRIPTION and according to the
use, adjustment, maintenance and cleaning procedures described in the present Manual.
In detail:
The features regarding the electric and water supplies must remain constant through time.
The performance values for each model of the series TVA (flows, maximum and minimum
temperatures, pressures, etc.) shall be observed.
All the provisions concerning the safety of persons and Cooling Tower must be strictly observed. Always
comply with both the procedures described in this Manual and the safety provisions of the directives and
standards in force in the Country where the machinery is installed.
Should that not be the case, the Purchaser shall be charged with both civil and criminal liability in relation to
any improper use whatsoever.
All uses which are not specifically described herein are to be considered INCORRECT USES.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 14 of 138
Any use of the Cooling Tower not described in this Manual must be regarded as “not intended” by the
Manufacturer. In particular, the requirements of ATEX Directive have not been complied with and for
this reason it is forbidden to operate the machinery in environments where there is the risk of
explosion and/or fire.
In particular, the Cooling Tower must not be used if the guards provided by the Manufacturer are not in
place, or if the safety devices are not installed, not connected, not adjusted, deliberately excluded, or
otherwise inefficient.
All general information concerning safety and accident prevention has been collected in Chapter 3 -
SAFETY. The information refers to the use, installation, cleaning and maintenance of the machinery.
The general safety provisions are not repeated in any of the other chapters; therefore, before carrying out
any operations, make sure you fully understand them.
Please do not hesitate to read them again or contact DECSA After Sales Service if you are in doubt.
1.10 Disclaimer
DECSA S.r.l. declines any liability arising from the misuse or not reasonably foreseeable use of the
Cooling Tower, use of non-genuine spare parts and from any modification or tampering whatsoever
(mechanical, electrical, electronic parts and safety components).
The responsibility for scrupulous application of the safety provisions lies with the Head of the Prevention and
Protection Service(1) (Italy) or a similar professional figure provided by the laws in force in the country where
the Cooling Tower is to be installed. The Head of the Prevention and Protection Service must also make
sure that the personnel entrusted with the use of the Cooling Tower hold the qualifications to carry out the
required task, are knowledgeable about the instructions described in this Manual and about the general
safety provisions applicable to the Cooling Tower of the series TVA.
Failure to observe the safety rules may cause personal injury and may damage components
of your Cooling Tower.
(1) RSPP, in Italian stands for Head of the Prevention and Protection Service; it refers to the health and safety professional (safety
officer) appointed by the Employer to manage and coordinate the prevention and protection service (SPP), which consists in the
people, the systems and the equipment inside or outside the company, all having the purpose of preventing and protecting the
workers against risks in the workplace (art. 2 lett. l of D.Lgs. 81/2008 - Italian law).
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 15 of 138
1.11 Warranty
The warranty is valid for 12 months as from the date of commissioning of the Cooling Tower, and, in any
case, for not over 18 months from date of shipment. The warranty is valid only if the defects will be
communicated to DECSA S.r.l. within 8 days from the date of discovery. The warranty is limited to any
defective parts ex-works of the Supplier and is subject to the acknowledgement of the defect by the Supplier
or an authorized After Sales service centre. Any expenses relating to disassembly, reassembly and shipment
will be charged to the Purchaser. Any defective parts will be replaced and/or repaired by the Supplier, who
will be relieved of any further liability; the Purchaser waives any and all damage or expenses claims, with this
including the expenses arising from impossibility to use the equipment for the time required for the repairing
of the defective parts.
The warranty is not applicable:
to those parts that are subject to normal wear
if the faults are ascribable or mainly ascribable to:
• improper use of the equipment
• modifications or repairs performed by the Buyer
• use of improper lubricants
• equipment overload of work
• incorrect installation of equipment
• other similar cases
The electric motors are not covered by the warranty in case of faults caused by voltage variations, unless the
Purchaser can demonstrate the necessary precautions have been taken in order to avoid this possibility.
The Supplier owns the defective parts that have been replaced.
The warranty is applicable only if the Purchaser has isolated the Cooling Tower as soon as the damage has
been detected.
The warranty and DECSA S.r.l. liability shall lapse in case any modification or tampering whatsoever
is carried out on the Cooling Tower or in the event of misuse.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 16 of 138
2 TECHNICAL DESCRIPTION
2.1 General information
The technical description of the main components of the Cooling Towers of the series TVA has been set out
in this chapter in a deliberately simple form, in order to provide operators and maintenance technicians with
the technical knowledge of those parts they will have to interact with for a proper and safe use and
maintenance.
The documentation provided by the Suppliers of commercial parts has been attached to the present
Instruction Manual: in order to acquire a complete and overall view of the technical aspects of the Cooling
Tower, also said documentation should be referred to and carefully read.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 17 of 138
The Cooling Tower has been designed and built to be incorporated in a plant in which it will be used to cool
process water by means of a current of air blown by axial fans.
The Cooling Towers of the series TVA have been designed and constructed in compliance with the following
directives and harmonised standards:
DIRECTIVES:
2006/42/EC Machinery Directive Annex I – Points:
- 1.1.1; 1.1.2; 1.1.3; 1.1.5
- 1.3.1; 1.3.2; 1.3.3; 1.3.4; 1.3.7; 1.3.8; 1.3.9
- 1.4.1; 1.4.2.1; 1.4.3
- 1.5.1; 1.5.2; 1.5.10; 1.5.13; 1.5.15; 1.5.16
- 1.6.1; 1.6.2; 1.6.4; 1.6.5
- 1.7.1 General part; 1.7.2; 1.7.3; 1.7.4
REFERENCE STANDARDS:
UNI EN ISO 14120: 2015 Safety of machinery - Guards - General requirements for the design and
construction of fixed and movable guards
UNI EN ISO 12100: 2010 Safety of machinery - General principles for design - Risk assessment and
risk reduction
UNI EN ISO 13850: 2015 Safety of machinery - Emergency stop function - Principles for design
UNI EN ISO 13857: 2008 Safety of machinery - Safety distances to prevent hazard zones being
reached by upper and lower limbs
The main theoretical principles of the plan and some definitions mentioned in the Instruction
Manual are included in this section in order to make understanding of the text more
immediate.
WET-BULB TEMPERATURE
The wet-bulb temperature is the temperature of water under equilibrium conditions of convective exchange
with air in turbulent flow fully developed.
Absolute humidity is determined by both wet-bulb temperature and dry-bulb temperature.
ABSOLUTE HUMIDITY
Absolute humidity “X” can be calculated by dividing the mass of vapour by the mass of dry air in a mixture of
dry air and water vapour. Specifically, it indicates the mass (kg) of water vapour present in 1 kg of dry air
under a given condition of temperature and relative humidity.
RELATIVE HUMIDITY
Relative humidity “UR” is used for measuring the humidity present in the air. It is defined as the ratio of the
partial pressure of the water vapour in the gaseous mixture of air and water vapour to the saturated vapour
pressure, (expressed as a percentage). A relative humidity of 100% indicates that the gaseous mixture
contains the maximum quantity of possible humidity for the given temperature and pressure conditions.
Relative humidity can also be defined as “the quantity of water vapour present in the air in proportion to the
saturation point”.
The vapour quantity that can be contained by an air mass decreases when the temperature decreases: it
becomes nil at -40 °C (= 233.15 K).
COOLING TOWER
A Cooling Tower is a gas-liquid heat exchanger in which thermal energy is released from the liquid phase to
the gaseous phase, thereby reducing the temperature of the liquid. In most cases, the gaseous phase is
made up of air or water vapour and the liquid phase of water of various types. Heat exchange can be
obtained by means of:
contact between the phases ⇒ Cooling Tower
surface in a tube heat exchanger, plate heat exchanger or other ⇒ Cooling Coil.
The most used type is the counterflow Cooling Tower (forced draft or induced draft), which ensures greater
efficiency.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 20 of 138
The Cooling Tower has a greater efficiency compared to a traditional radiator as the direct thermal exchange
causes water evaporation and makes it possible to use the latent heat of evaporation.
The reference parameter is not the ambient temperature, but the wet-bulb ambient temperature, i.e. the
temperature that can be determined from the ambient temperature and the relative humidity thanks to a
psychrometric chart.
The wet-bulb temperature is usually about 4÷6 °C (or more) lower than the ambient temperature: a Cooling
Tower allows cooling water at a lower temperature than the ambient temperature.
The use of the latent heat of evaporation greatly increases the efficiency, on the average, for every kg of
water that evaporates there is a thermal loss of 600 kcal/h (average value). From the analysis of this
process, it can obviously be assumed that a Cooling Tower consumes water: its circuit is therefore an “open
circuit” as there is a constant consumption of water, connected to the dissipated thermal power.
INTAKE AIR
It is the mass of air suctioned by the fans and then conveyed into the Cooling Tower.
EXHAUST AIR
Exhaust air is the mass of air which, after having been in contact with the water to be cooled, by absorbing
part of its thermal energy and collecting part of the evaporated water, is rejected into the environment.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 21 of 138
Among the most interesting solutions adopted for TVA series Cooling Towers are the following:
SPACE OPTIMISATION
The maximum depth of the majority of the TVA series Cooling Towers, as it is ≤ 2.30 m, excludes the
necessity to employ exceptional vehicles for transportation of oversized items, as it is within the maximum
dimensions for transportation with ordinary vehicles. These models may be transported already assembled,
using ordinary and not low-floor trucks. On the other hand, some models presenting higher depth than the
ordinary dimensions (maximum depth = 2.98 m), require transportation with special vehicles, with no need to
be escorted. To carry out transportation it is necessary to reduce the Cooling Tower height, therefore it is
divided into two modules: the “basin section” alone makes up the lower module, the “fan section” and
“exchange section” make up the upper module.
Also for sea shipment transportation the dimensions of the TVA series Cooling Towers do not create any
particular problems: the majority of models may be included into an ordinary container, whereas the models
presenting larger dimensions are divided into various modules, thus eliminating any transportation problems.
PROJECT OBJECTIVES
Besides designing and accomplishing a Cooling Tower of optimum performance, other important objectives
of the present project were also achieved:
the equipment presents easy maintenance characteristics
specific functional features have been adopted (for example: inspection openings)
protection of metal parts from internal and external corrosive agents
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 22 of 138
The main components of all the TVA series Cooling Towers are shown in the images reproduced in this and
the following pages:
1. Containment casing
2. Motor for fan rotation
3. Axial fan
4. Water collection basin
5. Air suction from the external environment
The main components remain the same for all the Cooling Tower models, whereas the number of fans varies (from “1” to “3”)
according to the model purchased ( section “2.8 – Technical data per model”).
