Professional Documents
Culture Documents
288623NC
288623NC
Part Number
288623-01
Rev.
NC (01/12)
CIDE Measurement Configuration and Verification Manual
* Denotes a trademark of Bently Nevada, Inc., a wholly owned subsidiary of General Electric
Company.
Proximitor*, Keyphasor*
Contact Information
The following contact information is provided for those times when
you cannot contact your local representative:
Mailing Address 1631 Bently Parkway South
Minden, Nevada USA 89423
USA
Telephone 1.775.782.3611
1.800.227.5514
Fax 1.775.215.2873
Internet www.ge-mcs.com/bently
ii
Additional Information
NOTE
This manual does not contain all the information required to operate and
maintain the monitoring system. Refer to the following manuals for other
required information.
Customers and third parties, who are not member states of the European Union, who are in
control of the product at the end of its life or at the end of its use, are solely responsible for
the proper disposal of the product. No person, firm, corporation, association or agency that
is in control of product shall dispose of it in a manner that is in violation of any applicable
federal, state, local or international law. Bently Nevada, Inc. is not responsible for the
disposal of the product at the end of its life or at the end of its use.
iii
CIDE Measurement Configuration and Verification Manual
Contents
1. 3500 ENCORE Compatibility Requirements ..................................................... 1
2. ENCORE Nomenclature ........................................................................................ 2
3. ENCORE CIDE Screen Displays ........................................................................... 3
3.1 Display Components ................................................................................................................................. 3
4. Configuration ......................................................................................................... 5
4.1 CIDE Channel Configuration Considerations ................................................................................ 5
4.2 Transducer Setup & Filtering Tab ....................................................................................................... 7
4.2.1 Reference Information ................................................................................................................... 7
4.2.2 Transducer ........................................................................................................................................... 8
4.2.3 Upscale Direction ........................................................................................................................... 10
4.3 Variables & Alarms Tab ........................................................................................................................ 10
4.3.1 Composite Full Scale Range ..................................................................................................... 11
4.3.2 Clamp Value ..................................................................................................................................... 11
4.3.3 Gap Range ......................................................................................................................................... 11
4.3.4 Delay ..................................................................................................................................................... 11
4.3.5 Alarm Mode ....................................................................................................................................... 12
4.3.6 OK Mode ............................................................................................................................................. 13
4.3.7 Not OK Channel Pair Defeat ..................................................................................................... 13
4.3.8 Recorder Output ............................................................................................................................. 14
4.3.9 Adjust (Cross Over Voltage, Direct) ....................................................................................... 14
4.4 Available Setpoints .................................................................................................................................. 14
4.4.1 Alarm Setpoint Dialog .................................................................................................................. 15
5. Verification ........................................................................................................... 16
5.1 Test Equipment and Software Setup ............................................................................................. 16
5.1.1 Test Equipment Setup ................................................................................................................ 16
5.1.2 Verification Screen Setup ........................................................................................................... 17
5.2 Adjusting the Scale Factor .................................................................................................................. 17
5.3 Adjusting the Cross Over Voltage ................................................................................................... 18
5.4 Test Alarms ................................................................................................................................................. 19
5.4.1 Composite .......................................................................................................................................... 20
5.5 Verify Channel Values ........................................................................................................................... 21
5.5.1 Verify Channel Composite and Direct Values .................................................................. 21
5.6 Test OK Limits ............................................................................................................................................ 24
iv
Section 1 - 3500 ENCORE Compatibility Requirements
1
CIDE Measurement Configuration and Verification Manual
2. ENCORE Nomenclature
3300 ENCORE Upgrade Rack
A 3300 Monitoring System Rack that has been upgraded to contain 3500 ENCORE
modules. The original 3300 I/O modules are retained. 3500/45E and 3500/42E monitors
installed in a 3300 ENCORE Upgrade rack are limited to two measurement channels.