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 23 of 138
The external containment casing is a self-supporting fibreglass monocoque structure, but the models
presenting larger dimensions have an internal supporting structure made of galvanized steel with external
fibreglass panels. All the panels have reinforced edges to make the unit sturdier and are assembled with
bolts. Tightness between panels is ensured by an adequate sealant which maintains its permanent elasticity.
1. Galvanized bolts
2. Panel reinforcing edges
To prevent problems deriving from the water circulating within the Cooling Tower, a stainless steel internal
supporting structure can be required.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 25 of 138
In the image that follows a sectional view is provided of the superficial internal and external treatments:
1 External surface
2 Internal surface
The various models of Cooling Towers covered by this manual are not given the DECSAPROT protective
treatment unless specifically agreed in the supply contract.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 26 of 138
When observing the right and the rear side of the Cooling Tower, the headers for connection to the water
lines and the hole for insertion of the electric immersion heater can be seen, the function of which is to
ensure that the temperature of the cooled-down water does not fall below the freezing value.
F 2.4 – Right side (with respect to the operator side) – Sample image
1. Bottom drain
2. Overflow
3. Water make-up
(maximum pressure 2 bar)
4. Cooled water outlet
5. Inlet of water to be cooled
The image above illustrates an example of flanges already assembled and ready to be connected to the
pipes.
Further information:
Please refer to the specific drawing (enclosed) relevant to the TVA series Cooling Tower.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 27 of 138
The water collection basin at the bottom of the module consists of fibreglass panels, assembled with
galvanized bolts. Between the panels there is a strip of butyl rubber; subsequently the joints are sealed with
appropriate silicone. The basin is complete with connections for make-up water intake, for the overflow and
the drain. There is a by-pass between the supply pipe to the water distribution system and the overflow, to
enable continuous draining of part of the water for cooling down the Towers, thus ensuring control of salt
concentration in the circuit.
In the following image the “basin section” is pointed out with a red arrow.
When installing the Cooling Tower, it is possible to apply a manual valve onto the drain, which enables
complete drainage of the water present in the basin, making it possible to carry out maintenance and
cleaning operations, as well as shutdown of the system at certain periods of the year.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 28 of 138
The area for air discharge into the environment is protected by grids which prevent accidental contact with
the axial fans.
These grids are considered “fixed guards” [definition taken from the Machinery Directive 2006/42/EC:
section 3.4] and are therefore kept in place by mechanical fastening devices (screws) and are not fitted with
a safety micro-switch: they must never be removed when the Cooling Tower is in operation.
The number of protection grids varies according to the number of fans installed on each model of Cooling
Tower ( Section 2.8 - Technical data per model).
1. Protection grids
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 29 of 138
For air circulation appropriate axial fans are used (in variable number according to the Cooling Tower
model), each one equipped with its own drive motor.
1. Axial fan
2. Motor
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 30 of 138
The evaporative wet deck fill consists of a PVC honeycomb structure composed of modules mounted on a
metal supporting frame. The honeycomb structure with vertical grooves ensures a low pressure drop in the
air flow and eliminates the possibility of stagnant water. The wet deck fill is suitable to temperatures below 60
°C, resistant to decomposition from biological or fungal attack, and is self-extinguishing.
The cooling water is conveyed inside the Tower by a distribution system consisting of polypropylene pipes
and of nozzles made with a special rubber compound (EPDM). These nozzles do not require any gasket and
may be removed and re-applied without the use of any tool, thus making it easy to carry out any required
maintenance interventions. Thanks to the dimension of the water outlet hole, the nozzles cannot become
obstructed.
Water pressure onto the nozzles Section 2.8- Technical data per model
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 32 of 138
The drift eliminators consist of thermoformed and appropriately assembled PVC layers, to form a honeycomb
structure, the function of which is to prevent the air flow inside the Cooling Tower from dragging water drops
towards the exterior. The drift eliminators are assembled between the water distribution system and the fans.
The geometry of the channels ensures low pressure drops.
The Cooling Towers for air-conditioning are normally chosen according to the standard water temperature:
conventionally a tower water inlet temperature of 35 °C and an outlet temperature of 30 °C are assumed.
The temperature differential is thus 5 °C. In any case, the minimum water outlet temperature will never be
less than the wet-bulb temperature of the outside air plus 2÷3 °C. The tower is chosen in reference to the
thermal power to be dissipated and the external design wet-bulb temperature. In this regard, it is, however,
necessary to also consider possible brief increases in temperature that may occur in the summer, in the
period of maximum cooling demand. To prevent a risk of overload of the refrigeration groups, the choice of a
Cooling Tower is usually made for a wet-bulb temperature of approximately 2 °C higher than the designed
one, relative to the place of installation. This feature, besides preventing overload conditions, enables
reduced consumption of energy in the refrigeration group.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 34 of 138
The diagram shows the functional areas of the Cooling Tower, with a brief description of their function.
1. Inlet of cold air into the Cooling Tower, suctioned from the external environment.
2. Wet deck fill: area in which thermal exchange between hot water and cold air + sprayed cold water takes
place.
3. Drift eliminators: small water drops transported by the mass of hot air are recovered and made to fall back
into the Cooling Tower.
4. Axial fans and release of hot air and water vapour into the environment.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 35 of 138
In the tables that follow, the overall approximate dimensions of the TVA series Cooling Towers are featured.
In detail, for each model the following data are listed:
- Model
- Height of evaporative wet deck fill
- Overall dimensions (depth “A”, width “B” and total height “H”)
Overall dimensions
Overall dimensions
Overall dimensions
Overall dimensions
Overall dimensions
Overall dimensions
Overall dimensions
Overall dimensions
Overall dimensions
2.8
Model
10-10 10-12 10-15 10-19 10-21 10-26 10-31 10-36 10-42 10-46 11-62S 11-78
80 °C with PP wet deck fill
55 °C with PVC wet deck fill
Maximum height mm 2440 2440 2440 2650 2650 2650 2900 2900 2900 2900 4000 4000
Total weight during operation kg 420 430 450 700 710 730 1120 1140 1170 1190 3540 3570
“Cooling Tower”
Air flow rate m3/s 2.80 2.72 2.72 5.15 4.84 4.84 8.22 9.36 9.36 8.79 15.87 16.92
CHARACTERISTICS
TVA Series
FUNCTIONAL
Water pressure on the nozzles bar (kPa) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50)
Motor and pump nominal 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3
V
voltage phases phases phases phases phases phases phases phases phases phases phases phases
Nominal voltage of services V 220 220 220 220 220 220 220 220 220 220 220 220
Page:
Revision:
Version:
Printed on:
Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
ELECTRICAL DIMENSIONS
Power of each motor No. x kW 1.1 1.1 1.5 2.2 2.2 3 2.2 3 4 4 5.5 5.5
MS 11 16 TVA/E
Power of electric heater (min.
kW 1x1.5 1x1.5 1x1.5 1x1.5 1x1.5 1x1.5 1x2 1x2 1x2 1x2 1x4 1x4
temperature: -20 °C)
44 of 138
Electrical insulation of the
Class F F F F F F F F F F F F
motors
01
Protection degree IP 55 55 55 55 55 55 55 55 55 55 55 55
(5) The maximum temperature of the exchange surface varies according to the material of the evaporative wet deck fill:
(4) The weights of the single modules of the Cooling Tower are featured on plates fixed on the modules.
Model
11-90 11-96 11-94S 11-126 11-138 11-152 14-86S 14-104S 14-116 14-124S 14-124 14-134S
80 °C with PP wet deck fill
55 °C with PVC wet deck fill
Maximum depth mm 2170 2170 2170 2170 2170 2170 2470 2470 2470 2470 2470 2470
Maximum height mm 4000 4000 4000 4000 4000 4000 4850 4850 4250 4850 4250 4850
Weight of the heavier section Kg 1270 1280 1920 1940 1990 2020 1630 1650 1700 1760 1710 1810
Total weight during operation Kg 3600 3610 6380 6400 6450 6480 5350 5370 5420 5500 5450 5550
“Cooling Tower”
Air flow rate m3/s 19.05 18.00 24.61 26.69 29.87 28.58 22.45 22.45 24.50 24.50 24.50 25.17
CHARACTERISTICS
TVA Series
FUNCTIONAL
Water pressure on the nozzles bar (kPa) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50)
Motor and pump nominal 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3
V
voltage phases phases phases phases phases phases phases phases phases phases phases phases
Nominal voltage of services V 220 220 220 220 220 220 220 220 220 220 220 220
Page:
Revision:
Version:
Printed on:
Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
ELECTRICAL DIMENSIONS
MS 11 16 TVA/E
Power of electric heater (min.
kW 1x4 1x4 1x5 1x5 1x5 1x5 1x5 1x5 1x5 1x5 1x5 1x5
temperature: -20 °C)
45 of 138
Electrical insulation of the
Class F F F F F F F F F F F F
motors
01
Protection degree IP 55 55 55 55 55 55 55 55 55 55 55 55
(7) The maximum temperature of the exchange surface varies according to the material of the evaporative wet deck fill:
(6) The weights of the single modules of the Cooling Tower are featured on plates fixed on the modules.
Model
14-134 14-105S 14-112 14-144 14-149 14-161S 14-171 14-171S 14-183 19-127S 19-142 19-180
80 °C with PP wet deck fill
55 °C with PVC wet deck fill
Maximum depth mm 2470 2470 2470 2470 2470 2470 2470 2470 2470 2970 2970 2970
Maximum height mm 4250 4850 4850 4850 4250 4850 4250 4850 4850 4850 4850 4850
Weight of the heavier section kg 1770 2120 2140 2190 2250 2350 2390 2480 2520 2250 2670 2770
Total weight during operation kg 5520 6955 6985 7955 7080 7180 7220 7310 7350 8350 8470 8570
“Cooling Tower”
Air flow rate m3/s 25.17 27.22 31.79 30.91 31.79 31.79 31.79 31.79 34.42 32.96 37.28 38.36
CHARACTERISTICS
TVA Series
FUNCTIONAL
Water pressure on the nozzles bar (kPa) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50)
Motor and pump nominal 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3
V
voltage phases phases phases phases phases phases phases phases phases phases phases phases
Nominal voltage of services V 220 220 220 220 220 220 220 220 220 220 220 220
Page:
Revision:
Version:
Printed on:
Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
ELECTRICAL DIMENSIONS
MS 11 16 TVA/E
Power of electric heater (min.
kW 1x5 1x6 1x6 1x6 1x6 1x6 1x7 1x7 1x6 1x6 1x6 1x7
temperature: -20 °C)
46 of 138
Electrical insulation of the
Class F F F F F F F F F F F F
motors
01
Protection degree IP 55 55 55 55 55 55 55 55 55 55 55 55
(9) The maximum temperature of the exchange surface varies according to the material of the evaporative wet deck fill:
(8) The weights of the single modules of the Cooling Tower are featured on plates fixed on the modules.
Model
19-202 19-216 19-179S 19-233 19-253 19-281 19-196S 19-207 19-271 19-292 19-304 21-123S/CT
80 °C with PP wet deck fill
55 °C with PVC wet deck fill
Maximum depth mm 2970 2970 2970 2970 2970 2970 2970 2970 2970 2970 2970 2170
Maximum height mm 4850 4850 4850 4850 4850 4850 4850 4850 4850 4850 4850 4000
Weight of the heavier section kg 2970 3070 3350 3650 3800 3900 3850 4200 4350 4450 4550 2600
Total weight during operation kg 8770 8870 10850 11050 11200 11300 12500 12850 13000 13100 13200 7660
“Cooling Tower”
FUNCTIONAL CHARACTERISTICS
Air flow rate m3/s 39.46 40.54 46.79 49.70 49.70 52.62 51.04 54.25 57.46 57.46 56.73 31.74
TVA Series
Water pressure on the nozzles bar (kPa) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50)
Motor and pump nominal 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3
V
voltage phases phases phases phases phases phases phases phases phases phases phases phases
Page:
Revision:
Version:
Printed on:
Nominal voltage of services V 220 220 220 220 220 220 220 220 220 220 220 220
Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
ELECTRICAL DIMENSIONS
MS 11 16 TVA/E
Power of electric heater (min.
No. x kW 1x7 1x7 2x5 2x5 2x5 2x5 2x6 2x6 2x6 2x6 2x6 2x4
temperature: -20 °C)
47 of 138
Electrical insulation of the
Class F F F F F F F F F F F F
motors
01
Protection degree IP 55 55 55 55 55 55 55 55 55 55 55 55
(11) The maximum temperature of the exchange surface varies according to the material of the evaporative wet deck fill:
(10) The weights of the single modules of the Cooling Tower are featured on plates fixed on the modules.
Model
21-157/CT 21-180/CT 21-193/CT 21-189S/CT 21-253/CT 21-277/CT 21-305/CT 24-210S 24-231 24-248S 24-248 24-268S
80 °C with PP wet deck fill
55 °C with PVC wet deck fill
Maximum depth mm 2170 2170 2170 2170 2170 2170 2170 2470 2470 2470 2470 2470
Maximum height mm 4000 4000 4000 4000 4000 4000 4000 4850 4250 4850 4250 4850
Weight of the heavier section kg 2620 2640 2660 3800 3840 3940 3320 3280 3380 3500 3400 3600
Total weight during operation kg 7680 7700 7720 10200 10300 10530 10550 10700 10820 10940 10840 11040
“Cooling Tower”
FUNCTIONAL CHARACTERISTICS
Air flow rate m3/s 33.84 38.10 36.00 49.22 53.38 59.74 57.16 44.90 49.00 49.00 49.00 50.34
TVA Series
Water pressure on the nozzles bar (kPa) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50)
Motor and pump nominal 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3
V
voltage phases phases phases phases phases phases phases phases phases phases phases phases
Page:
Revision:
Version:
Printed on:
Nominal voltage of services V 220 220 220 220 220 220 220 220 220 220 220 220
Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
ELECTRICAL DIMENSIONS
MS 11 16 TVA/E
Power of electric heater (min.
No. x kW 2x4 2x4 2x4 2x5 2x5 2x5 2x5 1x45 2x5 2x5 2x5 2x5
temperature: -20 °C)
48 of 138
Electrical insulation of the
Class F F F F F F F F F F F F
motors
01
Protection degree IP 55 55 55 55 55 55 55 55 55 55 55 55
(13) The maximum temperature of the exchange surface varies according to the material of the evaporative wet deck fill:
(12) The weights of the single modules of the Cooling Tower are featured on plates fixed on the modules.
Model
24-268 24-241 24-289 24-299 24-323 24-340 24-340S 24-367 29-361 29-400 29-433 29-359S
80 °C with PP wet deck fill
55 °C with PVC wet deck fill
Maximum depth mm 2470 2470 2470 2470 2470 2470 2470 2470 2970 2970 2970 2970
Maximum height mm 4250 4850 4850 4250 4850 4250 4850 4850 4850 4850 4850 4850
Weight of the heavier section kg 3520 4220 4360 4320 4520 4600 4780 4860 5480 5630 6030 6600
Total weight during operation kg 10880 13910 14050 14010 14210 14290 14470 14550 17100 17250 17650 21600
“Cooling Tower”
FUNCTIONAL CHARACTERISTICS
Air flow rate m3/s 50.34 63.58 61.82 63.58 63.58 63.58 63.58 68.84 76.72 78.92 81.08 93.58
TVA Series
Water pressure on the nozzles bar (kPa) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50)
Motor and pump nominal 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3
V
voltage phases phases phases phases phases phases phases phases phases phases phases phases
Page:
Revision:
Version:
Printed on:
Nominal voltage of services V 220 220 220 220 220 220 220 220 220 220 220 220
Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
ELECTRICAL DIMENSIONS
MS 11 16 TVA/E
Power of electric heater (min.
No. x kW 2x5 2x4 2x6 2x6 2x6 2x6 2x6 2x6 2x7 2x7 2x7 4x5
temperature: -20 °C)
49 of 138
Electrical insulation of the
Class F F F F F F F F F F F F
motors
01
Protection degree IP 55 55 55 55 55 55 55 55 55 55 55 55
(15) The maximum temperature of the exchange surface varies according to the material of the evaporative wet deck fill:
(14) The weights of the single modules of the Cooling Tower are featured on plates fixed on the modules.
Model
29-466 29-506 29-563 29-415S 29-585 29-608 31-380/CT 31-415/CT 31-458/CT 34-434 34-449 34-484
80 °C with PP wet deck fill
55 °C with PVC wet deck fill
Maximum depth mm 2970 2970 2970 2970 2970 2970 2170 2170 2170 2470 2470 2470
Maximum height mm 4850 4850 4850 4850 4850 4850 4000 4000 4000 4850 4850 4250
Weight of the heavier section kg 7200 7500 7700 8300 8600 9000 4680 4830 4930 6470 6410 6710
Total weight during operation kg 22000 22300 22500 25600 25900 26300 19100 19160 19260 23765 23700 24000
“Cooling Tower”
FUNCTIONAL CHARACTERISTICS
Air flow rate m3/s 99.40 99.40 105.24 114.92 114.92 113.46 80.07 89.61 85.74 95.37 92.73 95.37
TVA Series
Water pressure on the nozzles bar (kPa) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50)
Motor and pump nominal 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3
V
voltage phases phases phases phases phases phases phases phases phases phases phases phases
Page:
Revision:
Version:
Printed on:
Nominal voltage of services V 220 220 220 220 220 220 220 220 220 220 220 220
Frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
ELECTRICAL DIMENSIONS
MS 11 16 TVA/E
Power of electric heater (min.
No. x kW 4x5 4x5 4x5 4x6 4x6 4x6 3x5 3x5 3x5 3x6 3x6 3x6
temperature: -20 °C)
50 of 138
Electrical insulation of the
Class F F F F F F F F F F F F
motors
01
Protection degree IP 55 55 55 55 55 55 55 55 55 55 55 55
(17) The maximum temperature of the exchange surface varies according to the material of the evaporative wet deck fill:
(16) The weights of the single modules of the Cooling Tower are featured on plates fixed on the modules.
Model
34-510 34-510S 34-551 39-649 39-549S 39-699 39-759 39-844
80 °C with PP wet deck fill
55 °C with PVC wet deck fill
Maximum depth mm 2470 2470 2470 2970 2970 2970 2970 2970
Maximum height mm 4850 4250 4850 4850 4850 4850 4850 4850
Weight of the heavier section kg 6830 6900 7020 9100 9900 10800 11350 11650
Total weight during operation kg 25200 25900 27100 26500 27300 28200 28750 29050
“Cooling Tower”
FUNCTIONAL CHARACTERISTICS
Air flow rate m3/s 95.37 95.37 95.37 121.62 140.37 149.10 149.10 157.86
TVA Series
Water pressure on the nozzles bar (kPa) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50) 0.5 (50)
Motor and pump nominal 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3 400 / 3
V
voltage phases phases phases phases phases phases phases phases
Page:
Revision:
Version:
Printed on:
Nominal voltage of services V 220 220 220 220 220 220 220 220
Frequency Hz 50 50 50 50 50 50 50 50
ELECTRICAL DIMENSIONS
MS 11 16 TVA/E
Power of electric heater (min.
No. x kW 3x6 3x6 3x6 3x7 6x5 6x5 6x5 6x5
temperature: -20 °C)
51 of 138
Electrical insulation of the
Class F F F F F F F F
motors
01
Protection degree IP 55 55 55 55 55 55 55 55
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 52 of 138
Materials
Containment casing Galvanized steel plate Z725
Colour code for external varnish (upon request) RAL 5014 (may vary)
Noise
Sound pressure level Lp measured at the standard speed 5m 76 dB(A)
Sound pressure level Lp measured at reduced speed
5m 64 dB(A)
(half air flow rate)
Vibration
Vibrations detected at the operator's There are neither operator's workplaces on the machine nor
workplace activities foreseen for the operator/maintenance technician to be
performed on the machine during normal operation. Evaluation
and measurement of the vibrations transmitted from the Cooling
Vibrations on the machine Tower to the staff assigned are therefore not needed.