3500 ENCORE Rack
A 3500 ENCORE Monitoring System rack designed to contain 3500 ENCORE modules
including 3500 ENCORE I/O modules. 3500/45E and 3500/42E monitors installed in a
3500 ENCORE rack have four measurement channels.
2
Section 3 - ENCORE CIDE Screen Displays
1. Composite
2. Direct
3. Gap
3
CIDE Measurement Configuration and Verification Manual
1. Measurement Type
2. Upper Full Scale Range (FSR)
3. Upper Danger Setpoint (Red Solid Line)
4. Upper Alert Setpoint (Amber Solid Line)
5. Lower Alert Setpoint (Amber Dashed Line)
6. Lower Danger Setpoint (Red Dashed Line)
7. Channel Indicator
8. Zero Point (Black Solid Line)
9. Lower Full Scale Range
10. Channel Measured Value
11. Channel Units
12. Page Number Sequence
4
Section 4 - Configuration
4. Configuration
Complementary Input Differential Expansion, or CIDE, uses both channels of the channel
pair to make a single composite differential expansion measurement.
5
CIDE Measurement Configuration and Verification Manual
Figure 4-4: Voltage Probe Curves for Upscale Towards Probe Option
6
Section 4 - Configuration
• The up scale direction for the Direct measured values is always "toward" the probe.
1
Not available on 3500/45E monitors connected to 3300 I/O modules.
7
CIDE Measurement Configuration and Verification Manual
4.2.2 Transducer
Type
• 3300XL 11 mm Proximitor* Sensor
• 3300XL 25 mm Proximitor Sensor
• 3300XL 50 mm Proximitor Sensor
• 3300 16 mm HTPS Sensor
• 7200 11 mm Proximitor Sensor
• 7200 14 mm Proximitor Sensor
• 25 mm Extended Range Proximitor Sensor
• 35 mm Extended Range Proximitor Sensor
• 50 mm Extended Range Proximitor Sensor
• 50 mm DE Proximitor Sensor
• Nonstandard
Customize Button
Use this button to adjust the Scale Factor of transducers. If you select Nonstandard as
the transducer type, you can also adjust the OK Limits. The Nonstandard transducer's
scale factor must be between 8.5 and 130 mV/mil. Also, there must be at least 2 volts
between the Upper and Lower OK Limits.
8
Section 4 - Configuration
9
CIDE Measurement Configuration and Verification Manual
Transducer Upper OK (V) Lower OK (V) Center Gap Voltage (V)
3300XL 50 mm -13.35 to -13.45 -1.30 to -1.40 -7.00
50 mm DE
Note: Assume +/- 50 mV accuracy for check tolerance
10
Section 4 - Configuration
4.3.4 Delay
Delay is the time for which a static value must remain at or above an over alarm level,
or below an under alarm level, before the monitor declares an alarm as active.
11
CIDE Measurement Configuration and Verification Manual
You can set the Alert time delay in 1 second increments (from 1 to 60 seconds) for all
available static values. Alert is the first level alarm that occurs when the transducer
signal level exceeds the selected Alert/Alarm 1 setpoint. You can set this setpoint on the
Setpoint screen.
You can set the Danger Time Delay at 500 millisecond increments from 1 to 60 seconds.
Danger is the second level alarm that occurs when the transducer signal level exceeds
the selected Danger/Alarm 2 setpoint. You can set this setpoint on the Setpoint screen.
The 100 ms (typical) option applies only to the Danger time delay and has the following
effects:
If the 100 ms option is OFF:
• You can set the Danger time delay in 1-second increments (from 1 to 60 seconds).
• You can set the Danger time delay for up to 2 available static values.
If the 100 ms option is ON:
• The software sets the Danger time delay to 100 ms.
• You can set the Danger time delay for only the primary static value.