( Section 3.9 - Operator's workplace)
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 53 of 138
Total hardness (CaCO3) 50÷650 mg/l 50÷800 mg/l 50÷800 mg/l 50÷800 mg/l 50÷800 mg/l 50÷800 mg/l
Total alkalinity (CaCO3) < 550 mg/l < 650 mg/l < 650 mg/l < 650 mg/l < 650 mg/l < 650 mg/l
Chlorides < 250 mg/l < 300 mg/l < 300 mg/l < 300 mg/l < 350 mg/l < 350 mg/l
Sulphates < 250 mg/l < 350 mg/l < 350 mg/l < 350 mg/l < 350 mg/l < 350 mg/l
Conductivity < 2400µS/cm < 3000µS/cm < 3300µS/cm < 3300µS/cm < 3300µS/cm < 3300µS/cm
Free chlorine
< 1.2 mg/l < 1.2 mg/l < 1.2 mg/l < 1.8 mg/l < 1.8 mg/l < 1.8 mg/l
(continuous chlorination)
Free chlorine 5÷15 mg/l 5÷15 mg/l 5÷15 mg/l 5÷15 mg/l 5÷15 mg/l 5÷15 mg/l
(discontinuous chlorination) max 6 hours max 6 hours max 6 hours max 6 hours max 6 hours max 6 hours
To make it easy to read and interpret data relevant to the water treated, it is reminded that water hardness is
usually expressed in French degrees (°f): one degree represents 10 mg of calcium carbonate (CaCO3) per
litre of water (1 °f = 10 mg/l = 10 ppm - parts per million). Usually, water is classified based on its hardness:
Water quality check is a fundamental activity to optimise performance of Cooling Tower: the
formation of deposits and encrustations reduces heat exchange. It is advised to refer to a
specialised firm in water treatment, to obtain more specific technical instructions.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 54 of 138
3 SAFETY
3.1 Introduction
it is reminded to all staff that heedless behaviour, overconfidence with the operational and maintenance
procedures, failing to observe safety regulations, as well as inexperience may be the cause of damages and
accidents to people and objects, some of them of serious entity.
Therefore, operators and maintenance people are requested to interact with the Cooling Tower in the
following manner:
only after having carefully read and understood the contents of the whole “Instruction Manual” and of
the enclosed documentation,
with the awareness that individual attention is fundamental for personal protection and safety of the
Cooling Tower: no safety system or code of practice can guarantee absolute safety if interaction with
the Cooling Tower is not carried out in a professional, heedful and scrupulous manner.
DECSA S.r.l. will not accept liability for any reason in the case of accidents or damages to
people or objects, deriving from failing to observe:
• the provisions laid out in the Instruction Manual,
• the behavioural rules for the use of the Cooling Tower, laid out by DECSA,
• the behavioural rules for the use of the Cooling Tower provided by the RSPP(18) (Italy)
or by a similar professional figure whose role is provided for by the regulations in force
in the Country of installation of the Cooling Tower,
• the safety regulations in force,
• the indications and instructions by the suppliers of commercial components for the
manufacturing of the Cooling Tower.
(18) RSPP, in Italian stands for Head of the Prevention and Protection Service; it refers to the health and safety professional (safety
officer) appointed by the Employer to manage and coordinate the prevention and protection service (SPP), which consists in the
people, the systems and the equipment inside or outside the company, all having the purpose of preventing and protecting the
workers against risks in the workplace (art. 2 lett. l of D.Lgs. 81/2008 - Italian law).
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 55 of 138
The main obligations for the person responsible for safety are as follows:
The definitions of danger zone and exposed person are laid down in Annex 1 of Machinery Directive
2006/42/EC, Chapter 1: “Essential health and safety requirements”, section 1.1.1: “Definitions”. These
definitions are quoted here below:
«Danger zone», any zone within and/or around machinery in which an exposed person is subject to a risk to
his health or safety;
«Exposed person», any person wholly or partially in a danger zone.
Operator has the obligation to immediately notify his supervisor of any anomalous
condition detected on the Cooling Tower, making it possible to take timely
action before the anomaly turns into a hazard.
Maintenance operator must keep the Cooling Tower under adequate preventive maintenance, entrust
any repair interventions to qualified personnel and always use original spare
parts.
The provisions laid out in the Instruction Manual and in the enclosed
documentation with regard to the competence required to carry out
maintenance activities must be observed.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 56 of 138
DECSA S.r.l. has carefully evaluated, during the designing phase, all possible hazards; it has therefore
accomplished all TVA series Cooling Towers in such a way as to safeguard the operators’ health and safety,
but while ensuring a valid response to functionality needs and high performance.
To this end, the logic developed by DECSA S.r.l., for a safe interaction between Cooling Tower, personnel
and work environment, is summarised in the following diagram:
Machinery guarding:
+ =
mechanical, Codes of practice for Staff and Cooling
electrical, functional, staff members Tower safety
etc.
Two types of machinery guarding have been used on this machinery, “fixed” and “interlocking movable”, and
hereunder is the relevant definition taken from Machinery Directive 2006/42/EC \ Annex 1 \ Chapter 1:
“Essential health and safety requirements”, section 1.4.2: “Special requirements for guards”.
[…]
1.4.2.1 Fixed guards
Fixed guards must be fixed by systems that can be opened or removed only with tools.
Their fixing systems must remain attached to the guards or to the machinery when the guards are
removed.
Where possible, guards must be incapable of remaining in place without their fixings.
Where it is possible for an operator to reach the danger zone before the risk due to the hazardous
machinery functions has ceased, movable guards must be associated with a guard locking device
in addition to an interlocking device that:
- prevents the start of hazardous machinery functions until the guard is closed and locked,
and
- keeps the guard closed and locked until the risk of injury from the hazardous machinery
functions has ceased.
Interlocking movable guards must be designed in such a way that the absence or failure of one of
their components prevents starting or stops the hazardous machinery functions.
[…]
It is absolutely forbidden to remove, tamper with or deactivate in any way the safety guards
and devices, if not just for the time strictly needed to carry out special maintenance/repair
operations, following the safety procedures required for the intervention being carried out.
All guards and safety devices must be kept in perfect working order, to ensure such
operating efficiency as provided by DECSA S.r.l. It is mandatory to regularly check the
presence and adjustment of the fixed guards, the operation and efficiency of all safety
systems, the devices and services (emergency buttons, micro-switches, filters, etc.). In the
case of any damage, they must be immediately repaired or replaced.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 58 of 138
The Cooling Towers present potential hazards of different natures, which, even though they have been
removed during the designing and manufacturing phases, are stated in the present Instruction Manual. The
aim is to provide information to personnel in charge of the operation and maintenance, in order to fully
understand the Cooling Tower characteristics and the potential sources of hazard which may occur in the
event that, for unforeseeable reasons, one or more solutions adopted should prove ineffective.
For each one of the risks indicated above, CAUSES and SUGGESTED SOLUTIONS IMPLEMENTED BY
THE MANUFACTURER are laid out in the following paragraphs.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 59 of 138
All the constituent parts of the Cooling Tower must be connected to a grounding
system.
3.5.2 Potential risk deriving from interference with other electric devices
3.5.8 Potential risk of falling from heights, for the maintenance operator
Residual risks are defined as all potential risks associated with a machine which cannot be removed either
during the designing or the manufacturing phases because:
a) they depend on the nature of the machine itself
b) their removal would prevent the correct operation of the machine
Therefore, the only way to protect people and objects from potential damages derived from residual risks is
by following the behavioural rules laid out:
in the Instruction Manual
by the Head of the Prevention and Protection Service
by the regulations in force regarding safety in the working place
Furthermore, all personnel interacting with the Cooling Tower are reminded that attention as well as
responsible and professional behaviour are essential elements in carrying out any task involving interface
with machines, regardless of the instructions provided by the Manufacturer and of the regulations in force.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 63 of 138
Further information:
DATASHEET OF THE USED
PRODUCT
Normal access to the Cooling Tower is arranged only on the ground level, from all sides surrounding the
Cooling Tower. Any adjustment/maintenance operations needed for the upper part of the Cooling Tower
must be carried out by using suitable equipment complying with the safety regulations, which enable
reaching all components installed on the top of the Cooling Tower in complete safety. Upon request, the
Cooling Towers can be equipped with optional access structures to the upper part: a ladder with fall-
prevention caging allows access to a walkway fitted with fall-prevention guardrails fastened to the Cooling
Tower, on the side with inspection window.
- Access to the walkway (if present) must be allowed only to authorised maintenance
operators and with the Cooling Tower not in operation.
- The maximum admitted load on the walkway is 200 kg, corresponding to the presence of
two maintenance operators equipped with small working tools. The presence of more
than two people at the same time on the walkway is not allowed, nor of other loads
whose overall weight exceeds the one specified (200 kg). It is forbidden to climb to the
roof of the Cooling Tower: its horizontal surfaces are not made to be walked on.
The TVA Series Cooling Towers are equipped with specific openings for internal inspection;
these openings are closed by means of fixed guards, which must always be in place during
ordinary operation of the Cooling Towers. Opening these fixed guards can only be done
after having stopped the Cooling Tower and disconnected it from the electric power supply
(electric power supply cut off). The main switch I/O must be padlocked.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 66 of 138
As this is partly completed machinery to be incorporated into a plant operating outdoors, the Manufacturer
considers ordinary daytime environment illumination as more than sufficient to be able to use the Cooling
Tower in safety conditions, and therefore it does not require any illumination system.
In the case the Purchaser considers it appropriate to install a lighting system for the illumination of the
installation area, he should refer to a qualified technician to design and accomplish such a system according
to the laws in force in the Country where the Cooling Tower is installed.
The Manufacturer, DECSA S.r.l., will not accept any liability for damages to people and/or objects deriving
from the lighting system not correctly designed and installed.
The Cooling Towers produced by DECSA S.r.l. do not require the constant presence of any staff during their
ordinary operation, and therefore no specific working stations are arranged for. The presence of an operator
is necessary only during the start-up of the system, and in the area arranged for installation of the Electric
Panel and the machine Control Panel (to be done by the End User).
No other work station around or on the Cooling Tower (on the walkway where supplied) must be occupied by
the operator during ordinary plant operation (incorporation into a manned plant is not foreseen).
Access to the Cooling Tower and/or stationing on the walkways or on the access ladder (if
provided) are only for authorised maintenance personnel, and must only occur with the
Cooling Tower not in operation, disconnected from the electric power supply, and only for
the time absolutely necessary to carry out the maintenance procedures.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 67 of 138
Warning plates are applied onto the Cooling Tower by DECSA S.r.l., to point out mandatory courses of
action, prohibitions and potential dangers deriving from the use of the Cooling Tower.
The meaning of these plates is summarised in the following table, and their position is shown, as an
example, in the images shown in the following pages.
In the case of detaching of one or more of the plates, their position, as intended by the
manufacturer, must be promptly restored.
Plate Meaning
MANDATORY PLATE:
The operator and/or the maintenance workers must wear the personal
protective equipment (PPE) supplied by the Safety Manager in the place
where the Tower is installed and operates.
PROHIBITION PLATE:
Only appointed and authorised operators and maintenance workers are
allowed to access the areas marked by this plate.
PROHIBITION PLATE:
It is forbidden to remove the safety devices and guards present on the Cooling
Tower, if not for the time that is absolutely necessary to carry out specific
control/maintenance operations, and only after having disconnected the
electrical power supply to the Tower.
PROHIBITION PLATE:
It is forbidden to operate on the machine or its parts whilst in motion.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 68 of 138
PROHIBITION PLATE:
It is forbidden to climb and/or walk on the surfaces marked by this symbol.
Placing working tools or other objects on surfaces marked by this symbol is
also forbidden.
PROHIBITION PLATE:
It is forbidden to carry out any operation (maintenance, cleaning, checking,
etc.) in the areas marked by this plate, if electric power supply has not been
previously cut off from the machine.
DANGER PLATE:
Pay attention when walking or stopping near the machine or under the
perimeter walkways (if present); lack of attention or leaving objects behind in
the upper areas of the machine may cause their falling down.
DANGER PLATE:
Pay attention when accessing the upper section of the machine using
scaffolding, ladders and/or workbenches (or using the optional ladder for
access to the perimeter walkways).
DANGER PLATE:
Pay attention to any stagnating water in the machine lower basin or in the
pipes.
DANGER PLATE:
Pay attention when interacting with and accessing electrical boxes; disconnect
power supply before carrying out any intervention.
DANGER PLATE:
Pay attention when carrying out operations of opening /removal / repositioning
and closure of the fixed guards, such as for example, the axial fan protection
grids.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 69 of 138
In the following images the approximate positions of the plates applied onto the Cooling Tower are shown.
NOTE: The images shown are examples of application; the number and arrangement of the plates are not
binding and they may vary according to the Cooling Tower model.
2
This plate is applied on the electrical
junction boxes and on the live parts.
Because of the incorporation of the Cooling Tower into the plant, in which it will be
integrated, the Buyer shall perform a risk assessment of the plant and apply the
appropriate safety plates, where required (e.g.: "high voltage" warning sign on the
terminal boards of electric motors).
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 71 of 138
The TVA series Cooling Towers are usually dispatched and transported in two separate modules:
The TVA series Cooling Towers models 10-10, 10-12, 10-15 are dispatched fully assembled.
All optional accessories, if any, which have been established during the contract negotiation phase (e.g.
external ladders, guardrails, etc.) are sent disassembled and separate from the Cooling Tower.
The Cooling Tower is dispatched to the installation place disassembled, and therefore DECSA S.r.l. also
supplies a special strip gasket, of sufficient length to guarantee its use along the whole perimeter of the parts
coming into contact, besides all the bolts necessary for assembly of the two sections. These items are
properly packaged.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 72 of 138
The TVA Series Cooling towers are equipped with lifting lugs fastened, by means of bolts, to:
a) side of the lower module (for lifting the “basin section”, F 4.1).
b) top of the upper module (for combined lifting of “exchange section” + “fan section”, F 4.2).
A. Basin section
On each side (long side) of the “basin section” there are 2 or 3 lifting lugs (the number varies according to
the individual Cooling Tower model).
B. Exchange section
C. Fan section
At the top of the fan section there are 4 lifting lugs.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 73 of 138
1. Fasten a metal rope/chain to each seizing point, long enough that, when seizing the two free ends of two
adjoining ropes/chains, and connecting them to a metal ring, a triangle is obtained with the apex angle
having a width of less than 120° ( 3, F 4.3).
2. Couple the metal ring mentioned in item 1 above, with the transversal fixed lifting beam ( 2, F 4.3).
3. The transversal fixed lifting beams must be coupled to the longitudinal fixed lifting beam ( 1, F 4.3).
4. Use a lifting device (crane, bridge-crane, etc.) with a capacity suitable for lifting the Cooling Tower (see
Section 2.8 – Technical data per model).
Before installing the Cooling Tower on the raised floors of a building and/or on the top of a
building, ensure that the load capacity of the floor in the installation location is sufficient to
sustain the overall weight when the Cooling Tower is in operation (see Section 2.8 –
Technical data per model). Furthermore, if the place of installation is located in a seismic
area, the advisability of obtaining a specific certification should be considered.
Before lifting the Cooling Tower, verify that the working loads of the metal ropes, chains and
lifting and transport means are adequate for the overall weight to be lifted ( Section 2.8
- Technical data per model).
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 74 of 138
A Exchange section
B Fan section
C Basin section
1. Longitudinal fixed lifting beam
2. Transversal fixed lifting beams
3. Ropes/chains forming a triangle with apex angle < 120°
The lifting of the Cooling Tower must take place through the use of three lifting beams: one placed
lengthways and one/two transversally, based on the component to be lifted. The chains must be coupled to
the lifting beams as shown in the general drawing shown above.
Only authorised and expert personnel may carry out lifting and handling of the modules
making up the Cooling Tower.
Access to the area where lifting and handling operations are carried out is forbidden to
unauthorised persons.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 75 of 138
The module to be lifted must be placed parallel to the truck which is to be used for
transportation, and the whole area where these operations are performed must be clear of
foreign objects. Nobody should be present in the area of lifting and handling of the module
after the chains have been attached.
After having moved the module very slowly, avoiding any oscillations, check alignment with
the truck loading platform: the staff in charge of checking these operations must avoid
positioning parts of their own body under the lifted module or between the module and the
truck.
Phase 03: RESTING THE MODULE ONTO THE TRUCK LOADING PLATFORM
On the truck loading platform there must not be any foreign objects: their presence may
cause instability of the load or create damages to the loaded module of the Cooling Tower.
If necessary, use appropriate wooden supports to prevent the module of the Cooling Tower
from sliding on the platform of the truck during transportation.
When the module is entirely loaded into the truck and the load is balanced, all ground staff
must keep away. It is then possible to slowly lower the crane arm, in such a way that the
chain tension is gradually released. During the phase of releasing the chain tension, check
that the load does not become unbalanced towards one side of the truck. When the chain
tension is completely released, it is possible to go near the truck and remove the chains
from the lifting lugs.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 76 of 138
The seizing points fitted on the modules have been designed and manufactured for handling
loads on the ground and lifting them from the ground to convey them to the transportation
vehicle (truck), which means for a short distance, with minor lifting from the ground and for
short periods of time. In the event of lifting loads from the ground up to the top of
buildings where the Cooling Tower is to be installed, it is forbidden to use the seizing
points: suitable platforms and restraint systems must be used, instead.
After having placed the modules onto the truck loading platform, they must be fastened with
ropes or belts hooked onto the seizing points available on the modules.
The image above illustrates an example of final configuration of the load on the truck, and
the arrows indicate the position of the seizing points.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 77 of 138
5 INSTALLATION
5.1 Localisation: general guidelines
Operation of the TVA series Cooling Towers is not affected by either the direction or the intensity of wind, as
the air discharge is directed vertically and the discharge speed of the air is higher than its intake speed.
However, it is advised to take some precautions to prevent risks deriving from air circulation. The saturated
air exhausted must be freely dispersed in the atmosphere: should any of this air be recycled, the efficiency of
the Cooling Tower would be compromised. The air is the dispersion means for the heat extracted from the
water: to optimise performance of the Cooling Tower, the objective of correct installation must be that of
providing conditions for a perfect air circulation; for this reason, the main rules to observe are as laid out here
below:
4. Do not install the machinery near extractor fans of any type (hot air,
kitchen fumes, or similar).
5. Pay attention to the dominant winds: they increase the risk of recycling the exhausted air as they tend to
push the discharged air flow downwards. Furthermore, the action of the wind produces a depression area
in correspondence to the opposite wall of the one involved.
6. Evaluate any free spaces which must necessarily be provided, especially on the sides: both water intake
connections and safety equipment (ladder, walkways and guardrails) require, in fact, ample spaces to
enable maintenance interventions without creating any obstacles which may interfere with the activities of
maintenance personnel.
During the design phase of the cooling system, the parameters to be taken into
consideration for the choice of the Cooling Tower are summarised in the following table.
Before proceeding to installation, verify that the characteristics of the Cooling Tower are
coherent with the parameters evaluated during the design phase and that such parameters
have not undergone significant variations during the time elapsed between the design of the
system and its realization.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 78 of 138
T 5.1 – Evaluation parameters, for the choice of model, subject to possible change before installation
Parameter Evaluations
Presence of free spaces around the Cooling Tower, to make maintenance
interventions easy.
Localisation
Presence of obstacles for free circulation of the air exhausted and of the air
suctioned.
Substances used to treat the water, if any, and their action on the materials
Water treatment
used for manufacturing the Cooling Tower.
Environment noise Impact of noise pollution with respect to the area of installation of the Cooling
levels Tower.
It should be noted that in order to make it possible to install scaffolds, needed for the assembly of
the three sections which make up the Cooling tower, it is necessary to leave a free area, with a width
of at least 1500 mm, all around the tower.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 79 of 138
The Cooling Tower must not be installed near a wall with a height equivalent to or higher than the Tower, in
order to avoid the possible recycling of exhausted air, as shown in the following picture.
In the event it is not possible to place the Cooling Tower in a different position, to decrease the recycling
effect of the exhausted air, it is advised to use a suction hood, to raise the expulsion point beyond the height
of the obstacle.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 80 of 138
Moreover, the presence of roofs or other coverings which may impede free release into the environment of
the exhausted air must be avoided. The presence of this type of obstacle would cause a considerable
decrease in efficiency of the Cooling Tower.
Particular physical characteristics of the Cooling Tower installation area may require a pipe for air outlet.
In the case of Cooling Towers with axial fans (TVA series) it is appropriate to channel the
exhausted air with a vertical pipe. The solution with a vertical/horizontal pipe is not advised.
In both cases, it is necessary to arrange the pipes in such a way as not to create obstacles for the air flow,
and to provide windows/doors for inspection/access inside the Cooling Tower. In the case of doubts or need
for further information, please contact DECSA Technical Department.
The following table shows the minimum and maximum admitted values for positioning of the Cooling Tower,
according to the installation conditions, as shown in the pictures above:
The diagrams shown are, of course, an example of some of the various installation modes
for the Cooling Towers: it is impossible to provide exhaustive instructions on all possible
ways to install the Cooling Towers in the Instruction Manual.