4.3.5.1 Latching
Once a latching alarm is active, it will remain active even after the static value drops
below the configured setpoint level. The channel will remain in alarm until you use one
of the following methods to reset it:
• Pressing the RESET button on the System Monitor
• Closing the contact on the Power Input Module (PIM)
• Clicking the Reset button in the Operator Display software 1
• Issuing a reset command over Modbus
• Issuing a reset command through the Display Interface Module 1
• Issuing a reset command in the 3500 Rack Configuration Software
12
Section 4 - Configuration
1
3500 Only
4.3.5.2 Non-latching
When a non-latching alarm is active, it changes to inactive as soon as the static value
drops below the configured setpoint level.
4.3.6 OK Mode
Latching
If you configure a channel for Latching OK, then once the channel has gone Not OK, the
status will stay Not OK until you use one of the following methods to reset it:
• Pressing the RESET button on the System Monitor
• Closing the contact on the Power Input Module (PIM)
• Clicking the Reset button in the Operator Display software 1
• Issuing a reset command over Modbus
• Issuing a reset command through the Display Interface Module 1
• Issuing a reset command in the 3500 Rack Configuration Software
1
3500 Only
Non-latching
If you configure a channel for Non-latching OK, the OK status of that channel will track
the defined OK status of the transducer.
Click this check box to cause the monitor to clamp the Recorder Output for a Bypassed
channel to 2 mA.
Clear this check box to cause the monitor to use the selected clamp value for a
Bypassed channel.
14
Section 4 - Configuration
Setpoint CIDE
Number
Under Danger
4 Composite
NOTE
The setpoint over and under limits may be less than the linear range of the
transducer depending on the ramp angle and full-scale range.
You can set the composite measured value setpoints independently on each
channel of the channel pair. You must adjust setpoints on both channels of
the channel pair.
15
CIDE Measurement Configuration and Verification Manual
5. Verification
DANGER
High voltage present. Contact with high voltage can cause shock, burns, or
death. Do not touch exposed wires or terminals.
ADVISORY
1. Test levels will exceed alarm setpoint levels and activate alarms. This
could result in a relay contact state change.
2. Disconnecting field wiring will cause a Not OK condition.
Connect the power supplies and multimeter to the COM and SIG terminals of the two
channels of the channel pair with polarity as shown in the Figure below to simulate the
transducer signal. The test equipment outputs should be floating relative to earth
ground.
16
Section 5 - Verification
17
CIDE Measurement Configuration and Verification Manual
The advantage of using the Adjust Scale Factor screen is that you can use the bar
graphs to see the effect of your adjustments on the output signals of the channel.
The Cross Over Voltages (COVs) are the gap voltages that the monitor uses to determine
which transducer is “in range”. The “in range” transducer is the one that is at, or below
(more positive than), it’s COV. A COV is set on each channel of the channel pair. The
COVs are also the Zero Position Voltages for the Direct measured values.
The full-scale range of each Direct measured value is one-half of the Composite range
and the COVs define the middle point of the Composite range.
A zero reference voltage is also shown in the Composite values zero reference box in
the Verification screen. The value is derived from the COVs, is not adjustable, and is not
used for any maintenance or installation procedure. The COVs depend on the
Composite full-scale range, the transducer type and scale factor.
1. Connect and configure the channels then, after changes are completed, download
the configuration to the rack.
18
Section 5 - Verification
2. On the Variables + Alarms screen, enter a value in the Crossover Voltage box for
Crossover Voltage within the range specified below the box, use the up/down
arrows to scroll to the desired value or go to the Adjust function by clicking the
Adjust button at the right side of the COV field for the channel of interest.
The difference between the COV of the two channels must be less than ±0.60 volts.
Using the Adjust Button
If you use the Adjust function, you can adjust the Cross Over Voltage and see the
results.
1. Click the Adjust button. The Crossover Adjust screen is displayed.
2. Enter the voltage in the C.O. Volts box above the Direct bar graph display.
When you adjust the COVs you are defining the “switch point” (i.e., the zero reference for
the Direct measured values) and the midpoint of the Composite range. The Figure
shows the relationship of the Composite meter range to the Direct meter ranges and
the COVs. You should set the Cross Over Voltages as close as possible to the value
displayed in the COV text box in the CIDE Channel Pair Option screen.
Figure 5-11: Relationship of Composite Meter Range for Direct Meter Range and COVs
19
CIDE Measurement Configuration and Verification Manual
5.4.1 Composite
1. Disconnect the field wiring from the PWR, COM, and SIG channel terminals on the
I/O module.
2. Connect the test equipment and run the software as described in the section, “Test
Equipment and Software Setup."
3. Adjust the power supply voltage to be within the setpoint levels on the bar graph
display of the Verification screen.
You can usually do this by setting the power supplies to the cross over voltages for
each channel of the channel pair. Note that the Cross Over voltage is displayed over
the Direct bar graph display in the Verification screen. You can check each channel
of the channel pair by changing the selected channel using the Channel dropdown
list box in the Verification screen.
4. Press the RESET switch on the System Monitor. Verify that the OK LED is on, the
color of the bar graph indicator is green, and the Current Value field contains no
alarm indication.
5. Adjust the power supply voltage to just exceed the Over Alert/Alarm 1 setpoint level
and wait for 2 or 3 seconds after the alarm time delay expires. Verify that the color
of the bar graph indicator changes from green to yellow and that the Current Value
Field indicates an alarm.
6. Press the RESET switch. Verify that the color of the bar graph indicator remains
yellow and that the Current Value Field still indicates an alarm.
7. Adjust the power supply voltage to just exceed the Over Danger/Alarm 2 setpoint
level and wait for 2 or 3 seconds after the alarm time delay expires. Verify that the
color of the bar graph indicator changes from yellow to red and that the Current
Value Field indicates an alarm.
8. Press the RESET switch. Verify that the color of the bar graph indicator remains red
and that the Current Value Field still indicates an alarm.
9. Adjust the power supply voltage below the Over Alert setpoint levels. If the non-
latching option is configured, verify that the color of the bar graph indicator
changes to green and that the Current Value Box contains no indication of alarms.
Press the RESET switch to reset latching alarms.
10. Repeat steps 3 through 9 to test the Under Alert/Alarm 1 and Under Danger/Alarm
2 setpoints by adjusting the power supply voltage to exceed the Under Alarm
setpoint levels.
11. If you cannot verify any configured alarm, check the configured setpoints again. If
the monitor still does not alarm properly or fails any other part of this test, you
must replace the monitor. Refer to "If a Channel Fails a Verification Test" in your
monitor hardware manual.
20
Section 5 - Verification
12. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and
SIG channel terminals on the I/O module. Verify that the OK LED comes on and that
the OK relay energizes. Press the RESET switch to reset the OK LED.
13. Repeat steps 1 through 12 for all configured channels.
14. Disable the Enable Direct (Aux 1) Software Switch:
1. Close the Verification screen.
2. From the Utilities menu, select Software Switches.
3. Select the appropriate slot.
4. Disable Switch 5 (Enable Direct (Aux 1)).
5. Select Set to download the new switch setting.
21
CIDE Measurement Configuration and Verification Manual
Example 1
Channel Pair: (1,2)1
1
Channel Pair on a 3500/45E connected to 3300 I/O
module is (1,3).
Transducer Types: 35 mm (TSF = 20 mV/mil or 20 V/inch)
Composite Full-scale: 0.5 inch - 0 - 0.5 inch
Chan 1 COV: -11.6 V
Chan 2 COV: -11.8 V
Upscale Direction: Towards Probe 1
Example 2
Channel Pair: (1,2)1
1
Channel Pair on a 3500/45E connected to 3300 I/O
module is (1,3).