For further specific information, please contact DECSA Technical Department.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 82 of 138
During their normal operation, the TVA series Cooling Towers, especially in some periods of the year
(typically winter or autumn), may create mists.
To check what conditions generate this phenomenon, it is useful to refer to a psychometric diagram, as
provided in the following instructions:
1) Indicate with A the point representing the conditions of the air suctioned by the Cooling Tower.
2) Indicate with B the point representing the conditions of the air in the area of release into the environment.
3) Joint points A and B: if segment AB is beyond the saturation curve, the wider the area between the
segment and the saturation curve, the higher is the probability of mist formation.
⇒ Verify the temperatures of the location and the Cooling Tower operating conditions: if mist
formation is probable, install the Tower in such a way that any potential mist produced does not
represent an obstacle and does not become the cause of complaints (for example if near busy
roads, residential areas, etc.).
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 83 of 138
F 5.1 – Example for determination of the probability of mist formation at outlet of the Cooling Tower
Before installing the Cooling Tower, it must be ensured that the designated resting surface can support the
weight of the Tower in operation, i.e. the weight of the Cooling Tower plus the weight of the water contained
in the collection basin.
Further information Total weight during operation: Section 2.8 - Technical data per model
SIMPLE PLACEMENT
The TVA series Cooling Towers do not usually require any specific resting structure: it is sufficient that the
surface is perfectly horizontal. In the case of placing the machinery onto profiles, its frame must be of a
closed type.
Unload the modules from the means of transport and rest them on the ground in the area arranged for
final installation of the Cooling Tower, using the seizing points shown in figures F 4.1 and F 4.2.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 87 of 138
1) Rest the lower module onto the surface intended for installation (level and horizontal surface).
2) Check that the contact edge with the “exchange section” has not undergone damages during
transportation.
4) Cut a sufficient amount of sealing tape (butyl rubber) to cover the contact edge; remove the protective
film from one side of the tape and make it adhere to the upper edge of the “basin section”, pressing
firmly.
5) Remove the protective film from the upper side of the sealing tape and pierce the tape in
correspondence to the holes present on the edge.
6) Position the sealing rod on the tape, in the area between the holes and the internal part of the section,
as shown in the following image.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 88 of 138
F 5.3 – Sealing
1. Sealing tape
2. Sealing rod
3. Edge of the “Basin section”
4. Edge of the “Exchange section”
5. Fastening screw + bolt
7) Check that the contact edge of the “exchange section” with the “fan section” has not undergone
damages during transportation.
8) Lift the upper module consisting of the “fan section” and the “exchange section”, using chains fastened
onto the arranged lugs and position it correctly on the lower module by means of the metal pins inserted
into the holes next to the four corners.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 89 of 138
F 5.4 – Centring the “exchange section” on the “basin section” by means of metal pins
If the holes of the two edges were not aligned, the upper module might have been placed in
a not perfectly horizontal position, or it may have been seized in an incorrect manner for
lifting.
If necessary, it is possible to widen the holes, in order to obtain their proper alignment,
making it easier to introduce the stem of the fastening screw. Before making any hole larger,
remove the sealing tape.
During the centring phase of the two modules by means of the metal pins, never place your
hands between the two edges.
9) When the holes are perfectly aligned and the load is not unbalanced, all the ground staff in charge of
these operations must keep off the unit.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 90 of 138
10) Lower the crane arm slowly, so that the tension of the rods decreases gradually. Check that in the chain
tension releasing phase the load does not become unbalanced on one side. When the tension of the
chains is completely released, it is possible to approach the unit and remove the chains from the lugs.
At the end of this operation, the arrangement of the three sections will be like the one shown in the image
below.
1 Lower module
2 Upper module
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 91 of 138
12) Fasten the two modules with the nuts, along all the conjunction perimeter, in all points arranged by the
Manufacturer.
The ladder and walkway group is optional and it is therefore not present in the ordinary
supply of TVA series Cooling Towers. Relevant request for this equipment should be made
when purchasing the partly completed machinery.
If installing walkways, ladder, perimeter guardrails between the “exchange section” and “fan section” is
arranged by contract and stipulated between the parties, these will be installed only at the end of the
assembly procedures of the two sections that make up the Cooling Tower.
Fasten the guardrails to one another using the relevant clamps supplied.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 93 of 138
The following image shows the right side of the Cooling Tower (pump side) and the coupling points with the
water connection.
1. Bottom drain
2. Overflow
3. Water make-up
(maximum pressure 2 bar)
4. Cooled water outlet
5. Inlet of water to be cooled
Further information:
Section 5.8 - Water connection
Section 5.9 - Electric power supply line
Section 5.10 - Connecting the motors
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 94 of 138
All sealing of the panels making up the Cooling Tower are carried out by DECSA S.r.l. before delivery of the
unit to the Purchaser. However, both during the lifting phases and transportation it is possible that some of
the sealed sections undergo alterations or changes which may cause water leakages during operation of the
plant.
2. Sealing of the junctions must always be carried out in the internal part.
3. The surfaces to be re-sealed must be cleaned to remove any remains of material previously used, and
grease must be accurately removed with an appropriate product.
4. Evenly seal a section which is far larger than where the leak has been found: use an appropriate
extruder, avoiding excess application of product.
5. Do not operate the Cooling Tower for at least 24 hours. In the case of potential rain, protect the Cooling
Tower with plastic tarps.
Use a non-acetic, single-component sealant: read and follow the instructions on the product
Technical Specification sheet carefully.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 95 of 138
All inlet and outlet pipes must be sustained by their own specific supports: it is forbidden to use the
structure of the Cooling Tower or any other of its components as a support for the external pipes.
The Cooling Tower must be installed at the highest point in the water circuit to prevent emptying of the
system when the pump is not running; alternatively the following must be fitted:
• a check valve onto the fitting on the water outlet from the Cooling Tower
• an air-relief valve for water circulation system
Position the water-circulation pumps at a lower level than the water collection basin of the Cooling
Tower.
The sizing and laying of the pipes must be carried out taking into account their expansion.
Before tightening the bolts of the flanged connections, verify alignment and coplanarity of each flange.
In case of installation of 2 or more Cooling Towers, the pipes must be designed and installed in such a
way as to balance the following:
• the pressure drop of the various branch pipes
• the load of the process fluid on the individual Towers
Arrange sluice gates for each Cooling Tower installed, in such a way as to enable independent
maintenance interventions for each of them. These sluice gates may also be used to balance any
alteration of the water flow rate in the pipes.
The maximum pressure of the water line for water level make-up must be as indicated in the technical
data table ( Section 2.8 - Technical data per model).
The max. operating pressure at the fitting on the water inlet must be that indicated in the technical data
table ( Section 2.8 - Technical data per model).
Pressure values which are higher than indicated may damage the water distribution system
inside the Cooling Tower.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 96 of 138
The Cooling Tower is partly completed machinery, which can be equipped with an electrical panel supplied
as accessory.
The procedure of connecting the partly completed machinery to the electric power supply
provided by the purchaser must be carried out by qualified and specialised technicians, in
compliance with the relevant regulations in force.
Motor power (kW) Cable cross-section Motor power (kW) Cable cross-section
(mm2) (mm2)
0.09 1.5 4 2.5
0.12 1.5 5.5 4
0.18 1.5 7.5 4
0.25 1.5 9 6
0.37 1.5 11 6
0.55 1.5 15 10
0.75 1.5 18.5 10
0.9 1.5 22 16
1.1 1.5 30 25
1.8 1.5 37 25
2.2 1.5 45 35
3 2.5 55 35
T 5.3 – Minimum cable cross-sections according to the electric motor power
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 97 of 138
3. A thermal-magnetic circuit breaker must be installed upstream from the power supply line for the Cooling
Tower.
4. Verify that the electrical data of the power supply line (voltage and frequency) are consistent with the
rating plate data of the Cooling Tower.
5. Verify that all electrical cables are well connected, and fastened in such a way as to avoid their accidental
tearing, disconnection or damage.
7. For operation in winter, electric heating elements must be installed in the water collection basin: these will
have to be equipped with a safety thermostat. This is to prevent the water from reaching freezing
temperature.
The bulb of the control thermostat of the heating element will have to be positioned:
• near the bottom of the water collection basin
• as far as possible from the heating elements
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 98 of 138
The characteristics of the motors installed on the TVA series Cooling Towers in terms of insulation class and
protection level as laid out in Section 2.8 - Technical data per model, are such to ensure operation even
when they must operate in humid environments. However, the following is to be taken into account:
In the case of operation with inverter, it is necessary to verify that the number of revolutions of the motor-
ventilator group is within the designed values: in the case of doubt contact DECSA After Sales Service.
Never start-up a motor driven by an inverter without knowing the maximum admitted number
of revolutions for the fan: the risk is to cause serious damage to the fan!
Furthermore, before commissioning, verify what the resonance speed is and ensure that this
speed is never reached.
To limit wear and tear of the motors, the advised maximum number of start-up procedures
per hour is: 5
Before commissioning the Cooling Tower, carry out a trial of the electrical system. Fill in the
test & trial form with a description of the checks carried out, the outcome, identification of the
person in charge, signature and date. Keep the Test & Trial Form in a safe place with the
technical documentation relevant to the whole Cooling System.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 99 of 138
Being the Cooling Tower of the TVA series partly completed machinery, it must not be
operated until it is incorporated into the machinery/plant for which it was designed and the
CE certification attesting conformity of the final machinery/plant with the Machinery Directive
requirements is issued.
For safe operation of the Cooling Tower, after its installation a number of checks must be carried out,
following the procedures outlined here below:
1. The float valve, located on the water line for water level make-up is usually locked to avoid damages
during transportation: check that it has been unlocked.
2. Check that inside the Cooling Tower (water collection basin, fan housings, etc.) there are no foreign
bodies or working tools left behind by accident during the installation phase. Verify that thorough and
proper cleaning of the internal parts is carried out, to avoid circulation of solid remains which may obstruct
water circulation.
3. Visually check that the water and electrical lines do not present malfunctions or evident damages.
4. Visually check that the ladder, walkways and perimeter protection guardrails, positioned at the top of
the Cooling Tower, if applicable (optional), are correctly installed and fastened.
5. Check that all the protection grids and access doors are correctly positioned and fastened by means of
the relevant mechanical locking devices.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 100 of 138
2. The float valve must shut completely when the water level in the collection basin is at the overflow drain
connection.
Avoid at any rate, that the water level in the collection basin is lowered beyond 10 cm from the overflow
drain connection, to prevent the risk of cavitation of the pump, with consequent decrease of the amount of
water sprayed, as well as fast wear and tear of the pump impeller.