Transducer Types: 50 mm DE (TSF = 0.3937V/mm on channel 1 and
0.4055 V/mm on channel 2)
Composite Full-scale: 10 mm - 0 - 40 mm
Chan 1 COV: -11.64 V
Chan 2 COV: -11.94 V
Upscale Direction: Away from Probe 1
Channel 1 Direct Full-scale Volts = (-11.64) + (0.5) (0.3937 V/mm) (50 mm)
= -1.8 Vdc
Channel 2 Direct Full-scale Volts = (-11.94) + (0.5) (0.4055V/mm) (50 mm)
= -1.8 Vdc
Composite Full Scale = Channel 2 Direct Full Scale with Channel 1 more
negative than its COV
Composite Bottom Scale = Channel 1 Direct Full Scale with Channel 2 more
negative than its COV
22
Section 5 - Verification
NOTE
1. The Cross Over Voltage is the voltage input that will cause the reading
on the Direct bar graph display and Current Value Box to be zero. The
Cross Over Voltage is displayed in the COV box above the Direct value
bar graph for each channel of the channel pair. When both channels are
at the COV, the Composite bar graph display and Current Value Box
should indicate mid-scale (for example, if the scale is 4 mm - 0 - 16 mm,
a reading of 6 mm is mid-scale).
2. A value is also displayed in the Composite COV box above the
Composite bar graph. This value is not adjustable and is not used for
any installation or maintenance operation.
3. Use the Transducer Scale Factor displayed in the Scale Factor Box on
the Verification Screen for the appropriate channel when using the
formulas below.
4. Adjust the power supply voltages to match the voltage displayed in the COV. Volts
box for the Direct value on both channels. Verify that the Direct bar graph display
and the Current Value Box is reading 0 inches (0 mm) +/-1% for both channels of
the channel pair. Verify that the Composite bar graph display and Current Value Box
is reading mid-scale +/-1%.
5. Determine which channel is the upscale channel. On the upscale channel adjust the
power supply voltage to the Direct full-scale value calculated for that channel.
Adjust the power supply on the other channel to be more negative than its COV.
Verify that the Composite bar graph display and Current Value Box is reading full
scale +/-1%. If the recorder is configured, refer to Section 5.1.10 (Verify Recorder
Outputs) for steps to verify the recorder output.
Adjust the power supply voltage on both channels to the calculated full-scale
voltage. Verify that the Composite bar graph display and its Current Value Box is
reading full scale +/-Tc%. If the recorder output is configured, refer to Section "Verify
Recorder Outputs" in your hardware manual for steps to verify the recorder output.
Verify that the Direct bar graph displays and Current Value Boxes for both channels
are reading full scale +/-Tr%.
6. Determine which channel is the downscale channel. On the downscale channel
adjust the power supply voltage to the Direct full-scale value calculated for that
channel. Adjust the power supply on the other channel to be more negative than its
COV. Verify that the Composite bar graph display and Current Value Box is reading
bottom scale +/-1%. If the recorder is configured, refer to Section 5.1.10 (Verify
Recorder Outputs) for steps to verify the recorder output.
7. If the readings do not meet specifications, verify that the input signal is correct. If
the monitor still does not meet specifications or fails any other part of this test, you
must replace the monitor. See the section “If a Channel Fails a Verification Test” in
your hardware manual.
8. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and
SIG channel terminals on the I/O module. Verify that the OK LED comes on and that
the OK relay energizes. Press the RESET switch to reset the OK LED.
9. Repeat steps 1 through 8 for all configured channel pairs.
10. Disable the Enable Direct (Aux 1) Software Switch:
23
CIDE Measurement Configuration and Verification Manual
1. Close the Verification screen.
2. From the Utilities menu, select Software Switches.
3. Select the appropriate slot.
4. Disable Switch 5 (Enable Direct (Aux 1)).
5. Select Set to download the new switch setting.
NOTE
If the Danger Bypass is active, then the BYPASS LED will be on. All other
channels in the rack must be OK or bypassed for the OK relay to energize.
6. Verify that the OK relay on the System Monitor indicates OK (is energized). (See the
appropriate System Monitor manual for more information.)