- Adjustment of the counter-pressure exercised by the valve on the tap takes place as outlined below:
• by moving the float and making it slide along its rod, the counter-pressure exercised on the water at
inlet increases.
3. The water level in the collection basin must not be too low, because there may be the risk of re-suctioning
of air by the pump, with consequent quick wear and tear of the water pump impeller. The phenomenon of
air re-suction may be acknowledged by detecting an intermittent noise of air discharge through the
water spraying nozzles. This phenomenon must be considered as normal during commissioning of the
Cooling Tower, as it is caused by bleeding of the air contained inside the pipes. Should this, however,
continue, a potential re-suction of air in the pump connection should be considered: stop the system and
check the water level in the basin.
4. In the case of abnormal vibrations of the moving parts, stop the motors immediately and contact DECSA
After Sales Service.
Further information Section 1.4 – Instructions for customer care intervention request
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 102 of 138
For correct first start-up or seasonal start-up, follow the procedure outlined here below. For a thorough
understanding of the operations summarised in the table below, all information laid out in the previous pages
of the Instruction Manual must have been read and understood.
2. Cleaning and washing the suction grids, the water collection basin and the water filter
4. Check that the spraying nozzles have not been obstructed by deposits or encrustations
5. Check that on the external pipes of the evaporative wet deck fill there are no evident traces of
deposits or encrustations.
9. Checking the tightness of the fastening bolts on the motors and the protection grids
Once 24 hours of ordinary operation under load have elapsed, check status of the Cooling Tower:
2. Visual check of the spraying nozzles: they must be neither completely nor partially obstructed
by deposits
3. Visual check of the evaporative wet deck fill: there must not be any traces of deposits or other
remains
5. Verify correct tightening of the locking screws of the motors and of the protection grids / panels
After having left the Cooling Tower inactive for a long period, for example, because of seasonal stop or at
any rate for a period shorter than 6 months, before starting-up the system again, an overall check of the
conditions of the Cooling Tower must be carried out:
1. Overall check: status of sealing, electrical cables and relevant connections, protection grids.
Resume ordinary status of the Cooling Tower.
Nature of the residual risk Action to take
Biological / Chemical Use adequate PPE ( Chapter 3 – SAFETY).
Place the electric power supply switch in the “O” position and lock
Mechanical
it.
2. Visual check of correct operation of fans, correct direction of rotation, and constancy in the
rotation speed.
Nature of the residual risk Action to take
Electrical
Visual check with protection grids assembled and fastened.
Mechanical
4. Close the water make-up valve and drain the relevant pipe.
Nature of the residual risk Action to take
Biological Use adequate PPE ( Chapter 3 – SAFETY).
Each Cooling Tower must be connected to its relevant electric panel for power supply and system control.
Designing and constructing the control panel are done by the Purchaser. The control panel
must be designed and cabled according to the specific Cooling Tower model and the
optional accessories supplied; this must be fitted with a door containing a lock, to prevent
access to the controls by unauthorised personnel.
IMPORTANT: The key for opening the access door to the controls must be kept by the operator in charge of
running the system.
The Control Panel is to be positioned near the Cooling Tower, at a distance of about 5 metres, to enable the
person in charge of running the Tower to visually check the operational area during the start-up procedures.
If agreed during the contract negotiation phase, the partly completed machinery may be
equipped by DECSA S.r.l. with its own control and command panel ( Chapter 10 –
ACCESSORIES).
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 107 of 138
Although the Cooling Towers are simply built, they usually undergo heavy operating conditions, due to their
location which is, usually, outdoors. The TVA series Cooling Towers have excellent protection against
weather conditions, being entirely manufactured with top quality hot-dip galvanized steel plate, further
protected by epoxy resin based enamels (optional treatment). All the electric motors and supports for the
fans are of special construction, in consideration of outdoor installation. Maintenance operations are
therefore reduced to the least possible. Good operation of the Cooling Tower over time requires, however,
some maintenance and control operations. In this chapter the main operations which must be carried out
regularly are listed: the suggested frequency may undergo variations, even considerable ones, depending on
the particular conditions where the Cooling Tower operates.
Frequency: Monthly
Safety: • Place the electric power supply switch in the “O” position and lock it.
• Use adequate PPE ( Chapter 3 – SAFETY)
Procedure: • Empty and rinse the basin until all impurities have been removed.
• Wash the pump filter, removing it if necessary.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 109 of 138
Frequency: Monthly
Safety: • Place the electric power supply switch in the “O” position and lock it.
• Use adequate PPE ( Chapter 3 – SAFETY)
Any damage to the fan or to the electric motor may cause vibrations to the Cooling Tower. If this occurs, stop
the Cooling Tower immediately and check causes for the vibrations. The water recirculation pump must also
be checked regularly.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 110 of 138
Frequency: Monthly
Safety: • Place the electric power supply switch in the “O” position and lock it.
• Use adequate PPE ( Chapter 3 – SAFETY)
Procedure: • Check each nozzle: there must not be any obstructions or encrustations by foreign
substances and all nozzles must spray in a full and continuous way.
• If necessary, remove any nozzle requiring interventions, and carry out cleaning or
replacement.
Removal of the nozzles does not require particular tools as they are made of rubber and can
be disassembled by pulling them outwardly (F 7.1) while at the same time making them
rotate alternatively, slightly clockwise and anti-clockwise. Hold the PVC header in place
when doing this operation.
• Re-assembly: wet the collar of the nozzle before re-placing it in its position.
Frequency: Monthly
Safety: • Place the electric power supply switch in the “O” position and lock it.
• Use adequate PPE ( Chapter 3 – SAFETY)
Procedure: • Visual check of the status of the evaporative wet deck fill
As encrustations are formed due to bad water quality and/or irregular spraying, a frequent
check of the evaporative wet deck fill may save great problems to the Cooling Tower:
Safety: • Place the electric power supply switch in the “O” position and lock it.
• Use adequate PPE ( Chapter 3 – SAFETY)
Procedure: • The bleed pipe is fitted with a valve which should be adjusted according to the water
conditions: based on periodical observations and data collection, the best position of the
valve should be identified, to avoid encrustations and to keep water consumption at low
levels.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 113 of 138
Safety: • Place the electric power supply switch in the “O” position and lock it.
• Use adequate PPE ( Chapter 3 – SAFETY)
Procedure: • In the case of long periods of inactivity, the fans must be regularly activated to avoid
excessive drying out of the bearings and gaskets.
The pump must also be started regularly to prevent arising of situations inside it, which
could prevent it from starting up when putting the Cooling Tower back into use.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 114 of 138
Safety: • Place the electric power supply switch in the “O” position and lock it.
• Use adequate PPE ( Chapter 3 – SAFETY)
Procedure: • Loosen the bolt that fastens the float to its rod.
• Adjust the position of the float along the rod, in such a way that the valve shuts completely
once the desired water level is reached.
• Tighten the bolt that fastens the float to its rod.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 115 of 138
Frequency: Yearly
Safety: • Place the electric power supply switch in the “O” position and lock it.
• Use adequate PPE ( Chapter 3 – SAFETY)
Procedure: • Close the valve for water inlet into the spraying nozzles.
• Close the valve for inlet of make-up water into the basin.
• Open the drain valve.
• Let the water at the bottom flow out.
• Enter the basin through its relevant opening, clean the walls and the bottom of the basin
with clean water and, if necessary, use cleaning products to remove deposits. Follow the
instructions provided by technicians specialized in the treatment of industrial containers for
water storage.
• Close the drain valve when cleaning is completed.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 116 of 138
For motor maintenance details, please refer to the documentation provided by the motor Supplier.
However, to make it easier for information relevant to maintenance of the Cooling Tower to be passed on,
the following summary table is provided:
OPERATIONAL LIFE: The bearings are fitted with an automatic grease disposal device.
30000 hours The bearing chambers must be previously filled with grease up to
no more than half of their capacity, because an excessive
amount of grease would cause high operation temperature.
The refilling may be carried out through the grease nipple fitted
on bearing covers located on both sides of the motor. Clean the
grease nipple before refilling.
Motor at 1500 rpm (50 Hz) Motor at 1800 rpm (60 Hz)
or or
6 months 6 months
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 117 of 138
The parts not indicated in this section (for example: motors, fans and recycling pump) shall be
assembled only by DECSA s.r.l. service staff.
If needed, contact the After Sales Service using the contact details indicated in section 1.4 -
Instructions for customer care intervention request.
The following table shows the spare parts that can be requested to DECSA S.r.l. and assembled on the TVA
series Cooling Towers by the purchaser's maintenance personnel.
Position: The drift eliminators are assembled between the water distribution system and the fans
(see figure F 7.2).
Disassembly/assembly procedure:
1) Place the electric power supply switch ( section 6.5 - Control panel) in the “O” position and lock it.
2) Unscrew the 4 nuts from the stud bolts that fix the window to the fan section and remove the window.
3) Remove the drift eliminators from their housings (F 7.2) and extract them through the window.
4) Insert the new drift eliminators through the window by observing the previous arrangement.
Position: The gasket is fitted at the end of the nozzle header, as in picture (F 7.3).
Disassembly/assembly procedure:
1) Place the electric power supply switch ( Section 6.5 - Control panel) in the “O” position and lock it.
2) Remove the screws that fasten the protection grid located on the upper part of the fan cylinder and remove the grid
( 2.5.3 - Fan protection grids).
3) Go into the fan section passing through the fan blades.
4) Place one's feet on the fan supporting crossbars and take a position of stable equilibrium by having one hand on a
support.
5) Remove the drift eliminators ( Section 2.5.7 - Drift eliminators) with the free hand.
6) Enter inside the “exchange section”, placing one's feet carefully on the wet deck fill.
7) Unscrew the screws of the U-brackets holding the secondary headers (PVC) and remove the headers.
8) Replace the gaskets placed on the main header (F 7.3).
9) Put the secondary PVC headers back in place and fix them with the U-brackets previously removed.
10) Go back into the fan section, by placing one's feet on the fan supporting crossbars and take a position of stable
equilibrium by having one hand on a support.
11) Put the drift eliminators back in place.
12) Exit the fan section.
13) Reassemble the fan protection grid and lock it with the clamping screws.
Position: The water distribution system, composed of a header and spraying nozzles, is fitted
between the wet deck fill and the drift eliminators, as in picture (F 7.4).