7. Increase both power supply voltages (more negative) until the OK LED just goes off
(upper limit). Verify that the Channel OK State line in the Channel Status box reads
Not OK for both channels and that the OK Relay indicates Not OK. Verify that the
Upper OK limit voltage displayed on the Verification screen is equal to or more
positive than the input voltage.
Increase the power supply voltage (more negative) until the OK LED just goes off
(upper limit). Verify that the Channel OK State line on the Verification screen reads
Not OK and that the OK Relay indicates Not OK. Verify that Verification screen
displays an Upper OK Limit voltage that is equal to or more positive than the input
voltage.
24
Section 5 - Verification
8. Adjust both of the power supply voltages to -9.00 Vdc.
9. Press the RESET switch. Verify that the OK LED comes back on and that the OK relay
energizes. Verify that the Channel OK State line in the Channel Status section reads
OK.
10. Gradually decrease the power supply voltage on channel 1 (or 3 for pair 3,4 1) (less
negative) until the OK LED just goes off (lower limit). Verify that the Channel OK State
line in the Channel Status box reads Not OK and that the OK Relay indicates Not
OK. Verify that the Lower OK limit voltage displayed on the Verification screen is
equal to or more negative than the input voltage.
11. Increase the power supply voltage (more negative) to -9.00 Vdc on channel 1 (or 3
for pair 3,41).
12. Press the RESET switch. Verify that the OK LED comes back on and that the OK relay
energizes. Verify that the Channel OK State line in the Channel Status section reads
OK.
13. Gradually decrease the power supply voltage on channel 2 (or 4 for pair 3,4 1) (less
negative) until the OK LED just goes off (lower limit). Verify that the Channel OK State
line in the Channel Status box reads Not OK and that the OK Relay indicates Not
OK. Verify that the Lower OK limit voltage displayed on the Verification screen is
equal to or more negative than the input voltage.
14. Increase the power supply voltage (more negative) to -9.00 Vdc on channel 2 (or 4
for pair 3,41).
15. Press the RESET switch. Verify that the OK LED comes back on and that the OK relay
energizes. Verify that the Channel OK State line in the Channel Status section reads
OK.
16. If you cannot verify any configured OK limit, you must replace the monitor. Refer to
“If a Channel Fails a Verification Test” in your monitor hardware manual.
17. Repeat steps 2 through 13 for the other channel of the channel pair.
18. Disconnect the test equipment and reconnect the field wiring to the PWR, COM, and
SIG channel terminals on the I/O module. Verify that the OK LED comes on and that
the OK relay energizes. Press the RESET switch to reset the OK LED.
19. Repeat steps 1 through15 for all channel pairs.
20. Return the bypass switches for all configured channels back to their original
settings.
21. Disable the Enable Direct (Aux 1) Software Switch:
1. Close the Verification screen.
2. From the Utilities menu, select Software Switches.
3. Select the appropriate slot.
4. Disable Switch 5 (Enable Direct (Aux 1)).
5. Select Set to download the new switch setting.
25
CIDE Measurement Configuration and Verification Manual
1
Channels 3 and 4 not available on /45E monitors connected to 3300 I/O modules.
Table 5-4: CIDE Default OK Limits Table
Transducer (without barriers) Lower OK Limit (volts) Upper OK Limit (volts)
7200 5mm, 8 mm -1.23 to -1.33 -18.99 to -19.09
3300 XL 8 mm, 11 mm
3300 8 mm
7200 11 mm -3.50 to -3.60 -20.34 to -20.44
7200 14 mm -1.6 to -1.7 -18.0 to -18.1
3300 16 mm HTPS
25 mm, 35 mm, 50 mm -1.30 to -1.40 -12.5 to -12.6
50 mm DE -1.30 to -1.40 -13.35 to -13.45
Note: Assume +/- 50 mV accuracy for check tolerance.
26