Disassembly/assembly procedure:
1) Place the electric power supply switch ( Section 6.5 - Control panel) in the “O” position and lock it.
2) Remove the screws that fasten the protection grid located on the upper part of the fan cylinder and remove the grid
( 2.5.3 - Fan protection grids).
3) Go into the fan section passing through the fan blades.
4) Place one's feet on the fan supporting crossbars and take a position of stable equilibrium by having one hand on a
support.
5) Remove the drift eliminators ( Section 2.5.7 - Drift eliminators) with the free hand.
6) Enter inside the “exchange section”, placing one's feet carefully on the wet deck fill.
7) Unscrew the screws of the U-brackets holding the secondary headers (PVC) and remove the headers.
8) Replace the nozzle headers and/or the spraying nozzles (F 7.4).
9) Go back into the fan section, by placing one's feet on the fan supporting crossbars and take a position of stable
equilibrium by having one hand on a support.
10) Put the drift eliminators back in place.
11) Exit the fan section.
12) Reassemble the fan protection grid and lock it with the clamping screws.
1. Spraying nozzle
2. Nozzle header
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 121 of 138
Position: The air inlet grids are located in the basin section, as in figure (F 7.5)
Disassembly/assembly procedure:
1) Place the electric power supply switch ( section 6.5 - Control panel) in the “O” position and lock it.
2) Unscrew the screws fastening the crossbar that fixes the air inlet grids.
3) Remove the air inlet grids (F 7.5) and strictly respect the direction of the air inlet ducts in the Cooling Tower (not to
swap the air inlet grids when reassembling).
4) Wipe off any dirt from the lower support.
5) Place the new air inlet grids in the correct assembly direction (see point 3).
8 TROUBLESHOOTING
To make it easier to find the main causes for an operation failure, in this chapter the most probable failures
that can occur during the operational life of the TVA series Cooling Towers are listed:
The fans fail to rotate b) The motor is seized up. b) Reset the motor.
See documentation related to the motor.
The motor is noisy. b) If the noise is of a magnetic type, the b) Replace the motor.
motor is defective.
b) Spraying nozzles turned upwards. b) Rotate the nozzles in such a way that they
Water comes out from the drift
spray water downwards.
eliminators.
c) Excessive air flow rate. c) Reduce air flow rate by decreasing the
speed.
Water comes out from the plate a) Damage to the joints during a) Restore tight condition.
joints. transportation or installation. Section 5.7 - Sealing leaks.
A lot of water comes out of the a) Float valve open too wide. a) Lower the float.
overflow drain.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 123 of 138
The water level in the basin is a) Float valve too closed. a) Lift the float.
far below the overflow.
Suction of water from the basin a) Level of water too low. a) Adjust the valve. Lift the float.
and of air (cavitation).
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 124 of 138
9 DISMANTLING
At the end of the life cycle of the Cooling Tower, the most opportune measures must be taken to dismantle it
and dispose of its various parts.
To supplement these regulations it is advised that the following should be considered “special materials” and
disposed of appropriately:
lubricants and refrigeration fluids
various filters
pressure containers
batteries and accumulators
cathode-ray tubes and liquid crystal displays
rubber parts
electronic boards and components
With regard to disposal and recycling, it is advised that the following items should be separated:
plastic and synthetic material (structural, relevant to components or plants)
electrical material (cables, motors, transformers, etc.)
metal material (structure, guards, etc.)
Before proceeding to dismantling, it is mandatory to disconnect the Cooling Tower from the
water supply circuit and the electric power supply line.
Read Chapter 4 - HANDLING AND TRANSPORTATION which includes the necessary
information for lifting the components of the Cooling Tower.
Pack adequately the disassembled parts, according to their individual mass and characteristics: handle them
with the utmost care. Fasten a plate on each package stating the mass, the contents and any other
necessary information for transportation.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 125 of 138
For disposal of the components, the parts must be taken to relevant selective waste collection points
according to the material they are made of:
Float of the valve for water make-up PVC Motor casing Steel
10 ACCESSORIES
The present chapter lists and describes the accessories which may be applied to the Cooling Towers
manufactured by DECSA S.r.l. upon specific request from the Purchaser.
The accessories installed in the Cooling Tower are those established during the contract
negotiation phase. For these accessories DECSA S.r.l. will provide the necessary documentation
to identify the technical data relevant to a specific part, as well as any procedures for their correct
installation, adjustment and maintenance. The documentation available is provided in Chapter “11
– Enclosures” of the present Manual.
Ref. Accessories
10.1.1 Accessories for the motor
10.1.2 Antifreeze heater
10.1.3 Heating mesh
10.1.4 ON/OFF switch
10.1.5 Junction box
10.1.6 Level check device
10.1.7 Vibration switch
10.1.8 Water automatic bleed
10.1.9 Water treatment system
10.1.10 Axilent and Axilent Plus fans
10.1.11 Walkway and access ladder
10.1.12 Control panel
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 127 of 138
The motors installed in the Cooling Towers and their relevant accessories are chosen based on the
Purchaser’s operational needs, and according to the installation location of the Cooling Tower. In particular,
the following motors and accessories can be installed:
• Double-speed motor (Dahlander) to enable operation at two different rotation regimes (full load or
reduced load).
• Atex motor: explosion-proof motor for operation in environments subject to risk of formation of
explosive conditions.
• Motors with 50 Hz or 60 Hz frequency and power supply voltage, even different from 400 V,
according to the location of installation.
• The motors may be supplied with power supply cables (not wired) or with appropriate connection
terminal board installed on the motor itself.
• PTC probes (for operation with inverter).
• Tropicalization: protection device for operation in areas undergoing harsh weather conditions
(hot/cold and humid).
• Anti-condensation heaters: they prevent the formation of condensation in the winding when the
motor is operated at low temperatures.
In the table below the types of anti-condensation heaters that can be applied to the motors according to their
sizes are listed.
The antifreeze heater (F 10.1) is fitted at the bottom of the water collection basin, to prevent the risk of water
freezing when the Cooling Tower is installed in low temperature areas (outdoor installation in very cold
winters). The antifreeze heater can have a variable power from 1 kW to 8 kW (400 V / 3 phases / 50 Hz),
according to the temperature of the installation location. It is equipped with safety thermostat to prevent
temperature peaks from jeopardising the integrity of the gasket and of the PVC box.
Heater Thermostat
The heating mesh is fitted on the cylinder of the axial fans, to prevent possible frosting of the water vapour in
contact with the metal surfaces (solidification of the vapour)
The resistance (70 W/m – 230 V / 1 phase / 50 Hz) is provided with a safety thermostat.
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 129 of 138
This is a disconnection device from the electric power supply. It is installed on board the machine and
enables the removal of electric power supply from the users connected to it, to be able to safely carry
out maintenance operations to the Cooling Tower. The switch can be locked in the “O” position (OFF).
This is installed on board the machine, and it allows distribution of the terminal boards to the various
users, enabling an easier power supply to them.
This is a single or four-probe electronic device for water level check inside the basin. It is a “simple contact”
which can send an alarm message and/or activate auxiliary units connected to it (for example, water make-
up with solenoid valve).
Absorbed power 5 VA 5 VA -
Power supply to
22 VAC 22 VAC -
electrodes
Specific weight of
³ 0.7 ³ 0.7 -
fluid
This is an electro-mechanical device for detection of the vibration intensity. It is installed near the rotating
parts, it consists of a simple contact which can send an alarm signal or remove continuity to the motor power
supply circuit, when the vibration level detected by the device exceeds the value set on the device itself
(adjustment of sensitivity).
This is a device to control concentration of salts dissolved in water. It mainly consists of a conductivity probe
(F 10.6) which detects water conductivity (linked to the concentration of salts contained in it), and of a
programmable controller (F 10.7) which reads and analyses signals sent by the probe. In the event the water
conductivity level detected by the probe is beyond the threshold set by the controller, an electro-activated
valve is prompted (F 10.8) to enable bleeding of part of the water present in the Cooling Tower basin. In this
way, the water level in the basin decreases progressively until it activates the automatic device for water
make-up in the Cooling Tower, with consequent restoration of the correct water level and decrease of the
degree of concentration of the dissolved salts.
F 10.6 – Example of conductivity probe F 10.7 – Example of programmable F 10.8 - Example of electro-activated valve
controller
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 132 of 138
This a system for treatment of water used in the cooling process of the Tower. It enables appropriate dosing
of relevant products inside the Cooling Tower (biocides and/or solutions for control of water characteristics,
such as pH, hardness, salt concentration, etc.) with the aim of maintaining the desired water characteristics
constant over the time. This system usually consists of a WTC (F 10.10), a pulse-sender Meter (F 10.11), an
electro-activated valve (F 10.12). In picture F 10.9 the diagram of an example of water treatment system is
shown.
Instead of a standard fan, the Axilent fan (F 10.13) and the Axilent Plus fan (F 10.14) enable noise reduction
to 6 db(A) and 12 db(A) respectively, although they have reduced powers installed with respect to its
homologue centrifugal Cooling Tower.
These optional items require the adoption of an angle transmission with reduction ratio reaching up to 5:1,
and service factor equivalent to 2.
A walkway is usually installed on the Cooling Tower on the side fitted with inspection window, so as to carry
out in safety the inspection and/or maintenance operations for the components located on the top of the
Tower (for example motors, fans, etc.). The walkway is equipped with guardrails, and is reached by means of
a ladder fitted with safety cage.
Maximum overall load of the walkway: 200 kg (corresponding to two maintenance operators
plus small working tools).
Printed on:
Assembly and maintenance instructions Version: MS 11 16 TVA/E
“Cooling Tower”
TVA Series Revision: 01
Page: 135 of 138
The Control Panel supplied by DECSA S.r.l. includes all the commands needed to control the Cooling Tower
operation, and other accessories. The image below shows an example of the Control panel of TVA partly
completed machinery made by DECSA S.r.l.
11 ANNEXES
The present chapter includes any annexes, produced by DECSA S.r.l., which must be considered as an
essential part of the Instruction Manual. Some of these annexes may already have been previously
forwarded to the Purchaser, when delivering the Cooling Tower: the enclosed copy should not be intended
as a change or an update, but the completion of the Manual, to facilitate the availability of information sought
for.
Moreover, any documentation provided by the Suppliers of trade parts (for example: electric motors, etc.),
which are forwarded to the Purchaser by DECSA S.r.l., must also be considered an essential part of the
present Instruction Manual. For a detailed list of the supplier documentation see the Consignment Letter.